p.4262025 Residential Appendices (e) Isolation valves shall be fully functional. Extended stem isolation valves shall be installed on
p.4272025 Residential Appendices (a) More than one circulation loop may be installed. Each loop shall have its own pump and
p.426hot water piping or where pipe insulation is required.
p.427controls.
p.427(b) Verify that the pump, demand controls and thermo-sensor are present. Manual switches
p.426RA3.6.4 Verified Central Parallel Piping (PP-H)
p.427shall be located in the kitchen, all bathrooms, and any hot water fixture location that is at least 20 feet (measured along the hot water piping) from the water heater.
p.426This measure expands on the requirements for parallel piping systems that use one or more central manifolds with individual runs from the manifold to each point of use. Visual inspection shall verify that all supply lines of the parallel piping system meet the specific installation requirements listed below:
p.427(c) Manual controlled systems may be activated by wired or wireless button mechanisms.
p.427Verify that manual controls have standby power of 1 watt or less.
p.427(d) Verify that pump and control placement for the demand recirculation meets one of the
p.426(a) The measured length of pipe from the water heater to each central manifold shall not
p.427following criteria:
p.426exceed 5 feet (measured to the nearest half foot).
p.4271. When a dedicated return line has been installed the pump, controls and thermo- sensor are installed at the end of the supply portion of the recirculation loop (typically under a sink); or
p.426(b) The hot water distribution system piping from the manifold to the fixtures and appliances
p.426must take the most direct path. For example, in a house with more than 1-story and the water heater in the garage, this requirement would exclude running hot water supply piping from the manifold to the attic, and then running the line back down to a first floor point of use.
p.4272. The pump and controls are installed on the return line near the water heater and the thermo-sensor is installed in an accessible location as close to the end of the supply portion of the recirculation loop as possible (typically under a sink), or
p.4261. The hot water distribution piping must be separated by at least two inches from any other hot water supply piping, and at least six inches from any cold water supply piping.
p.4273. When the cold water line is used as the return, the pump, demand controls and thermosensor shall be installed in an accessible location at the end of supply portion of the hot water distribution line (typically under a sink).
p.426(c) The ECC-rater shall also verify that other hot water piping is insulated and installed to
p.426meet the requirements of RA3.6.2.
p.427(e) Verify that a check valve is installed in the recirculation loop to prevent unintentional
p.427circulation of the water (thermo-siphoning) and back flow when the system is not operating. This check valve may be included with the pump.
p.426RA3.6.5 Verified Compact Hot Water Distribution System Expanded Credit (CHWDS-H-EX)
p.426To meet the Compact Hot Water Distribution System Expanded Credit eligibility requirements, the requirements in RA4.4.6 must be met. In addition, the following field verifications are required:
p.427(f) The ECC-rater shall also verify that the supply portion of each circulation loop, the first
p.427five feet of branches off the loop and the dedicated return line are insulated based on the conductivity range in TABLE 120.3-A, the insulation level shall be selected from the fluid temperature range based on the thickness requirements in TABLE 120.3-A and the insulation shall be installed in accordance with RA3.6.2. Other hot water piping shall meet the requirements of §150.0(j) and be installed in accordance with RA3.6.2. Insulation is not required on the cold water line when it is used as the return.
p.426(a) No hot water piping larger than 1 inch diameter is allowed,
p.426(b) Length of 1 inch diameter piping is limited to 8 ft or less,
p.426(c) Two and three story buildings cannot have hot water distribution piping in the attic,
p.426unless the water heater is also located in the attic, and
p.427(g) The hot water distribution system piping from the water heater(s) to the fixtures and
p.426(d) Eligible recirculating systems must be Verified Demand Recirculation: Manual Control
p.427appliances must take the most direct path. For example, in a house with more than 1 story and the water heater in the garage, this requirement would exclude running hot water supply piping from the water heater to the attic, and then running the line back down to a first floor point of use.
p.426RA3.6.6 Verified Demand Recirculation; Manual Control (R-DRmc-H)
p.426Demand controlled recirculation systems shall operate “on-demand”, meaning that pump operation shall be initiated shortly prior to the hot water draw. The recirculation pump can be located external to the water heater or be integral to the water heater. The controls shall operate on the principal of shutting off the pump with a sensed rise in pipe temperature (Delta-T). For this verification process, a manual switch is required.
p.427(h) Verify that manual controls initiate pump operation by pressing one of the manual
p.427controls and observing that the pump turns on and then shuts off in accordance with one of the two methods listed:
p.4271. After the pump has been activated, the controls shall allow the pump to operate until the water temperature at the thermo-sensor rises not more than 10oF (5.6 oC) above the initial temperature of the water in the pipe, or
p.426Verification shall include:
p.426– Residential Field Verification and Diagnostic Test Protocolsp.427
p.427Appendix RA3– Residential Field Verification and Diagnostic Test Protocols