JA10.6 Calculations

TABLE JA-10 FLICKER DATA TO CALIFORNIA ENERGY COMMISSIONBE RECORDED AND SUBMITTED TO THE
DataUnits/Format
Test DateUse middle endian format (Month/Day/Year).
Test OperatorCompany Name, Contact Name, Address, Phone Number, e-mail address
Entity submitting resultsCompany Name, Contact Name, Address, Phone Number, e-mail address
Entity submitting resultsManufacturer or Brand
Tested lighting system component: DimmerDimmer type, Manufacturer or Brand, model number
Tested lighting system component: light source (lamp or light engine)Light source type (lamp, light engine, etc), Manufacturer or Brand, model number
Tested lighting system component: Ballast or DriverBallast or Driver, Manufacturer or Brand, model number
Recording intervalSeconds (no greater than 0.00005 seconds)
Equipment Measurement PeriodSeconds (no less than 1 second)
Fraction of rated light output integrated over measurement period at 100%, 20% and minimum fraction of light output.Fraction of rated light output integrated over measurement period at 100%, 20% and minimum fraction of light output.
Amplitude modulation unfilteredCalculated percent amplitude modulation unfiltered for each dimming level (100%, 20% and minimum fraction of light output)
Percent amplitude modulation with 1,000 Hz cut-offCalculated percent amplitude modulation, data filtered with a 1,000 Hz cut-off frequency for each dimming level: (100%, 20%, and minimum fraction of light output)
Percent amplitude modulation with 400 Hz cut-offCalculated percent amplitude modulation, data filtered with a 400 Hz cut-off frequency for each dimming level: (100%, 20%, and minimum fraction of light output)
Percent amplitude modulation with 200 Hz cut-offCalculated percent amplitude modulation, data filtered with a 200 Hz cut-off frequency for each dimming level: (100%, 20% and minimum fraction of light output)
Percent amplitude modulation with 90 Hz cut-offCalculated percent amplitude modulation, data filtered with a 90 Hz cut-off frequency for each dimming level: (100%, 20% and minimum fraction of light output)
Percent amplitude modulation with 40 Hz cut-offCalculated percent amplitude modulation, data filtered with a 40 Hz cut-off frequency for each dimming level: (100%, 20% and minimum fraction of light output)

p.250Lamp light output shall be stabilized in advance of taking measurements at each dimming level. Light output shall be considered stabilized when consecutive measurements taken at one minute intervals deviate by no more than 0.5%.

p.250Recording interval: Measured data shall be recorded to a digital file with an interval between each measurement no greater than 0.00005 sec (50 microseconds) corresponding to an equipment measurement rate of no less than 20kHz and capture at least 1 second of data.

p.250For each dimming level after the lamps have stabilized, record lighting measurements (in footcandles or volts) from test equipment with readings taken at intervals of no greater than 50 microseconds. These readings shall be recorded for a test period of no less than one second.

p.250JA10.6 Calculations

p.252(This page intentionally left blank.)

p.250Perform the following data manipulation and calculation tasks for each dimming level (100 percent, 20 percent and minimum dimming level claimed by the manufacturer):

p.250Calculate percent amplitude modulation (percent flicker) of unfiltered data over the duration of the test for a given dimming level using the following equation:

p.250Percent Amplitude Modulation = 100 x (Max – Min)/(Max + Min)

p.250Where:

p.250Max is the maximum recorded light level or voltage from the test apparatus during the duration of the test for a given dimming level.

p.250Min is the minimum recorded light level or voltage from the test apparatus during the duration of the test for a given dimming level.

p.250Conduct a Fourier analysis to transform data for each dimming level into the frequency domain.

p.250Filter frequency data to evaluate the data under four additional different conditions: frequencies under 40 Hz (data above 40 Hz is set to 0), and frequencies under 90 Hz,

p.250Perform inverse Fourier transform to place data back in time domain.

p.250Calculate percent amplitude modulation on resulting time domain data for each filtered dataset over the full sampling duration.

p.250JA10.7 Test Report and Data Format

p.250For all systems where reporting of flicker is required, the test data shall be submitted to the California Energy Commission in the format specified in Table JA-10. For two years from the date of certification, the entity submitting the test report shall keep all documentation required for compliance, stored and shall provide copies of this documentation to the Energy Commission within 10 days of written request received from the Commission. This documentation shall also include for each measured system, a digital file containing the raw photometric data as described in Section JA10.5.

p.250Appendix JA10 – Test Method for Measuring Flicker of Lighting Systems and Reporting Requirementsp.251

p.251Appendix JA10 – Test Method for Measuring Flicker of Lighting Systems and Reporting Requirementsp.252

p.252Appendix JA10 – Test Method for Measuring Flicker of Lighting Systems and Reporting Requirements