NOTE: Section 160.2 is not applicable to townhouses or dwellings that contain two dwelling units.

Scanned crop of table from PDF page 482
Text in this table

SECTION 160.2 – MANDATORY REQUIREMENTS FOR VENTILATION AND INDOOR AIR QUALITY or grilles located no more than 10 feet above a walking surface inside a space specified above comply with this requirement. Exception to Section 160.2(b)2Axia: Systems that require servicing from inside the attic shall have the following: 1. A Fault Indicator Display (FID) meeting the requirements of Reference Appendix JA 17; and 2. An attic access door located in a wall or, where attic access is provided through a ceiling, an attic access hatch that includes an integrated ladder; and 3. A walkway from the attic access door to the HRV/ERV. b. IAQ system component accessibility. Fans, motors, heat exchangers, filters and recovery cores shall meet all applicable requirements of California Mechanical Code 304.0 accessibility of service. B. Dwelling unit field verification and diagnostic testing. i. The whole-dwelling unit ventilation airflow required by Section 160.2(b)2Aiv or 160.2(b)2Av shall be confirmed through field verification and diagnostic testing in accordance with Reference Appendix RA3.7.4.1.1 or NA2.2.4.1.1 as applicable for supply and exhaust systems or RA3.7.4.1.2 or NA2.2.4.1.2 as applicable for balanced systems. Balanced mechanical ventilation system airflow shall be the average of the supply fan and exhaust fan flows. Ventilation airflow of systems with multiple operating modes shall be tested in all modes designed to comply with the required ventilation airflows. ii. Kitchen local mechanical exhaust—vented range hoods. Vented range hoods installed to comply with local mechanical exhaust requirements specified in Section 160.2(b)2Avi shall be field verified in accordance with Reference Appendix RA3.7.4.3 or NA2.2.4.1.4 as applicable to confirm the model is rated by HVI or AHAM to comply with the following requirements: a. The minimum ventilation airflow rate as specified by Section 160.2(b)2Avi, or alternatively the minimum capture efficiency as specified by Section 160.2(b)2Avi; and b. The maximum sound rating as specified in Section 160.2(b)2Avif. iii. Heat recovery ventilation (HRV) and energy recovery ventilation (ERV) system fan efficacy. At a minimum, systems with heat or energy recovery serving a single dwelling unit shall have a fan efficacy of ≤1.0 W/cfm as confirmed by field verification in accordance with Reference Appendix RA3.7.4.4 or NA2.2.4.1.5 as applicable. If Section 170.2(c)3Biva requirements are applicable to the dwelling unit, then field verification shall instead confirm compliance with the maximum fan efficacy and minimum sensible recovery efficiency specified in Section 170.2(c)3Biva in accordance with the procedures specified in Reference Appendix RA3.7.4.4 or NA2.2.4.1.5 as applicable.

Equation on PDF page 476: Aface = air filter face area, the product of air filter nominal length × nominal width, ft2.

Equation text: Aface = air filter face area, the product of air filter nominal length × nominal width, ft2.

Needs visual review

p.476
Equation on PDF page 476: Qfilter = design airflow rate for the air filter, ft3/min

Equation text: Qfilter = design airflow rate for the air filter, ft3/min

Needs visual review

p.476
Equation on PDF page 476: Vface = air filter face velocity ≤ 150 ft/min

Equation text: Vface = air filter face velocity ≤ 150 ft/min

Needs visual review

p.476
Equation on PDF page 478: Qtot = 0.03Afloor + 7.5(Nbr + 1) (Equation 160.2-B)

Equation text: Qtot = 0.03Afloor + 7.5(Nbr + 1) (Equation 160.2-B)