C. For other modular lighting systems with power supplied by a driver, power supply or transformer, including but not limited to low-voltage lighting systems, the wattage of the system shall be the maximum rated input wattage of the driver, power supply or transformer published in the manufacturer’s catalogs, as specified by UL 2108 or 8750. Exception to Section 130.0(c)6: For power-over-Ethernet lighting systems, power provided to installed nonlighting devices may be subtracted from the total power rating of the power-over-Ethernet system. 7. For all other lighting equipment not addressed by Sections 130.0(c)2 through 6, the wattage of the lighting equipment shall be the maximum rated wattage of the lighting equipment, or operating input wattage of the system, labeled in accordance with Section 130.0(c)1, or published in manufacturer’s catalogs, based on independent testing lab reports as specified by UL 1574, 1598, 2108 or 8750, or IES LM-79. (d) Lighting controls. All lighting controls and equipment shall comply with the applicable requirements in Sections 110.9, 130.1 and 130.2, and shall be installed in accordance with any applicable manufacturer instructions. (e) Energy Management Control System (EMCS). An EMCS may be installed to comply with the requirements of one or more lighting controls if it meets the following minimum requirements: 1. Provides all applicable functionality for each specific lighting control or system for which it is installed in accordance with Sections 110.9, 130.1 and 130.2; and 2. Complies with all applicable lighting control installation requirements in accordance with Section 130.4 for each specific lighting control or system for which it is installed; and 3. Complies with all applicable application requirements for each specific lighting control or system for which it is installed, in accordance with Part 6. Note: Authority: Sections 25213, 25218, 25218.5, 25402 and 25402.1, Public Resources Code. Reference: Sections 25007, 25008, 25218.5, 25310, 25402, 25402.1, 25402.4, 25402.5, 25402.8, and 25943, Public Resources Code.

p.273(c) Luminaire classification and power. Luminaires shall be classified, and their wattage shall be

p.274i. 30 watts per linear foot of track or plug-in busway; or

p.273determined as follows:

p.274ii. the rated wattage of all of the luminaires included in the system, where the

p.2731. Luminaire wattage shall be labeled as follows:

p.274luminaire wattage is determined as specified in Section 130.0(c)1.

p.273A. The maximum rated wattage or relamping rated wattage of a luminaire shall be

p.274B. For line-voltage lighting track and plug-in busway served by a track lighting integral

p.273listed on a permanent, preprinted, factory installed label, as specified by UL 1574, 1598, 2108 or 8750, as applicable; and

p.274current limiter or a dedicated track lighting supplementary overcurrent protection panel, the wattage shall be determined as follows:

p.273B. The factory-installed maximum rated wattage or relamping rated wattage label shall

p.274i. The volt-ampere rating of the current limiter as specified by UL 1077; or

p.273not consist of peel-off or peel-down layers or other methods that allow the rated wattage to be changed after the luminaire has been shipped from the manufacturer.

p.274ii. The sum of the ampere (A) rating of all of the current protection devices times

p.274the branch circuit voltages for track lighting supplementary overcurrent protection panel.p.275