SECTION 130.2 – OUTDOOR LIGHTING CONTROLS AND EQUIPMENT

p.2841. Daylight availability. All installed outdoor lighting shall be controlled by a photo control, astronomical time-switch control, or other control capable of automatically shutting OFF the outdoor lighting when daylight is available.

p.283SECTION 130.2 – OUTDOOR LIGHTING CONTROLS AND EQUIPMENT

p.283Nonresidential and hotel/motel buildings shall comply with the applicable requirements of Sections 130.2(a) through 130.2(c).

p.2842. Automatic scheduling controls.

p.283(a) Reserved.

p.284A. Automatic scheduling controls shall be installed for all outdoor lighting. Automatic

p.283(b) Luminaire shielding requirements. All outdoor luminaires of 6,200 initial luminaire lumens or

p.284scheduling controls may be installed in combination with motion sensing controls or other outdoor lighting controls.

p.283greater shall comply with backlight, uplight and glare (BUG) (in accordance with ANSI/IES TM-15- 20, Annex A) requirements in accordance with Title 24, Part 11, Section 5.106.8.

p.284B. Automatic scheduling controls shall be capable of reducing the outdoor lighting power by

p.28450 to 90 percent, and separately capable of turning the lighting OFF, during scheduled unoccupied periods.

p.284C. Automatic scheduling controls shall allow scheduling of a minimum of two nighttime

p.284periods with independent lighting levels, and may include an override function that turns lighting ON during its scheduled dim or OFF state for no more than two hours when an override is initiated.

p.2843. Motion sensing controls.

p.284A. Motion sensing controls shall be installed for outdoor luminaires providing lighting for

p.284general hardscape, parking lots, outdoor sales lots, vehicle service station hardscape, service station canopies, sales canopies, and non-sales canopies, where the bottom of the luminaire is mounted 24 feet above grade or lower.

p.283A. Where the existing luminaire does not meet the luminaire BUG requirements in Section

p.283130.2(b); and

p.283B. Spacing between existing poles is greater than six times the mounting height of the existing

p.284B. Motion sensing controls shall be capable of reducing the outdoor lighting power of each

p.283luminaires; and

p.284controlled luminaire by 50 to 90 percent, and separately capable of turning the luminaire OFF, during unoccupied periods.

p.283C. Where no additional poles are being added to the site; and

p.283D. Where new wiring to the luminaires is not being installed; and

p.284C. Motion sensing controls shall be capable of reducing the lighting to its dim or OFF state no

p.284longer than 15 minutes after the area has been vacated, and of returning the lighting to its ON state when the area becomes occupied.

p.283E. Provided that the connected lighting power wattage is not increased.

p.284D. No more than 1,500 watts of lighting power shall be controlled by a single sensor or as a

p.284single zone.

p.283(c) Controls for outdoor lighting. Outdoor lighting shall be independently controlled from other

p.283electrical loads, and the controls for outdoor lighting shall meet the following functional requirements:

p.283SECTION 130.2 – OUTDOOR LIGHTING CONTROLS AND EQUIPMENTSECTION 130.2 – OUTDOOR LIGHTING CONTROLS AND EQUIPMENT

p.284SECTION 130.2 – OUTDOOR LIGHTING CONTROLS AND EQUIPMENT