p.401space, the newly installed, replaced, or altered lighting shall meet the requirements of Section 120.6(h)5.
p.400SECTION 141.1 – REQUIREMENTS FOR COVERED PROCESSES IN ADDITIONS, ALTERATIONS TO EXISTING NONRESIDENTIAL, AND HOTEL/MOTEL BUILDINGS
p.400Covered processes in additions or alterations to existing buildings that will be nonresidential, and hotel/motel occupancies shall comply with the applicable subsections of section 120.6 and 140.9.
p.401(d) Process piping. Newly installed process heating and process cooling system piping and
p.401pipes relocated as part of an alteration shall meet the requirements of Section 120.3.
p.400(a) Lab and Process Facility Exhaust Systems. Additions and alterations to existing laboratories
p.400and factories shall meet the requirements of Section 140.9(c).
p.400(b) Computer Rooms. All newly installed computer room cooling systems and uninterruptible
p.400power supply systems in additions/alterations shall meet the requirements of Sections 120.6(j), 140.9(a)2, and 140.9(a)4 and comply with item 1 below.
p.4001. Economizers. Each individual cooling system primarily serving computer rooms in an existing building shall include either:
p.400A. An integrated air economizer capable of partial cooling when additional mechanical
p.400cooling is required and capable of providing 100 percent of the expected system cooling load up to 80°F room supply air temperature at outside air temperatures of 55°F dry-bulb and below or 50°F wet-bulb and below, and be equipped with a fault detection and diagnostic system as specified by section 120.2(i); or
p.400B. An integrated water economizer capable of partial cooling when additional
p.400mechanical cooling is required and capable of providing 100 percent of the expected system cooling load up to 80°F room supply air temperature at outside air temperatures of 40°F dry-bulb and below or 35°F wet-bulb and below.
p.400(c) Controlled Environment Horticulture Spaces.
p.4001. Indoor Growing, Space-Conditioning Systems and Dehumidification. All newly installed heating, ventilation, air conditioning systems or dehumidification systems in buildings with indoor growing shall meet the applicable requirements of Section 120.6(h)1 and 120.6(h)2.
p.4002. Greenhouses, Building Envelope and Space-Conditioning Systems. A greenhouse being converted to a conditioned greenhouse or additions to a conditioned greenhouse shall meet the requirements of Sections 120.6(h)3 and 120.6(h)4.
p.4003. Indoor Growing and Greenhouses, Horticultural Lighting. When alterations to horticultural lighting systems increase lighting wattage or include adding, replacing, or altering 10 percent or more of the horticultural luminaires serving an enclosedp.401