p.289receptacle. Where receptacles are installed in modular furniture in open office areas, at least one controlled receptacle shall be installed at each workstation; and
p.288SECTION 130.5 –ELECTRICAL POWER DISTRIBUTION SYSTEMS
| ELECTRICAL LOAD TYPE | ELECTRICAL SERVICES RATED 50 kVA OR LESS | ELECTRICAL SERVICES RATED MORE THAN 50 kVA AND LESS THAN OR EQUAL TO 250 kVA | ELECTRICAL SERVICES RATED MORE THAN 250 kVA AND LESS THAN OR EQUAL TO 1000 kVA | ELECTRICAL SERVICES RATED MORE THAN 1000 kVA |
|---|---|---|---|---|
| Other individual non- HVAC loads or appliances rated 25 kVA or greater | Not required | All loads in aggregate | All loads in aggregate | All loads in aggregate |
| Industrial and commercial load centers 25 kVA or greater, including theatrical lighting installations and commercial kitchens | Not required | All loads in aggregate | All loads in aggregate | All loads in aggregate |
| Renewable power source (net or total) | Each group | Each group | Each group | Each group |
| Loads associated with renewable power source | Not required | All loads in aggregate | All loads in aggregate | All loads in aggregate |
| Charging stations for electric vehicles | All loads in aggregate | All loads in aggregate | All loads in aggregate | All loads in aggregate |
| Metering Functionality | Electrical Services rated 50 kVA or less | Electrical Services rated more than 50kVA and less than or equal to 250 kVA | Electrical Services rated more than 250 kVA and less than or equal to 1000kVA | Electrical Services rated more than 1000kVA |
|---|---|---|---|---|
| Instantaneous (at the time) kW demand | Required | Required | Required | Required |
| Historical peak demand (kW) | Not required | Not required | Required | Required |
| Tracking kWh for a user-definable period. | Required | Required | Required | Required |
| kWh per rate period | Not required | Not required | Not required | Required |
p.288Nonresidential and hotel/motel buildings shall comply with the applicable requirements of Sections 130.5(a) through 130.5(e).
p.2893. Provide a permanent marking for controlled receptacles or circuits to differentiate them from uncontrolled receptacles or circuits; and
p.288(a) Service electrical metering. Each electrical service or feeder shall have a permanently
p.291Other individual non- HVAC loads or
p.2894. For hotel and motel guest rooms, install controlled receptacles for at least one-half of the 120-volt receptacles in each guestroom. Electric circuits serving controlled receptacles in guestrooms shall have captive card key controls, occupant sensing controls, or automatic controls so the power is switched OFF no longer than 20 minutes after the guestroom has been vacated.
p.288installed metering system which measures electrical energy use in accordance with Table 130.5-A.
p.289i. Receptacles specifically for refrigerators and water dispensers in kitchen area.
p.289ii. Receptacles located a minimum of six feet above the floor that are specifically for
p.288(b) Separation of electrical circuits for electrical energy monitoring. Electrical power
p.289clocks.
p.288distribution systems shall be designed so that measurement devices can monitor the electrical energy usage of load types according to Table 130.5-B.
p.289iii. Receptacles for network copiers, fax machines, A/V and data equipment other than
| ELECTRICAL LOAD TYPE | ELECTRICAL SERVICES RATED 50 kVA OR LESS | ELECTRICAL SERVICES RATED MORE THAN 50 kVA AND LESS THAN OR EQUAL TO 250 kVA | ELECTRICAL SERVICES RATED MORE THAN 250 kVA AND LESS THAN OR EQUAL TO 1000 kVA | ELECTRICAL SERVICES RATED MORE THAN 1000 kVA |
|---|---|---|---|---|
| Lighting including exit and egress lighting and exterior lighting | Not required | All lighting in aggregate | All lighting disaggregated by floor, type or area | All lighting disaggregated by floor, type or area |
| HVAC systems and components including chillers, fans, heaters, furnaces, package units, cooling towers and circulation pumps associated with HVAC | Not required | All HVAC in aggregate | All HVAC in aggregate and each HVAC load rated at least 50 kVA | All HVAC in aggregate and each HVAC load rated at least 50 kVA |
| Domestic and service water system pumps and related systems and components | Not required | All loads in aggregate | All loads in aggregate | All loads in aggregate |
| Plug load including appliances rated less than 25 kVA | Not required | All plug load in aggregate Groups of plug loads exceeding 25 kVA connected load in an area less than 5000 sf | All plug load separated by floor, type or area Groups of plug loads exceeding 25 kVA connected load in an area less than 5000 sf | All plug load separated by floor, type or area All groups of plug loads exceeding 25 kVA connected load in an area less than 5000 sf |
| Elevators, escalators, moving walks and transit systems | Not required | All loads in aggregate | All loads in aggregate | All loads in aggregate |
p.289personal computers in copy rooms.
p.289iv. Receptacles on circuits rated more than 20 amperes.
p.289v. Receptacles connected to an uninterruptible power supply (UPS) that are intended to
p.289be in continuous use, 24 hours per day/365 days per year, and are marked to differentiate them from other uncontrolled receptacles or circuits.
p.288(c) Voltage drop. The maximum combined voltage drop on both installed feeder conductors and
p.288branch circuit conductors to the farthest connected load or outlet shall not exceed 5 percent.
p.289(e) Demand responsive controls and equipment. See Section 110.12 for requirements for
p.289demand responsive controls and equipment, including demand responsive controls for controlled receptacles.
p.288(d) Circuit controls for 120-volt receptacles and controlled receptacles. In all buildings, both
p.288controlled and uncontrolled 120 volt receptacles shall be provided in office areas, lobbies, conference rooms, kitchen areas in office spaces and copy rooms. Additionally, hotel/motel guest rooms shall comply with Section 130.5(d)4. Plug-in strips and other plug-in devices shall not be used to comply with the requirements of Section 130.5(d). Controlled receptacles shall meet the following requirements, as applicable:
p.2881. Install a control capable of automatically shutting OFF the controlled receptacles when the space is typically unoccupied, either at the receptacle or circuit level. When an automatic time switch control is installed it shall incorporate an override control that allows the controlled receptacle to remain ON for no more than 2 hours when an override is initiated and an automatic holiday “shut-OFF” feature that turns OFF all loads for at least 24 hours and then resumes the normally scheduled operation. Countdown timer switches shall not be used to comply with the automatic time switch control requirements; and
p.2882. Install at least one controlled receptacle within 6 feet from each uncontrolled receptacle or install a multiple-receptacle outlet with at least one controlled and one uncontrolledp.289
p.288SECTION 130.5 –ELECTRICAL POWER DISTRIBUTION SYSTEMS
p.290SECTION 130.5 –ELECTRICAL POWER DISTRIBUTION SYSTEMS