p.535Section 160.6 – Mandatory Requirements for Electric Power Distribution Systems
| Electrical Load Type | Electrical Services1 rated 50 kVA or less | Electrical Services1 rated more than 50kVA and less than or equal to 250 kVA | Electrical Services1 rated more than 250 kVA and less than or equal to 1000kVA | Electrical Services1 rated more than 1000kVA |
|---|---|---|---|---|
| Lighting including exit and egress lighting and exterior lighting | Not required | All lighting in aggregate | All lighting disaggregated by floor, type or area | All lighting disaggregated by floor, type or area |
| HVAC systems and components including chillers, fans, heaters, furnaces, package units, cooling towers, and circulation pumps associated with HVAC | Not required | All HVAC in aggregate | All HVAC in aggregate and each HVAC load rated at least 50 kVA | All HVAC in aggregate and each HVAC load rated at least 50kVA |
| Domestic and service water system pumps and related systems and components | Not required | All loads in aggregate | All loads in aggregate | All loads in aggregate |
| Plug load including appliances rated less than 25 kVA | Not required | All plug load in aggregate Groups of plug loads exceeding 25 kVA connected load in an area less than 5000 sf | All plug load separated by floor, type or area Groups of plug loads exceeding 25 kVA connected load in an area less than 5000 sf | All plug load separated by floor, type or area All groups of plug loads exceeding 25 kVA connected load in an area less than 5000 sf |
p.535Multifamily buildings shall comply with the applicable requirements of Sections 160.6(a) through 160.6(e).
p.535(a) Service electrical metering. Each electrical service or feeder that provides power to the common
p.535use areas (interior and exterior) shall have a permanently installed metering system that measures electrical energy use in accordance with Table 160.6-A.
p.535TABLE 160.6-A MINIMUM REQUIREMENTS FOR METERING OR SUBMETERING OF ELECTRICAL
| Metering Functionality | Electrical Services1 rated 50 kVA or less | Electrical Services1 rated more than 50kVA and less than or equal to 250 kVA | Electrical Services1 rated more than 250 kVA and less than or equal to 1000kVA | Electrical Services1 rated more than 1000kVA |
|---|---|---|---|---|
| Instantaneous (at the time) kW demand | Required | Required | Required | Required |
| Historical peak demand (kW) | Not required | Not required | Required | Required |
| Tracking kWh for a user-definable period. | Required | Required | Required | Required |
| kWh per rate period | Not required | Not required | Not required | Required |
p.536Elevators, escalators, moving walks, and transit systems
p.536All loads in
p.536All loads in
p.536All loads in
p.536aggregate
p.536aggregate
p.536aggregate
p.536Renewable power source (net or total)
p.536Each group Each group Each group Each group
p.536Loads associated with renewable power source
p.536All loads in
p.536All loads in
p.536All loads in
p.5351 “Electrical Services” applies to the building service-entrance rating or to the submetering service. For a building with submetering, this applies to the submetering service size to the common use areas.
p.536aggregate
p.536aggregate
p.536aggregate
p.536Charging stations for electric vehicles
p.536All loads in
p.536All loads in
p.536All loads in
p.536All loads in
p.536aggregate
p.536aggregate
p.536aggregate
p.536aggregate 1 “Electrical Services” applies to the building service-entrance rating or to the submetering service. For a building with submetering, this applies to the submetering service size to the common use area.
p.535(b) Separation of electrical circuits for electrical energy monitoring. Electrical power distribution
p.535systems shall be designed so that measurement devices can monitor the electrical energy usage of load types according to Table 160.6-B.
p.536(c) Voltage drop. The maximum combined voltage drop on both installed feeder conductors and
p.536branch circuit conductors to the farthest connected load or outlet shall not exceed 5 percent.
p.536(d) Circuit controls for 120-volt receptacles and controlled receptacles. In all common areas, both
p.536controlled and uncontrolled 120 volt receptacles shall be provided in office areas, lobbies,
p.535SECTION 160.6 – MANDATORY REQUIREMENTS FOR ELECTRIC POWER DISTRIBUTION SYSTEM
p.536SECTION 160.6 – MANDATORY REQUIREMENTS FOR ELECTRIC POWER DISTRIBUTION SYSTEM