Section 160.6 – Mandatory Requirements for Electric Power Distribution Systems

p.535Section 160.6 – Mandatory Requirements for Electric Power Distribution Systems

MINIMUM REQUIREMENTS FOR SEPARATION OF ELECTRICAL LOAD p.536 Download CSV
Electrical Load TypeElectrical Services1 rated 50 kVA or lessElectrical Services1 rated more than 50kVA and less than or equal to 250 kVAElectrical Services1 rated more than 250 kVA and less than or equal to 1000kVAElectrical Services1 rated more than 1000kVA
Lighting including exit and egress lighting and exterior lightingNot requiredAll lighting in aggregateAll lighting disaggregated by floor, type or areaAll lighting disaggregated by floor, type or area
HVAC systems and components including chillers, fans, heaters, furnaces, package units, cooling towers, and circulation pumps associated with HVACNot requiredAll HVAC in aggregateAll HVAC in aggregate and each HVAC load rated at least 50 kVAAll HVAC in aggregate and each HVAC load rated at least 50kVA
Domestic and service water system pumps and related systems and componentsNot requiredAll loads in aggregateAll loads in aggregateAll loads in aggregate
Plug load including appliances rated less than 25 kVANot requiredAll plug load in aggregate Groups of plug loads exceeding 25 kVA connected load in an area less than 5000 sfAll plug load separated by floor, type or area Groups of plug loads exceeding 25 kVA connected load in an area less than 5000 sfAll plug load separated by floor, type or area All groups of plug loads exceeding 25 kVA connected load in an area less than 5000 sf

p.535Multifamily buildings shall comply with the applicable requirements of Sections 160.6(a) through 160.6(e).

p.535(a) Service electrical metering. Each electrical service or feeder that provides power to the common

p.535use areas (interior and exterior) shall have a permanently installed metering system that measures electrical energy use in accordance with Table 160.6-A.

p.535TABLE 160.6-A MINIMUM REQUIREMENTS FOR METERING OR SUBMETERING OF ELECTRICAL

MINIMUM REQUIREMENTS FOR METERING OR SUBMETERING OF ELECTRICAL LOAD p.535 Download CSV
Metering FunctionalityElectrical Services1 rated 50 kVA or lessElectrical Services1 rated more than 50kVA and less than or equal to 250 kVAElectrical Services1 rated more than 250 kVA and less than or equal to 1000kVAElectrical Services1 rated more than 1000kVA
Instantaneous (at the time) kW demandRequiredRequiredRequiredRequired
Historical peak demand (kW)Not requiredNot requiredRequiredRequired
Tracking kWh for a user-definable period.RequiredRequiredRequiredRequired
kWh per rate periodNot requiredNot requiredNot requiredRequired

p.536Elevators, escalators, moving walks, and transit systems

p.536All loads in

p.536All loads in

p.536All loads in

p.536aggregate

p.536aggregate

p.536aggregate

p.536Renewable power source (net or total)

p.536Each group Each group Each group Each group

p.536Loads associated with renewable power source

p.536All loads in

p.536All loads in

p.536All loads in

p.5351 “Electrical Services” applies to the building service-entrance rating or to the submetering service. For a building with submetering, this applies to the submetering service size to the common use areas.

p.536aggregate

p.536aggregate

p.536aggregate

p.536Charging stations for electric vehicles

p.536All loads in

p.536All loads in

p.536All loads in

p.536All loads in

p.536aggregate

p.536aggregate

p.536aggregate

p.536aggregate 1 “Electrical Services” applies to the building service-entrance rating or to the submetering service. For a building with submetering, this applies to the submetering service size to the common use area.

p.535(b) Separation of electrical circuits for electrical energy monitoring. Electrical power distribution

p.535systems shall be designed so that measurement devices can monitor the electrical energy usage of load types according to Table 160.6-B.

p.536(c) Voltage drop. The maximum combined voltage drop on both installed feeder conductors and

p.536branch circuit conductors to the farthest connected load or outlet shall not exceed 5 percent.

p.536(d) Circuit controls for 120-volt receptacles and controlled receptacles. In all common areas, both

p.536controlled and uncontrolled 120 volt receptacles shall be provided in office areas, lobbies,

p.535SECTION 160.6 – MANDATORY REQUIREMENTS FOR ELECTRIC POWER DISTRIBUTION SYSTEM

p.536SECTION 160.6 – MANDATORY REQUIREMENTS FOR ELECTRIC POWER DISTRIBUTION SYSTEM