Luminaires in skylit daylit zone or primary sidelit daylit zone or secondary sidelit daylit zone
0.10
2. Occupant sensing controls in offices larger than 250 square feet
One sensor controlling an area that is no larger than 125 square feet
0.30
3. Occupant sensing controls in offices larger than 250 square feet
One sensor controlling an area that is 126-250 square feet
0.20
4. Institutional tuning
Luminaires in non-daylit areas. Luminaires that qualify for other PAFs in this table may also qualify for this tuning PAF.
0.10
5. Institutional tuning
Luminaires in daylit areas. Luminaires that qualify for other PAFs in this table may also qualify for this tuning PAF.
0.05
6. Demand responsive control
General lighting luminaires not in the scope of Section 110.12(c). If DR controls are required of Section 110.12(c), this PAF is not available for any lighting in the project. Luminaires that qualify for other PAFs in this table may also qualify for this demand responsive control PAF.
0.05
7. Clerestory fenestration
Luminaires in daylit areas adjacent to the clerestory. Luminaires that qualify for daylight dimming plus OFF control may also qualify for this PAF.
0.05
8. Horizontal slats
Luminaires in daylit areas adjacent to vertical fenestration with interior or exterior horizontal slats. Luminaires that qualify for daylight dimming plus OFF control may also qualify for this PAF.
0.05
9. Light shelves
Luminaires in daylit areas adjacent to clerestory fenestration with interior or exterior light shelves. This PAF may be combined with the PAF for clerestory fenestration. Luminaires that qualify for daylight dimming plus OFF control may also qualify for this PAF.