SECTION 140.6 – PRESCRIPTIVE REQUIREMENTS FOR INDOOR LIGHTING (part 1 of 2)

Scanned crop of table from PDF page 348
AREA CATEGORY METHOD - LIGHTING POWER DENSITY VALUES (WATTS/FT²) p.357 Download CSV
Building Type/UsePrimary Function AreaAllowed Lighting Power Density for General Lighting (W/ft2)Additional Lighting Power Qualified Lighting SystemsAdditional Lighting Power Additional Allowance 3 (W/ft², unless noted otherwise)
Aging Eye/Low-vision11Corridor Area0.70Decorative/Display0.30
Aging Eye/Low-vision11Dining0.80Decorative/Display0.30
Aging Eye/Low-vision11NA0.80Tunable white or dim- to-warm100.10
Aging Eye/Low-vision11Lobby, Main Entry0.85Decorative/Display0.30
Aging Eye/Low-vision11Lobby, Main Entry0.85Transition Lighting OFF at night120.95
Aging Eye/Low-vision11Lobby, Main Entry0.85Tunable white or dim- to-warm100.10
Aging Eye/Low-vision11Lounge/Waiting Area0.80Decorative/Display0.30
Aging Eye/Low-vision11Lounge/Waiting Area0.80Tunable white or dim- to-warm100.10
Aging Eye/Low-vision11Multipurpose Room0.85Decorative/Display0.30
Aging Eye/Low-vision11Multipurpose Room0.85Tunable white or dim- to-warm100.10
Aging Eye/Low-vision11Religious Worship Area1.00Decorative/Display0.30
Aging Eye/Low-vision11Religious Worship Area1.00Tunable white or dim- to-warm100.10
Aging Eye/Low-vision11Restroom1.00Decorative/Display0.20
Aging Eye/Low-vision11Stairwell0.80Decorative/Display0.30
Audience Seating AreaNA0.50Decorative/Display0.25
Auditorium AreaNA0.70Decorative/Display0.45
Auto Repair / Maintenance AreaNA0.55Detailed Task Work70.20
Barber, Beauty Salon, Spa AreaNA0.70Detailed Task Work70.30
Barber, Beauty Salon, Spa AreaNA0.70Decorative/Display0.25
Civic Meeting Place AreaNA0.90Decorative/Display0.25
Classroom, Lecture, Training, Vocational AreaNA0.60White or Chalk Board17 W/ft
Concourse and Atria AreaNA0.60Decorative/Display0.25
Convention, Conference, Multipurpose and Meeting AreaNA0.75Decorative0.25
Convention, Conference, Multipurpose and Meeting AreaNA0.75Wall Display MH <= 10’6”2 W/ft
Convention, Conference, Multipurpose and Meeting AreaNA0.75Wall Display MH 10’7”- 14’2.35 W/ft
Convention, Conference, Multipurpose and Meeting AreaNA0.75Wall Display MH > 14’2.66 W/ft
COMPLETE BUILDING METHOD LIGHTING POWER DENSITY VALUES p.354 Download CSV
TYPE OF BUILDINGALLOWED LIGHTING POWER DENSITY (WATTS PER SQUARE FOOT)
Assembly Building0.65
Bank or Financial Institution Building0.65
Grocery Store Building0.90
Gymnasium Building0.60
Healthcare Facility0.90
Industrial/Manufacturing Facility Building0.60
Library Building0.70
Motion Picture Theater Building0.60
Museum Building0.65
Office Building0.60
Parking Garage Building0.13
Performing Arts Theater Building0.75
Religious Facility Building0.70
Restaurant Building0.65
Retail Store Building0.90
School Building0.60
Sports Arena Building0.75
All other buildings0.40
LIGHTING POWER ADJUSTMENT FACTORS (PAF) p.349 Download CSV
TYPE OF CONTROLTYPE OF AREAFACTOR
1. Daylight continuous dimming plus OFF controlLuminaires in skylit daylit zone or primary sidelit daylit zone or secondary sidelit daylit zone0.10
2. Occupant sensing controls in offices larger than 250 square feetOne sensor controlling an area that is no larger than 125 square feet0.30
3. Occupant sensing controls in offices larger than 250 square feetOne sensor controlling an area that is 126-250 square feet0.20
4. Institutional tuningLuminaires in non-daylit areas. Luminaires that qualify for other PAFs in this table may also qualify for this tuning PAF.0.10
5. Institutional tuningLuminaires in daylit areas. Luminaires that qualify for other PAFs in this table may also qualify for this tuning PAF.0.05
6. Demand responsive controlGeneral lighting luminaires not in the scope of Section 110.12(c). If DR controls are required of Section 110.12(c), this PAF is not available for any lighting in the project. Luminaires that qualify for other PAFs in this table may also qualify for this demand responsive control PAF.0.05
7. Clerestory fenestrationLuminaires in daylit areas adjacent to the clerestory. Luminaires that qualify for daylight dimming plus OFF control may also qualify for this PAF.0.05
8. Horizontal slatsLuminaires in daylit areas adjacent to vertical fenestration with interior or exterior horizontal slats. Luminaires that qualify for daylight dimming plus OFF control may also qualify for this PAF.0.05
9. Light shelvesLuminaires in daylit areas adjacent to clerestory fenestration with interior or exterior light shelves. This PAF may be combined with the PAF for clerestory fenestration. Luminaires that qualify for daylight dimming plus OFF control may also qualify for this PAF.0.10
Equation on PDF page 357: NA 0.75 Wall Display MH <=

Equation text: NA 0.75 Wall Display MH <=

Needs visual review

p.357