p.402SUBCHAPTER 7 SINGLE-FAMILY RESIDENTIAL BUILDINGS – MANDATORY
p.406a. Minimum: Heating systems are required to have a heating capacity meeting
p.4081. Water piping, solar water-heating system piping, and space-conditioning system line insulation thickness and conductivity. Piping shall be insulated as follows:
p.403insulated between wood-framing members with insulation resulting in an installed thermal resistance of R-19 or greater.
p.404iv. The requirements in Reference Residential Appendix RA4.5.1.
p.407nominal cooling capacity (at 95°F ambient conditions) multiplied by 2.7 kW per ton, rounded up to the closest kW.
p.409iii. High-intensity discharge (HID) light sources, including pulse start metal halide and
p.410specified in Section 150.0(k)2A. No controls shall bypass control functions of a dimmer, occupant sensor, or vacancy sensor where the dimmer or sensor has been installed to comply with Section 150.0(k)2.
p.411i. Controlled by a manual ON and OFF control switch that permits the automatic
p.412E502.4.2 to prevent air infiltration into the cavity. All connections in unconditioned space are insulated to a minimum of R-6.0 as confirmed by visual inspection.
p.413D. Joints and seams of duct systems and their components shall not be sealed with
p.406the minimum requirements of the CBC, not including any supplementary heating.
p.409high-pressure sodium light sources; and
p.411actions of Items ii below; and
p.413cloth-back rubber adhesive duct tapes unless such tape is used in combination with mastic and drawbands.
p.404(e) Installation of fireplaces, decorative gas appliances and gas logs. If a masonry or factory-
p.4033. Attic access doors shall have permanently attached insulation using adhesive or mechanical fasteners. The attic access shall be gasketed to prevent air leakage; and
p.404built fireplace is installed, it shall comply with Section 110.5, Section 4.503 of Part 11, and shall have the following:
p.4079. Capacity variation with third-party thermostats. Variable or multi-speed systems shall comply with the following requirements:
p.408A. All domestic hot water piping shall be insulated as specified in Section 609.12 of the
p.409iv. Luminaires with hardwired high-frequency generator and induction lamp.
p.411ii. Controlled by one of the following controls:
p.402FEATURES AND DEVICES
p.406b. Maximum: There is no limit on the maximum heating capacity.
p.410E. Automatic-off controls.
p.4133. Field-fabricated duct systems.
p.408California Plumbing Code.
p.411a. A photocell and a motion sensor; or
p.4034. Insulation shall be installed in direct contact with a roof or ceiling which is sealed to limit infiltration and exfiltration as specified in Section 110.7, including but not limited to placing insulation either above or below the roof deck or on top of a drywall ceiling.
p.4041. Closable metal or glass doors covering the entire opening of the firebox; and
p.4052. Design conditions. Design conditions shall be determined in accordance with the following:
p.4066. Defrost.
p.407A. The space conditioning system and thermostat together shall be capable of
p.408B. Piping for space-conditioning systems, solar water-heating system collector loop, and
p.410i. In bathrooms, garages, laundry rooms, utility rooms and walk-in closets, at least
p.413A. Factory-made rigid fiberglass and flexible ducts for field-fabricated duct systems shall
p.409C. Recessed downlight luminaires in ceilings. Luminaires recessed into ceilings shall
p.411b. A photocell and an automatic time switch control; or
p.407responding to heating and cooling loads by modulating system compressor speed, and meet thermostat requirements in Section 150.0(i)2.
p.408distribution piping for steam and hydronic heating system shall meet the requirements of Section 120.3(a).
p.410one installed luminaire shall be controlled by an occupancy or vacancy sensor providing automatic-off functionality.
p.412a. The attic has at least R-30 insulation between the roof rafters in contact with
p.413comply with UL 181. All pressure-sensitive tapes, mastics, aerosol sealants or other closure systems used for installing field-fabricated duct systems shall meet the applicable requirements of UL 181, UL 181A and UL 181B.
p.402SECTION 150.0 – MANDATORY FEATURES AND DEVICES
p.4042. A combustion air intake to draw air from the outside of the building, which is at least 6 square inches in area and is equipped with a readily accessible, operable and tight-fitting damper or combustion-air control device; and
p.406A. If a heat pump is equipped with an installer adjustable defrost delay timer, the delay
p.409meet all of the following requirements:
p.411c. Controlled by an astronomical time clock control.
p.412the roof deck.
p.405A. For the purpose of sizing the space-conditioning (HVAC) system, the indoor
p.406timer shall be set to greater than or equal to 90 minutes.
p.409i. Shall not contain screw base lamp sockets; and
p.402Single-family residential buildings shall comply with the applicable requirements of Sections 150(a) through 150.0(v).
p.411B. Controls that override to ON shall not be allowed unless the override automatically
p.403(b) Loose-fill insulation. When loose-fill insulation is installed, the minimum installed weight per
p.405design temperatures shall be 68°F for heating and 75°F for cooling.
p.407B. The installer shall certify on the Certificate of Installation that the control
p.410ii. For lighting internal to drawers and cabinetry with opaque fronts or doors,
p.412b. The gable ends meet the wall insulation requirements of Section 150.1(c)1B.
p.406B. The installer shall certify on the Certificate of Installation (CF2R) that the control
p.409ii. Have a label that certifies the luminaire is airtight with air leakage less than 2.0
p.411returns the automatic control to its normal operation within 6 hours.
p.403square foot shall conform with the insulation manufacturer’s installed design weight per square foot at the manufacturer’s labeled R-value.
p.407configuration has been tested in accordance with the testing procedure found in the CF2R.
p.410controls that turn the light off when the drawer or door is closed shall be provided.
p.413B. Mastic sealants and mesh.
p.405B. Outdoor design conditions shall be selected from one of the following:
p.406configuration has been tested in accordance with the testing procedure in the CF2R.
p.412c. The dwelling unit achieves a whole building leakage rate of 3.0 ACH50 or less,
p.409cfm at 75 Pascals when tested in accordance with ASTM E283. An exhaust fan housing with integral light shall not be required to be certified airtight; and
p.411C. An energy management control system (EMCS) or other controls that provides the
p.412as confirmed by field verification and diagnostic testing in accordance with Reference Residential Appendix RA3.8.
p.413i. Sealants shall comply with the applicable requirements of UL 181, UL 181A and
p.405i. Reference Joint Appendix JA2, which is based on data from the ASHRAE Climatic Data for Region X; or
p.411specified lighting control functionality and complies with all requirements applicable to the specified controls may be used to meet these requirements.
p.403(c) Wall insulation. Opaque portions of above grade walls separating conditioned spaces from
p.407(i) Thermostats.
p.410F. Dimming controls. Lighting in habitable spaces, including living rooms, dining rooms,
p.413UL 18IB, and be nontoxic and water resistant.
p.409iii. Be sealed with a gasket or caulk between the luminaire housing and ceiling, and
p.403unconditioned spaces or ambient air shall meet the following requirements:
p.410kitchens, and bedrooms, shall have readily accessible wall-mounted dimming controls that allow the lighting to be manually adjusted up and down. Forward phase cut dimmers controlling LED light sources in these spaces shall comply with NEMA SSL 7A.
p.4043. A flue damper with a readily accessible control.
p.4071. Setback thermostats. All heating or cooling systems, including heat pumps, not controlled by a central energy management control system (EMCS) shall have a setback thermostat, as specified in Section 110.2(c).
p.412ii. Ducts do not require insulation when the duct system is located entirely within
p.413ii. Sealants for interior applications shall be tested in accordance with ASTM C731
p.405ii. The ASHRAE Handbook, Fundamentals Volume; or
p.409have all air leak paths between conditioned and unconditioned spaces sealed with a gasket or caulk, or be installed per manufacturer’s instructions to maintain airtightness between the luminaire housing and ceiling; and
p.402(a) Roof deck, ceiling and rafter roof insulation. The opaque portions of roof decks separating
p.4114. Internally illuminated address signs. Internally illuminated address signs shall either:
p.4031. 2 × 4 inch framing shall have an overall assembly U-factor not exceeding U-0.095.
p.412conditioned space, as confirmed through field verification and diagnostic testing in accordance with the requirements of Reference Residential Appendix RA3.1.4.3.8. For dwelling units with attics, the duct system shall be located below the ceiling separating the occupiable space from the attic.
p.413and D2202 incorporated herein by reference.
p.402attic spaces from ambient air, and ceilings or rafter roofs separating conditioned spaces from unconditioned spaces or ambient air, shall meet the requirements of Items 1 through 4 below:
p.405iii. The ACCA Manual J.
p.4067. Supplementary heating control configuration. Heat pumps with supplementary heat, including, but not limited to, electric resistance heaters or gas furnace supplementary heating, shall comply with the following requirements:
p.411A. Comply with Section 140.8; or
p.413iii. Sealants for exterior applications shall be tested in accordance with ASTM C731,
p.405C. The outdoor design temperatures for heating shall be no lower than the 99.0
p.4072. Thermostats that are applied to heat pumps with supplemental heating. In addition to the requirements in Section 150.0(i)1, thermostats controlling heat pumps with electric resistance supplementary heat or gas furnace supplementary heat shall comply with the following requirements:
p.413C732 and D2202, incorporated herein by reference.
p.411B. Consume no more than 5 watts of power.
p.409iv. Meet the clearance and installation requirements of California Electrical Code
p.405percent Heating Dry Bulb or the Heating Winter Median of Extremes values.
p.404(f) Slab edge insulation. Material used for slab edge insulation shall meet the following
p.409Article 410.116 for recessed luminaires.
p.413iv. Sealants and meshes shall be rated for exterior use.
p.4021. In Climate Zones 4 and 8 through 16, roof decks in newly constructed attics that are above conditioned space shall be insulated to achieve an area-weighted average U- factor not exceeding U-0.184.
p.4115. Residential garages for eight or more vehicles. Lighting for residential parking garages for eight or more vehicles shall comply with the applicable requirements for nonresidential garages in Sections 110.9, 130.0, 130.1, 130.4, 140.6, and 141.0.
p.406A. Lock out supplementary heating above an outdoor air temperature of not greater
p.412C. Connections of metal ducts and the inner core of flexible ducts shall be mechanically
p.405D. The outdoor design temperatures for cooling shall be no greater than the 1.0
p.4032. 2 × 6 inch or greater framing shall have an overall assembly U-factor not exceeding U- 0.069.
p.404minimum specifications:
p.406than 35°F. There are additional thermostat requirements in section 150.0(i)2.
p.413C. Pressure-sensitive tape. Pressure-sensitive tapes shall comply with the applicable
p.412fastened.
p.405percent Cooling Dry Bulb and Mean Coincident Wet Bulb values.
p.4041. Water absorption rate for the insulation material alone without facings no greater than 0.3 percent when tested in accordance with Test Method A – 24-Hour-Immersion of ASTM C272.
p.409rated installations extruded into ceiling space and recessed luminaires installed in noninsulated ceilings.
p.413requirements of UL 181, UL 181A and UL 181B.
p.406B. The installer shall certify on the Certificate of Installation that the control
p.407A. The thermostat shall receive outdoor air temperature from an outdoor air
p.412D. Openings shall be sealed with mastic, tape or other duct-closure system that meets
p.4053. Outdoor condensing units.
p.4033. Opaque non-framed assemblies shall have an overall assembly U-factor not exceeding U- 0.102.
p.411(l) Reserved.
p.406configuration has been tested in accordance with the testing procedure found in the CF2R.
p.413D. Joints and seams of duct systems and their components shall not be sealed with
p.407temperature sensor or from an internet weather service.
p.412the applicable requirements of UL 181, UL181A or UL 181B or aerosol sealant that meets the requirements of UL 723. If mastic or tape is used to seal openings greater than 1/4 inch, the combination of mastic and either mesh or tape shall be used.
p.405A. Clearances. Installed air conditioner and heat pump outdoor condensing units shall
p.409D. Light sources in enclosed or recessed luminaires. Lamps and other separable light
p.413cloth-back rubber adhesive duct tapes unless such tape is used in combination with mastic and drawbands.
p.402i. The space-conditioning system air handler and ducts are located entirely in conditioned space below the ceiling separating the occupiable space from the attic; or
p.4082. Insulation protection. Pipe insulation shall meet the insulation protection requirements of Section 120.3(b).
p.411(m) Air-distribution and ventilation system ducts, plenums, and fans.
p.407B. The thermostat shall display the outdoor air temperature.
p.405have a clearance of at least five (5) feet (1.5 meters) from the outlet of any dryer vent.
p.4034. Bay or bow window roofs and floors shall be insulated to meet the wall insulation requirements of Table 150.1-A.
p.4042. Water vapor permeance no greater than 2.0 perm/inch when tested in accordance with ASTM E96.
p.409sources in enclosed or recessed luminaires shall be in compliance with the JA8 elevated temperature requirements, including marking requirements.
p.406C. The controls may allow supplementary heater operation above 35°F only during
p.407C. As described in Section 150.0(h)7, the thermostat and heat pump shall lock out
p.4111. CMC compliance.
p.406defrost or when the user selects emergency operation.
p.413E. Drawbands used with flexible duct.
p.408(k) Residential lighting.
p.412E. Building cavities, support platforms for air handlers and plenums designed or
p.411A. All air-distribution system ducts and plenums, including but not limited to,
p.405B. Liquid line drier. Installed air conditioner and heat pump systems shall be equipped
p.4035. Masonry/Mass walls shall be insulated to meet the wall insulation requirements of Table 150.1-A.
p.4043. Concrete slab perimeter insulation shall be protected from physical damage and ultraviolet light deterioration.
p.409E. Blank electrical boxes. The number of electrical boxes that are more than five feet
p.402ii. The space-conditioning system air handler is located in unconditioned space and has 12 linear feet or less of supply duct, including the length of the air handler and the plenum, located in unconditioned space, with all other portions of the supply ducts located in conditioned space below the ceiling separating the occupiable space from the attic; or
p.407supplementary heat when the outdoor air temperature is above 35°F.
p.412constructed with materials other than sealed sheet metal, duct board or flexible duct shall not be used for conveying conditioned air. Building cavities and support platforms may contain ducts. Ducts installed in cavities and support platforms shall not be compressed to cause reductions in the cross-sectional area of the ducts.
p.413i. Drawbands shall be either stainless-steel worm-drive hose clamps or UV-resistant
p.4081. Luminaire requirements.
p.411mechanical closets and air-handler boxes, shall meet the requirements of the CMC Sections 601.0, 602.0, 603.0, 604.0, 605.0 and ANSI/SMACNA-006-2006 HVAC Duct Construction Standards Metal and Flexible, 3rd Edition, incorporated herein by reference.
p.405with liquid line filter driers if required, as specified by manufacturer’s instructions.
p.409above the finished floor and do not contain a luminaire or other device shall be no greater than the number of bedrooms. These electrical boxes shall be served by a dimmer, vacancy sensor control, low voltage wiring, or fan speed control.
p.413nylon duct ties.
p.407D. The thermostat shall have an indicator to notify when supplementary heat or
p.408A. Luminaire efficacy. All installed luminaires and light sources shall comply with
p.4054. Central forced-air heating furnaces.
p.410G. Independent controls. Lighting integral to exhaust fans shall be controlled
p.4036. In wood framed assemblies, compliance with U-factors may be demonstrated by installing wall insulation with an R-value of R-15 in 2x4 assemblies and R-21 in 2x6 assemblies, with 16 inches on center spacing.
p.4044. Insulation for a heated slab floor shall meet the requirements of Section 110.8(g).
p.407emergency heat is in use.
p.413ii. Drawbands shall have a minimum tensile strength rating of 150 pounds.
p.408Reference Joint Appendix JA8 and shall be certified and marked as required by JA8.
p.410independently from the fans. The following shall be controlled separately from ceiling-installed lighting such that one can be turned on without turning on the other:
p.406i. Option A: 1. That prevent supplementary heater operation when the heating load can be met by the heat pump alone; and 2. In which the cut-on temperature for heat pump heating is higher than the cut- on temperature for supplementary heating, and the cut-off temperature for heat pump heating is higher than the cut-off temperature for supplementary heating. ii. Option B: The controls may allow supplementary heater operation during defrost mode and transient periods, such as start-ups and following a room thermostat setpoint advance, if the controls prevent the unnecessary operation of supplementary heating.
p.405A. Temperature rise. Central forced-air heating furnace installations shall be configured
p.404(g) Vapor retarder.
p.407E. During defrost or when the user selects emergency heating, supplementary heat
p.413iii. Drawbands shall be tightened as recommended by the manufacturer with an
p.4092. Indoor lighting controls.
p.405to operate in conformance with the furnace manufacturer’s maximum inlet-to-outlet temperature rise specifications.
p.407operation is permitted above 35°F.
p.411B. Portions of supply-air and return-air ducts and plenums of a space heating or cooling
p.4041. In Climate Zones 1–16, the earth floor of unvented crawl space shall be covered with a Class I or Class II vapor retarder. This requirement shall also apply to controlled ventilation crawl space for buildings complying with the Exception to Section 150.0(d).
p.413adjustable tensioning tool.
p.402iii. The space-conditioning system is a ductless system.
p.403(d) Raised-floor insulation. Raised floors separating conditioned space from unconditioned
p.409A. Lighting shall have readily accessible wall-mounted controls that allow the lighting to
p.411system shall be insulated in accordance with either Subsection i or ii below:
p.4122. Factory-fabricated duct systems.
p.407F. The installer shall certify on the Certificate of Installation that the system has been
p.410i. Undercabinet lighting.
p.413F. Aerosol-sealant closures.
p.403space or ambient air shall have an overall assembly U-factor not exceeding U-0.037. In a wood framed assembly, compliance with the U-factor may be demonstrated by installing insulation with an R-value of 19 or greater.
p.409be manually turned ON and OFF.
p.4055. System selection.
p.407tested in accordance with the testing procedure found in the CF2R.
p.412A. All factory-fabricated duct systems shall comply with UL 181 for ducts and closure
p.411i. Ducts shall have a minimum installed level of R-6.0, or
p.410ii. Undershelf lighting.
p.413i. Aerosol sealants shall meet the requirements of UL 723 and be applied according
p.412systems, including collars, connections and splices, and be labeled as complying with UL 181. UL 181 testing may be performed by UL laboratories, or a laboratory approved by the Executive Director.
p.405A. Equipment sizing and selection shall meet the cooling and heating loads of Sections
p.4042. In Climate Zones 14 and 16, a Class I or Class II vapor retarder shall be installed on the conditioned space side of all insulation in all exterior walls, vented attics and unvented attics with air-permeable insulation.
p.413to manufacturer specifications.
p.405150.0(h)1 and 2.
p.410iii. Interior lighting of display cabinets.
p.4022. Ceilings and rafter roofs shall be insulated to achieve an area-weighted average U-factor not exceeding U-0.043 or shall be insulated between wood-framing members with insulation resulting in an installed thermal resistance of R-22 or greater for the insulation alone. For vented attics, the mandatory insulation shall be installed at the ceiling level; for unvented attics, the mandatory insulation shall be placed at either ceiling or roof level; and
p.413ii. Tapes or mastics used in combination with aerosol sealing shall meet the
p.410iv. Switched outlets.
p.405B. Systems shall be sized based on ACCA Manual S-2023 in accordance with these
p.413requirements of this section.
p.412B. All pressure-sensitive tapes, heat-activated tapes, and mastics used in the
p.405requirements:
p.404(h) Space-conditioning equipment.
p.409C. All lighting controls. Lighting controls shall comply with the applicable requirements
p.4103. Residential outdoor lighting. In addition to meeting the requirements of Section 150.0(k)1A, luminaires providing residential outdoor lighting shall meet the following requirements, as applicable:
p.411a. The noninsulated portion of the duct system is located entirely inside the building’s thermal envelope as confirmed by visual inspection.
p.403i. The foundation walls are insulated to meet the wall insulation minimums as shown in Table 150.1-A; and
p.412manufacture of rigid fiberglass ducts shall comply with UL 181 and UL 181A.
p.4134. Duct insulation R-value ratings. All duct insulation product R-values shall be based on insulation only (excluding air films, vapor retarder or other duct components) and tested C-values at 75°F mean temperature at the installed thickness, in accordance with ASTM C518 or ASTM C177, incorporated herein by reference, and certified pursuant to Section 110.8.
p.405i. Cooling capacity: There is no limit on the minimum capacity.
p.4041. Building cooling and heating loads. Building heating and cooling loads shall be determined using a method based on any one of the following:
p.412C. All pressure-sensitive tapes and mastics used with flexible ducts shall comply with UL
p.409D. Controls permitted. An energy management control system (EMCS) or a multi-scene
p.405ii. Furnaces: Heating capacity shall be sized based on ACCA Manual S-2023, Table
p.411b. At all locations where noninsulated portions of the duct system penetrate into unconditioned space, the penetration shall be draft stopped compliant with CFC Sections 703.1 and 704.1 and air-sealed to the construction materials that are penetrated, using materials compliant with CMC Sectionp.412
p.403ii. A Class I or Class II vapor retarder is placed over the entire floor of the crawl space; and
p.408i. LED light sources installed outdoors;
p.412181 and UL 181B.p.413
p.409programmable control may be used to comply with dimming, occupancy, and lighting control requirements in Section 150.0(k)2 if it provides the functionality of the specified controls in accordance with Section 110.9 and the physical controlsp.410
p.410A. Outdoor lighting permanently mounted to a residential building or to other buildings
p.405N2.5.
p.404A. The ASHRAE Handbook, Equipment Volume, Applications Volume and
p.407(j) Insulation for piping and tanks.p.408
p.403iii. Vents between the crawlspace and outside air are fitted with automatically operated louvers that are temperature actuated; andp.404
p.408ii. Inseparable solid state lighting (SSL) luminaires containing colored light sources
p.410on the same lot shall meet the following requirements:p.411
p.4068. Sizing of electric resistance supplementary heat. Where heat pumps have electric resistance heat, the capacity of electric resistance heat shall not exceed the heat pumpp.407
p.404Fundamentals Volume; or
p.405iii. Heat pump heating capacity:p.406
p.408that are installed to provide decorative lighting;p.409
p.404B. The SMACNA Residential Comfort System Installation Standards Manual; orp.405
p.402SECTION 150.0 – MANDATORY FEATURES AND DEVICES
p.403SECTION 150.0 – MANDATORY FEATURES AND DEVICES
p.404SECTION 150.0 – MANDATORY FEATURES AND DEVICES
p.405SECTION 150.0 – MANDATORY FEATURES AND DEVICES
p.406SECTION 150.0 – MANDATORY FEATURES AND DEVICES
p.407SECTION 150.0 – MANDATORY FEATURES AND DEVICES
p.408SECTION 150.0 – MANDATORY FEATURES AND DEVICES
p.409SECTION 150.0 – MANDATORY FEATURES AND DEVICES
p.410SECTION 150.0 – MANDATORY FEATURES AND DEVICES
p.411SECTION 150.0 – MANDATORY FEATURES AND DEVICES