iv. Meet the clearance and installation requirements of California Electrical Code Article 410.116 for recessed luminaires.

p.521iii. Be sealed with a gasket or caulk between the luminaire housing and ceiling, and have all

p.522allow the lighting to be manually adjusted up and down. Forward phase cut dimmers controlling LED light sources shall comply with NEMA SSL 7A.

p.521air leak paths between conditioned and unconditioned spaces sealed with a gasket or caulk, or be installed per manufacturer’s instructions to maintain airtightness between the luminaire housing and ceiling; and

p.521iv. Meet the clearance and installation requirements of California Electrical Code Article

p.521410.116 for recessed luminaires. Exception to Section 160.5(a)1Cii and Iii: Recessed luminaires marked for use in fire- rated installations, and recessed luminaires installed in noninsulated ceilings.

p.521D. Light sources in enclosed or recessed luminaires. Lamps and other separable light sources

p.522G. Independent controls. Lighting integrated with the exhaust fans shall be controlled

p.521in enclosed or recessed luminaires shall be in compliance with the JA8 elevated temperature requirements, including marking requirements. E. Blank electrical boxes. The number of electrical boxes that are more than five feet above

p.522independently from the fans. The following shall be controlled separately from ceiling- installed lighting such that one can be turned on without turning on the other:

p.522v. Undercabinet lighting

p.521the finished floor and do not contain a luminaire or other device shall be no greater than the number of bedrooms. These electrical boxes shall be served by a dimmer, vacancy sensor control, low voltage wiring, or fan speed control.

p.522vi. Undershelf lighting

p.522vii. Interior lighting of display cabinets

p.5212. Indoor lighting controls.

p.522viii. Switched outlets

p.521A. Lighting shall have readily accessible wall-mounted controls that allow the lighting to be

p.521manually turned ON and OFF.

p.5223. Outdoor lighting controls. In addition to meeting the requirements of Section 160.5(a)1, luminaires providing residential outdoor lighting shall meet the following requirements, as applicable:

p.522A. Outdoor lighting attached to a building and separately controlled from the inside of a

p.521B. Reserved.

p.522dwelling unit shall meet the following requirements:

p.521C. All lighting controls. Lighting controls shall comply with the applicable requirements of

p.522i. Controlled by a manual ON and OFF control switch that permits the automatic actions

p.521Section 110.9.

p.522of Item ii or iii below; and

p.521D. Controls permitted. An energy management control system (EMCS) or a multi-scene

p.522ii. Controlled by one of the following controls:

p.521programmable controller may be used to comply with dimming, occupancy and lighting control requirements in Section 160.5(a)2 if it provides the functionality of the specified controls in accordance with Section 110.9 and the physical controls specified in Section 160.5(a)2A. No controls shall bypass control functions of a dimmer, occupant sensor, or vacancy sensor where the dimmer or sensor has been installed to comply with Section 160.5(a)2.

p.522a. a photocell and a motion sensor; or

p.522b. a photocell and an automatic time switch control; or

p.522iii. Controlled by an astronomical time clock control.

p.522B. Controls that override to ON shall not be allowed unless the override automatically returns

p.521E. Automatic-off controls.

p.522the automatic control to its normal operation within six hours.

p.521iii. In bathrooms, garages, laundry rooms, utility rooms and walk-in closets, at least one

p.522C. An energy management control system (EMCS) or other controls that provides the specified

p.521installed luminaire shall be controlled by an occupancy or vacancy sensor providing automatic-off functionality.

p.522lighting control functionality and complies with all requirements applicable to the specified controls may be used to meet these requirements.

p.521iv. For lighting internal to drawers and cabinetry with opaque fronts or doors, controls that

p.522(b) Common services area lighting. Lighting systems and equipment in multifamily common services

p.521turn the lighting off when the drawer or door is closed shall be provided.

p.522areas shall comply with the applicable provisions of Sections 160.5(b)1 through 160.5(b)4.

p.521F. Dimming controls. Lighting in habitable spaces, including living rooms, dining rooms,

p.521kitchens and bedrooms, shall have readily accessible wall-mounted dimming controls thatp.522

p.521SECTION 160.5 – MANDATORY LIGHTING REQUIREMENTS FOR INDOOR AND OUTDOOR SPACES

p.522SECTION 160.5 – MANDATORY LIGHTING REQUIREMENTS FOR INDOOR AND OUTDOOR SPACES