p.525A. Manual controls. Each space shall be provided with lighting controls that allow the lighting
p.524F. For modular lighting systems that allow the addition or relocation of luminaires without
p.526i. All installed indoor lighting shall be equipped with controls that meet the following
p.527a. a partial-ON occupant sensing control capable of automatically activating between
p.528c. In parking garages, parking areas, and loading and unloading areas, general lighting
p.524altering the wiring of the system, wattage shall be determined as follows:
p.525in that space to be manually turned on and off. The manual control shall:
p.526requirements:
p.52750 and 70 percent of controlled lighting power, or
p.528shall be controlled by occupant sensing controls that meet the requirements below instead of complying with Section 160.5(b)4Ci:
p.529areas.
p.524i. The wattage shall be the greater of:
p.525i. Be readily accessible; and
p.526a. Shall be controlled with an occupant sensing control set at no more than a 20-
p.527b. a vacancy sensing control, where all lighting responds to a manual ON input only.
p.529vii. The daylight responsive controls shall provide separate control for general lighting in
p.526minute time delay, automatic time-switch control, or other control capable of automatically shutting OFF all of the lighting when the space is typically unoccupied; and
p.528i. The occupant sensing controls shall uniformly reduce lighting power in the
p.529each type of daylit zone. The daylight responsive controls shall meet the following:
p.524a. 30 watts per linear foot of track or plug-in busway; or
p.527In areas not required by Section 160.5(b)4B to have multi-level lighting controls the occupant sensing controls shall function either as:
p.528control zone to between 20 percent and 50 percent of full power and with at least one control step; and
p.529a. General lighting in overlapping skylit daylit zone and sidelit daylit zone shall be
p.524b. the rated wattage of all of the luminaires included in the system, where the
p.529controlled as part of the skylit daylit zone.
p.524luminaire wattage is determined as specified in Section 160.5(b)1A; or
p.527a. an automatic full-on occupant sensing control; or
p.5231. Luminaire classification and power. Luminaires shall be classified, and their wattage determined as follows:
p.526b. Separate controls for the lighting on each floor, other than lighting in stairwells; and
p.528ii. No more than 500 watts of rated lighting power shall be controlled together as a
p.525ii. Be located in the same space or be located such that the controlled lighting or the
p.529b. General lighting in overlapping primary and secondary sidelit daylit zone shall be
p.524ii. For line-voltage lighting track and plug-in busway served by a track lighting integral
p.527b. a partial-ON occupant sensing control, or
p.528single zone; and
p.525status of the controlled lighting can be seen when operating the controls; and
p.526c. Separate control zones for a space enclosed by ceiling height partitions not
p.529controlled as part of the primary sidelit daylit zone.
p.524current limiter or a dedicated track lighting supplementary overcurrent protection panel, the wattage shall be determined as follows:
p.527c. a vacancy sensing control, where all lighting responds to a manual ON input only.
p.523A. Luminaire wattage shall be labeled as follows:
p.526exceeding 5,000 square feet;
p.528iii. The occupant sensing controls shall be capable of automatically turning the
p.525iii. Provide separate control of general, floor display, wall display, window display, case
p.529c. General lighting luminaires longer than 8 feet shall be controlled as segments of 8
p.528lighting fully ON only in the separately controlled zone and shall be automatically activated from all designed paths of egress.
p.527In addition, controls shall be provided that allow the lights to be manually shut OFF in accordance with Section 160.5(b)4A regardless of the sensor status.
p.523i. The maximum rated wattage or relamping rated wattage of a luminaire shall be listed
p.525display, ornamental, and special effects lighting, such that each type of lighting can be turned on or off without turning on or off other types of lighting. Scene controllers may comply with this requirement provided that at least one scene turns on general lighting only, and the control provides a means to manually turn off all lighting.
p.529feet or less according to the type of the daylit zone the segment is primarily located; and
p.524a. The volt-ampere rating of current limiter as specified by UL 1077; or
p.523on a permanent, preprinted, factory-installed label, as specified by UL 1574, 1598, 2108 or 8750, as applicable; and
p.524b. The sum of the ampere (A) rating of all of the current protection devices times the
p.528Interior areas of parking garages are under the classification of indoor lighting and shall comply with Section 160.5(b)4Cvic. Parking areas on the roof of a parking structure are under the classification of outdoor hardscape and shall comply with Section 160.5(c).
p.527vi. Full or partial OFF occupant sensing controls. For corridors, stairwells, and offices
p.524branch circuit voltages for track lighting supplementary overcurrent protection panel.
p.527greater than 250 square feet, parking garages, parking areas, loading areas, and unloading areas, the installed lighting shall meet the following requirements:
p.523ii. The factory-installed maximum rated wattage or relamping rated wattage label shall not
p.529housing and light source as an integral unit in segments longer than 8 feet, the luminaire is allowed to be controlled according to the type of the daylit zone in which the segment is primarily located.
p.523consist of peel-off or peel-down layers or other methods that allow the rated wattage to be changed after the luminaire has been shipped from the manufacturer.
p.524iii. For other modular lighting systems with power supplied by a driver, power supply or
p.527a. In corridors and stairwells, lighting shall be controlled by occupant sensing controls
p.524transformer, including but not limited to low-voltage lighting systems, the wattage of the system shall be the maximum rated input wattage of the driver, power supply or transformer published in the manufacturer’s catalogs, as specified by UL 2108 or 8750.
p.528D. Daylight Responsive Controls.
p.527that separately reduce the lighting power in each space by at least 50 percent when the space is unoccupied. The occupant sensing controls shall be capable of automatically turning the lighting fully ON only in the separately controlled space and shall be automatically activated from all designed paths of egress.
p.529viii. The daylight responsive controls shall meet the following:
p.528Daylight responsive controls shall be installed in the following locations, as applicable:
p.529a. For spaces where the installation of multilevel lighting controls is required under
p.525i. The space is designated for means of egress on the plans and specifications submitted
p.528i. In any enclosed space where the total installed wattage of general lighting luminaires
p.529Section 160.5(b)4B, allow the multilevel lighting controls to adjust the light level with continuous dimming;
p.525to the enforcement agency under Section 10-103(a)2 of Part 1; and
p.523a. Low-voltage luminaires (except low voltage track systems), ≤ 24 volts, with a
p.528completely or partially within skylit daylit zones is 75 watts or greater, the general lighting in the skylit daylit zones shall be controlled by daylight responsive controls.
p.526ii. Countdown timer switches may be used to comply with the automatic shut-OFF control
p.527b. In office spaces greater than 250 square feet, general lighting shall be controlled by
p.523maximum relamping rated wattage of 50 watts.
p.525ii. The egress lighting controls shall not be controllable by unauthorized personnel during
p.526requirements in Section 160.5(b)4Ci only in closets less than 70 square feet. The maximum timer setting shall be 10 minutes for closets.
p.529b. For each space, ensure the combined illuminance from the controlled lighting and
p.527occupancy sensing controls that meet all of the following:
p.525a normal power failure.
p.523b. Compact fluorescent luminaires, having an integral electronic ballast, with a
p.528ii. In any enclosed space where the total installed wattage of general lighting luminaires
p.529daylight is not less than the illuminance from controlled lighting when no daylight is available;
p.524G. For all other lighting equipment not addressed by Sections 160.5(b)1B through F, the
p.527I. The occupancy sensing controls shall be configured so that lighting shall be
p.523maximum relamping rated wattage of 42 watts.
p.525B. Multilevel lighting controls. The general lighting of any space with a size of 100 square
p.528completely or partially within primary sidelit daylit zones is 75 watts or greater, the general lighting in the primary sidelit daylit zones shall be controlled by daylight responsive controls.
p.524wattage of the lighting equipment shall be the maximum rated wattage of the lighting equipment, or operating input wattage of the system, labeled in accordance with Section 160.5(b)1A, or published in manufacturer’s catalogs, based on independent testing lab reports as specified by UL 1574, 1598, 2108, 8750, or IES LM-79.
p.526iii. If an automatic time-switch control is installed to comply with Section 160.5(b)4Ci, it
p.527controlled separately in control zones not greater than 600 square feet. All control zones in offices greater than 250 square feet shall be shown on the plans; and
p.525feet or larger and with a connected lighting load greater than 0.5 watts per square foot shall be provided with multilevel lighting controls. The multilevel lighting controls shall provide and enable continuous dimming from 100 percent to 10 percent or lower of lighting power.
p.523c. High intensity discharge luminaires, having an integral electronic ballast, with a
p.526shall incorporate a manual override lighting control that allows the lighting to remain on for no more than 2 hours when an override is initiated.
p.529c. For areas other than parking garages, ensure that when the daylight illuminance is
p.523maximum relamping rated wattage of 150 watts.
p.529greater than 150 percent of the illuminance provided by the controlled lighting system when no daylight is available, the controlled lighting power in that daylight zone shall be reduced by a minimum of 90 percent; and
p.528iii. In any enclosed space where the total wattage of general lighting luminaires in the
p.523B. For luminaires with line voltage lamps not served by drivers, ballasts or transformers, the
p.527II. In 20 minutes or less after the control zone is unoccupied, the occupancy
p.528secondary zones is 75 watts or greater, the general lighting in the secondary sidelit daylit zones shall be controlled by daylight responsive controls. General lighting in the secondary sidelit daylit zones shall be controlled independently of general lighting in the primary sidelit daylit zones.
p.523wattage of such luminaires shall be determined as the maximum rated wattage as labeled in accordance with Section 160.5(b)1A.
p.5242. Lighting controls. All lighting controls and equipment shall comply with the applicable requirements in Sections 110.9, 160.5(b) and 160.5(c), and shall be installed in accordance with any applicable manufacturer instructions.
p.526iv. If an automatic time-switch control is installed to comply with Section 160.5(b)4Ci, it
p.527sensing controls shall uniformly reduce lighting power in the control zone to no more than 20 percent of full power. Control functions that switch control zone lights completely off when the zone is vacant meet this requirement; and
p.529d. For parking garages, ensure that when daylight illuminance levels measured at the
p.526shall incorporate an automatic holiday "shut-OFF" feature that turns OFF all loads for at least 24 hours, and then resumes the normally scheduled operation.
p.529farthest edge of the secondary sidelit zone away from the glazing or opening are greater than 150 percent of the illuminance provided by the controlled lighting when no daylight is available, the controlled lighting power in the combined primary and secondary sidelit daylight zones shall be reduced by 100 percent; and
p.523C. For luminaires with permanently installed or remotely installed ballasts, the wattage of
p.523such luminaires shall be the operating input wattage of the rated lamp/ballast combination published in the ballast manufacturer’s catalogs based on independent testing lab reports as specified by UL 1598.
p.5243. Energy Management Control System (EMCS). An EMCS may be installed to comply with the requirements of one or more lighting controls if it meets the following minimum requirements:
p.527III. In 20 minutes or less after the entire office space is unoccupied, the occupancy
p.528iv. For skylights located in an atrium, the skylit daylit zones shall apply to the floor area
p.526required in restaurants.
p.527sensing controls shall automatically turn off lighting in all control zones in the space; and
p.528directly under the atrium and the top floor area directly adjacent to the atrium.
p.524A. Provides all applicable functionality for each specific lighting control or system for which it
p.528v. Parking garage areas where the total installed wattage of the general lighting in the
p.529ix. Photosensor shall be located so that they are not readily accessible to unauthorized
p.523D. For inseparable SSL luminaires and SSL luminaires with remotely mounted drivers, the
p.524is installed in accordance with Sections 110.9, 160.5(b) and 160.5(c); and
p.525C. Shut-OFF controls. All installed indoor lighting shall be equipped with controls able to
p.527IV. In each control zone, lighting shall be allowed to automatically turn on to any
p.528primary and the secondary sidelit daylit zones is 60 watts or greater, the general lighting in the primary and secondary sidelit daylit zones shall be controlled by daylight responsive controls.
p.529personnel; and
p.523maximum rated wattage shall be the maximum rated input wattage of the SSL luminaire as specified in Section 160.5(b)1A when tested in accordance with UL 1598, 2108 or 8750, or IES LM-79.
p.525automatically reduce lighting power when the space is typically unoccupied.
p.524B. Complies with all applicable lighting control installation requirements in accordance with
p.527level up to full power upon occupancy within the control zone. When occupancy is detected in any control zone in the space, the lighting in other control zones that are unoccupied shall operate at no more than 20 percent of full power.
p.526v. Occupant sensing controls. In offices 250 square feet or smaller, multipurpose rooms of less than 1,000 square feet, conference rooms, and restrooms, lighting shall be controlled with occupant sensing controls to automatically shut OFF all of the lighting in 20 minutes or less after the control zone is unoccupied.
p.529x. The location where calibration adjustments are made to the daylight responsive
p.524Section 160.5(e) for each specific lighting control or system for which it is installed; and
p.529controls shall be readily accessible to authorized personnel but may be inside a locked case or under a cover that requires a tool for access; and
p.524C. Complies with all applicable application requirements for each specific lighting control or
p.528All daylight responsive controls shall meet the following requirements:
p.523E. For LED tape lighting and LED linear lighting with LED tape lighting components, the
p.524system for which it is installed, in accordance with Part 6.
p.523maximum rated wattage shall be the sum of the installed length of the tape lighting times its rated linear power density in watts per linear foot, or the maximum rated input wattage of the driver or power supply providing power to the lighting system, with tape lighting tested in accordance with UL 2108 or 8750, or IES LM-79.p.524
p.528vi. All skylit daylit zones, primary sidelit daylit zones, secondary sidelit daylit zones and the
p.529xi. Interaction with other lighting controls in a space where manual controls are required, the
p.5244. Mandatory indoor lighting controls. Multifamily common use areas shall comply with the applicable requirements of Sections 160.5(b)4A through 160.5(b)4F, in addition to the applicable requirements of Section 110.9.p.525
p.526In areas required by Section 160.5(b)4B to have multi-level lighting controls, the occupant sensing controls shall function either as:p.527
p.528combined primary and secondary sidelit daylit zones in parking garages shall be shown on the plans; andp.529
p.529manual controls shall be capable of turning off or decreasing light levels below the light level set by the daylight responsive controls.
p.523SECTION 160.5 – MANDATORY LIGHTING REQUIREMENTS FOR INDOOR AND OUTDOOR SPACES
p.524SECTION 160.5 – MANDATORY LIGHTING REQUIREMENTS FOR INDOOR AND OUTDOOR SPACES
p.525SECTION 160.5 – MANDATORY LIGHTING REQUIREMENTS FOR INDOOR AND OUTDOOR SPACES
p.526SECTION 160.5 – MANDATORY LIGHTING REQUIREMENTS FOR INDOOR AND OUTDOOR SPACES
p.527SECTION 160.5 – MANDATORY LIGHTING REQUIREMENTS FOR INDOOR AND OUTDOOR SPACES
p.528SECTION 160.5 – MANDATORY LIGHTING REQUIREMENTS FOR INDOOR AND OUTDOOR SPACES
p.529SECTION 160.5 – MANDATORY LIGHTING REQUIREMENTS FOR INDOOR AND OUTDOOR SPACES