Exception 1 to Section 160.5(c)1: Signs.

p.530E. Demand Responsive Controls. See Section 110.12 for requirements for demand responsive

p.530lighting controls.

p.530F. Occupancy Sensing Controls interactions with Space-conditioning Systems. For space-

p.530conditioning system zones serving only spaces that are required to have occupancy sensing controls as specified in Sections 160.5(b)4Cv and vi, and where Table 120.1-A allows the ventilation air to be reduced to zero when the space is in occupied-standby mode, the space conditioning system shall be permitted to be controlled by occupancy sensing controls as specified in Section 120.2(e)3.

p.530(c) Outdoor lighting and control equipment. Multifamily buildings shall comply with the applicable

p.530requirements of Sections 160.5(c)1 through 160.5(c)2.

p.5301. Luminaire shielding requirements. All outdoor luminaires of 6,200 initial luminaire lumens or greater shall comply with Backlight, Uplight, and Glare (BUG) (in accordance with ANSI/IES TM- 15-20, Annex A) requirements in accordance with Title 24, Part 11, Section 5.106.8.

p.530SECTION 160.5 – MANDATORY LIGHTING REQUIREMENTS FOR INDOOR AND OUTDOOR SPACES