p.285SECTION 130.3 – SIGN LIGHTING CONTROLS
p.285Nonresidential buildings other than healthcare facilities and hotel/motel buildings shall comply with the applicable requirements of Sections 130.3(a)1 through 130.3(a)3.
p.285(a) Controls for sign lighting. All sign lighting shall meet the requirements below as applicable:
p.2851. Indoor signs. All indoor sign lighting other than exit sign lighting shall be controlled with an automatic time-switch control or astronomical time-switch control.
p.2852. Outdoor signs. Outdoor sign lighting shall meet the following requirements as applicable:
p.285A. All outdoor sign lighting shall be controlled with a photocontrol in addition to an
p.285automatic time-switch control, or an astronomical time-switch control.
p.285B. All outdoor sign lighting that is ON both day and night shall be controlled with a
p.285dimmer that provides the ability to automatically reduce sign lighting power by a minimum of 65 percent during nighttime hours. Signs that are illuminated at night and for more than 1 hour during daylight hours shall be considered ON both day and night.
p.2853. Demand responsive Electronic Message Center (EMC) control. See Section 110.12 for requirements for demand responsive EMC controls.