p.245i. Sealants shall comply with the applicable requirements of UL 181, UL 181A and UL 181B, and be nontoxic and water resistant.
p.246Insulation exposed to weather shall be suitable for outdoor service, e.g., protected by aluminum, sheet metal, painted canvas or plastic cover. Cellular foam insulation shall be protected as above or painted with a coating that is water retardant and provides shielding from solar radiation that can cause degradation of the material.
p.244SECTION 120.4 – REQUIREMENTS FOR AIR DISTRIBUTION SYSTEM DUCTS AND PLENUMS
p.245ii. Sealants for interior applications shall pass ASTM C731 (extrudability after aging) and D2202 (slump test on vertical surfaces), incorporated herein by reference.
p.244Nonresidential and hotel/motel buildings shall comply with the applicable requirements of Sections 120.4(a) through 120.4(g).
p.246(g) Duct sealing. Duct systems shall comply with Subsection 1 or 2 below:
p.245iii. Sealants for exterior applications shall pass ASTM tests C731, C732 (artificial weathering test),
p.245and D2202, incorporated herein by reference.
p.2461. New duct systems that meet the criteria in Subsections A, B, C and D below shall be sealed to a leakage rate not to exceed 6 percent of the nominal air handler airflow rate as confirmed through acceptance testing, in accordance with Reference Nonresidential Appendix NA7.5.3;
p.245iv. Sealants and meshes shall be rated for exterior use.
p.244(a) CMC compliance. All air distribution system ducts and plenums, including but not limited to building cavities,
p.245C. Pressure-sensitive tape. Pressure-sensitive tapes shall comply with the applicable requirements of UL
p.244mechanical closets, air-handler boxes and support platforms used as ducts or plenums, shall meet the requirements of the CMC Sections 601.0, 602.0, 603.0, 604.0, and 605.0, and ANSI/SMACNA-006-2006 HVAC Duct Construction Standards Metal and Flexible, 3rd Edition incorporated herein by reference. Connections of metal ducts and the inner core of flexible ducts shall be mechanically fastened. Openings shall be sealed with mastic, tape, aerosol sealant or other duct-closure system that meets the applicable requirements of UL 181, UL 181A, or UL 181B. If mastic or tape is used to seal openings greater than 1/4 inch, the combination of mastic and either mesh or tape shall be used.
p.246A. The duct system does not serve a healthcare facility; and
p.245181, UL 181A and UL 181B.
p.246B. The duct system provides conditioned air to an occupiable space for a constant volume, single zone,
p.245D. All ductwork and plenums with pressure class ratings shall be constructed to Seal Class A. Joints and
p.246space-conditioning system; and
p.245seams of duct systems and their components shall not be sealed with cloth-back rubber adhesive duct tapes unless such tape is used in combination with mastic and drawbands.
p.246C. The space-conditioning system serves less than 5,000 square feet of conditioned floor area; and
p.246D. The combined surface area of the ducts located outdoors or in unconditioned space is more than 25
p.246percent of the total surface area of the entire duct system.
p.244Portions of supply-air and return-air ducts conveying heated or cooled air located in one or more of the following spaces shall be insulated to a minimum installed level of R-8:
p.2462. New duct systems that are not subject to testing under Section 120.4(g)1 shall instead meet the duct leakage testing requirements of CMC Section 603.10.1.
p.245E. Drawbands used with flexible duct.
p.245i. Drawbands shall be either stainless-steel worm-drive hose clamps or UV-resistant nylon duct ties.
p.2441. Outdoors; or
p.245ii. Drawbands shall have a minimum tensile strength rating of 150 pounds.
p.2442. In a space between the roof and an insulated ceiling; or
p.2443. In a space directly under a roof with fixed vents or openings to the outside or unconditioned spaces; or
p.245iii. Drawbands shall be tightened as recommended by the manufacturer with an adjustable
p.245tensioning tool.
p.2444. In an unconditioned crawlspace; or
p.245F. Aerosol-sealant closures.
p.2445. In other unconditioned spaces.
p.245i. Aerosol sealants shall meet the requirements of UL 723 and be applied according to manufacturer specifications.
p.244Portions of supply-air ducts that are not in one of these spaces, including ducts buried in concrete slab, shall be insulated to a minimum installed level of R-4.2 or be enclosed in directly conditioned space.
p.245ii. Tapes or mastics used in combination with aerosol sealing shall meet the requirements of this section.
p.244(b) Duct and plenum materials.
p.245(c) All duct insulation product R-values shall be based on insulation only (excluding air films, vapor retarders or
p.2441. Factory-fabricated duct systems.
p.245other duct components) and tested C-values at 75°F mean temperature at the installed thickness, in accordance with ASTM C518 or ASTM C177, incorporated herein by reference, and certified pursuant to Section 110.8.
p.244A. All factory-fabricated duct systems shall comply with UL 181 for ducts and closure systems, including
p.244collars, connections and splices, and be labeled as complying with UL 181. UL 181 testing may be performed by UL laboratories or a laboratory approved by the Executive Director.
p.245(d) The installed thickness of duct insulation used to determine its R-value shall be determined as follows:
p.244B. All pressure-sensitive tapes, heat-activated tapes, and mastics used in the manufacture of rigid
p.244fiberglass ducts shall comply with UL 181 and UL 181A.
p.2451. For duct board, duct liner and factory-made rigid ducts not normally subjected to compression, the nominal insulation thickness shall be used.
p.244C. All pressure-sensitive tapes and mastics used with flexible ducts shall comply with UL 181 and UL
p.244181B.
p.2452. For duct wrap, installed thickness shall be assumed to be 75 percent (25 percent compression) of nominal thickness.
p.244D. All ductwork and plenums with pressure class ratings shall be constructed to Seal Class A. Joints and
p.244seams of duct systems and their components shall not be sealed with cloth-back rubber adhesive duct tapes unless such tape is used in combination with mastic and drawbands.
p.2453. For factory-made flexible air ducts, the installed thickness shall be determined by dividing the difference between the actual outside diameter and nominal inside diameter by two.
p.245(e) Insulated flexible duct products installed to meet this requirement must include labels, in maximum intervals of
p.2453 feet, showing the thermal performance R-value for the duct insulation itself (excluding air films, vapor retarder or other duct components), based on the tests in Section 120.4(c) and the installed thickness determined by Section 120.4(d)3. (f) Protection of insulation. Insulation shall be protected from damage, including that due to
p.2442. Field-fabricated duct systems.
p.244A. Factory-made rigid fiberglass and flexible ducts for field-fabricated duct systems shall comply with UL
p.244181. All pressure-sensitive tapes, mastics, aerosol sealants or other closure systems used for installing field-fabricated duct systems shall meet the applicable requirements of UL 181, UL 181A and UL 181B.
p.245sunlight, moisture, equipment maintenance and wind, but not limited to the following:p.246
p.244B. Mastic sealants and mesh.p.245
p.244SECTION 120.4 – REQUIREMENTS FOR AIR DISTRIBUTION SYSTEM DUCTS AND PLENUMS
p.245SECTION 120.4 – REQUIREMENTS FOR AIR DISTRIBUTION SYSTEM DUCTS AND PLENUMS
p.246SECTION 120.4 – REQUIREMENTS FOR AIR DISTRIBUTION SYSTEM DUCTS AND PLENUMS