Exception 1 to Section 160.3(c)1: Factory-installed piping within space-conditioning equipment certified under Section 110.1 or 110.2.

p.508WHERE:

p.509iii. In a space directly under a roof with fixed vents or openings to the outside or

p.510c. Pressure-sensitive tape. Pressure-sensitive tapes shall comply with the applicable

p.509unconditioned spaces; or

p.510requirements of UL 181, UL 181A and UL 181B.

Equation on PDF page 508: T = Minimum insulation thickness for material with conductivity K, inches.

Equation text: T = Minimum insulation thickness for material with conductivity K, inches.

Needs visual review

p.508

p.509iv. In an unconditioned crawl space; or

p.510d. Ductwork and plenums with pressure class ratings shall be constructed to Seal Class

p.510A. Joints and seams of duct systems and their components shall not be sealed with cloth back rubber adhesive duct tapes unless such tape is used in combination with mastic and drawbands.

Equation on PDF page 508: PR = Pipe actual outside radius, inches.

Equation text: PR = Pipe actual outside radius, inches.

Needs visual review

p.508

p.509v. In other unconditioned spaces.

p.509Portions of supply-air ducts that are not in one of these spaces, including ducts buried in concrete slab, shall be insulated to a minimum installed level of R-4.2 or be enclosed in directly conditioned space.

Equation on PDF page 508: t = Insulation thickness from TABLE 160.3-D, inches.

Equation text: t = Insulation thickness from TABLE 160.3-D, inches.

Needs visual review

p.508

p.510e. Drawbands used with flexible duct.

p.508K = Conductivity of alternate material at the mean rating temperature indicated in TABLE 160.3-D for the applicable fluid temperature range, in Btu- inch per hour per square foot per °F.

p.510I. Drawbands shall be either stainless-steel worm-drive hose clamps or UV-

p.509C. Duct and plenum materials.

p.510resistant nylon duct ties.

p.509i. Factory-fabricated duct systems.

p.510II. Drawbands shall have a minimum tensile strength rating of 150 pounds.

p.508k = The lower value of the conductivity range listed in TABLE 160.3-D for the applicable fluid temperature range, Btu-inch per hour per square foot per °F.

p.509a. All factory-fabricated duct systems shall comply with UL 181 for ducts and closure

p.510III. Drawbands shall be tightened as recommended by the manufacturer with an

p.509systems, including collars, connections and splices, and be labeled as complying with UL 181. UL 181 testing may be performed by UL laboratories or a laboratory approved by the Executive Director.

p.510adjustable tensioning tool.

p.510f. Aerosol-sealant closures.

p.509b. All pressure-sensitive tapes, heat-activated tapes and mastics used in the

p.510I. Aerosol sealants shall meet the requirements of UL 723 and be applied

p.509manufacture of rigid fiberglass ducts shall comply with UL 181 and UL 181A.

p.510according to manufacturer specifications.

p.509c. All pressure-sensitive tapes and mastics used with flexible ducts shall comply with

p.510II. Tapes or mastics used in combination with aerosol sealing shall meet the

p.509UL 181 and UL 181B.

p.510requirements of this section.

p.509d. Ductwork and plenums with pressure class ratings shall be constructed to Seal Class

p.510D. All duct insulation product R-values shall be based on insulation only (excluding air films,

p.509A. Joints and seams of duct systems and their components shall not be sealed with cloth back rubber adhesive duct tapes unless such tape is used in combination with mastic and drawbands.

p.510vapor retarders or other duct components) and tested C-values at 75°F mean temperature at the installed thickness, in accordance with ASTM C518 or ASTM C177, incorporated herein by reference, and certified pursuant to Section 110.8.

p.510E. The installed thickness of duct insulation used to determine its R-value shall be determined

p.510as follows:

p.5082. Requirements for air distribution system, ducts and plenum. Multifamily common areas shall comply with the applicable requirements of Sections 160.3(c)2A through 160.3(c)2F.

p.509ii. Field-fabricated duct systems.

p.510i. For duct board, duct liner and factory-made rigid ducts not normally subjected to

p.510compression, the nominal insulation thickness shall be used.

p.509a. Factory-made rigid fiberglass and flexible ducts for field-fabricated duct systems

p.508A. CMC compliance. All air distribution system ducts and plenums, including, but not limited

p.509shall comply with UL 181. All pressure-sensitive tapes, mastics, aerosol sealants or other closure systems used for installing field-fabricated duct systems shall meet the applicable requirements of UL 181, UL 181A and UL 181B.

p.510ii. For duct wrap, installed thickness shall be assumed to be 75 percent (25 percent

p.508to, building cavities, mechanical closets, air-handler boxes and support platforms used as ducts or plenums shall meet the requirements of CMC Sections 601.0, 602.0, 603.0, 604.0 and 605.0, and ANSI/SMACNA-006-2006 HVAC Duct Construction Standards Metal and Flexible 3rd Edition, incorporated herein by reference. Connections of metal ducts and the inner core of flexible ducts shall be mechanically fastened. Openings shall be sealed with mastic, tape, aerosol sealant or other duct-closure system that meets the applicable requirements of UL 181, UL 181A or UL 181B. If mastic or tape is used to seal openings greater than 1/4 inch, the combination of mastic and either mesh or tape shall be used.

p.510compression) of nominal thickness.

p.510iii. For factory-made flexible air ducts, the installed thickness shall be determined by

p.509b. Mastic sealants and mesh.

p.510dividing the difference between the actual outside diameter and nominal inside diameter by two.

p.509I. Sealants shall comply with the applicable requirements of UL 181, UL 181A and

p.509UL 181B, and be nontoxic and water resistant.

p.510F. Insulated flexible duct products installed to meet this requirement must include labels, in

p.510maximum intervals of 3 feet, showing the thermal performance R-value for the duct insulation itself (excluding air films, vapor retarder or other duct components), based on the tests in Section 160.3(c)2D and the installed thickness determined by Section 160.3(c)2Eiii.

p.509II. Sealants for interior applications shall pass ASTM C731 (extrudability after aging)

p.509and D2202 (slump test on vertical surfaces), incorporated herein by reference.

p.508B. Portions of supply-air and return-air ducts conveying heated or cooled air located in one or

p.508more of the following spaces shall be insulated to a minimum installed level of R-8:

p.509III. Sealants for exterior applications shall pass ASTM C731, C732 (artificial

p.509weathering test) and D2202, incorporated herein by reference.

p.508i. Outdoors; or

p.510G. Insulation shall be protected from damage, including that due to sunlight, moisture,

p.509IV. Sealants and meshes shall be rated for exterior use.p.510

p.510equipment maintenance and wind but not limited to the following: Insulation exposed to weather shall be suitable for outdoor service; e.g., protected by aluminum, sheet metal,

p.508ii. In a space between the roof and an insulated ceiling; orp.509

p.508SECTION 160.3 – MANDATORY REQUIREMENTS FOR SPACE CONDITIONING SYSTEMS IN MULTIFAMILY BUILDINGS

p.509SECTION 160.3 – MANDATORY REQUIREMENTS FOR SPACE CONDITIONING SYSTEMS IN MULTIFAMILY BUILDINGS

p.510SECTION 160.3 – MANDATORY REQUIREMENTS FOR SPACE CONDITIONING SYSTEMS IN MULTIFAMILY BUILDINGS