SECTION 120.1 – REQUIREMENTS FOR VENTILATION AND INDOOR AIR QUALITY (part 1 of 2)

Scanned crop of table from PDF page 226
Text in this table

2. Class 2 Air is air with moderate contaminant concentration, mild sensory-irritation intensity or mildly offensive odors (Class 2 air also includes air that is not necessarily harmful or objectionable but that is inappropriate for transfer or recirculation to spaces used for different purposes). Recirculation or transfer of Class 2 air shall be permitted in accordance with Sections 120.1(g)2A through 120.1(g)2E: A. Recirculation of Class 2 air within the space of origin shall be permitted [ASHRAE 62.1:5.13.3.2.1]; B. Recirculation or transfer of Class 2 to other Class 2 or Class 3 spaces shall be permitted, provided that the other spaces are used for the same or similar purpose or task and involve the same or similar pollutant sources as the Class 2 space [ASHRAE 62.1:5.13.3.2.2]; or C. Transfer of Class 2 air to toilet rooms [ASHRAE 62.1:5.13.3.2.3]; or D. Recirculation or transfer of Class 2 air to Class 4 spaces [ASHRAE 62.1:5.13.3.2.4]; or E. Class 2 air shall not be recirculated or transferred to Class 1 spaces. [ASHRAE 62.1:5.13.3.2.5] Exception to Section 120.1(g)2E: When using any energy recovery device, recirculation from leakage, carryover, or transfer from the exhaust side of the energy recovery device is permitted. Recirculated Class 2 air shall not exceed 10 percent of the outdoor air intake flow. 3. Class 3 Air is air with significant contaminant concentration, significant sensory-irritation intensity or offensive odor. Recirculation or transfer of Class 3 air shall be permitted in accordance with 120.1(g)3A and B: A. Recirculation of Class 3 air within the space of origin shall be permitted. [ASHRAE 62.1:5.13.3.3.1] B. Class 3 air shall not be recirculated or transferred to any other space. [ASHRAE 62.1:5.13.3.3.2]. Exception to Section 120.1(g)3B: When using any energy recovery device, recirculation from leakage, carryover, or transfer from the exhaust side of the energy recovery device is permitted. Recirculated Class 3 air shall not exceed 5 percent of the outdoor air intake flow. 4. Class 4 Air is air with highly objectionable fumes or gases or with potentially dangerous particles, bioaerosols, or gases at concentrations high enough to be considered as harmful. Class 4 air shall not be recirculated or transferred to any space or recirculated within the space of origin. [ASHRAE 62.1:5.13.3.4] 5. Ancillary spaces. Redesignation of Class 1 air to Class 2 air shall be permitted for Class 1 spaces that are ancillary to Class 2 spaces. [ASHRAE 62.1:5.13.2.3] 6. Transfer. A mixture of air that has been transferred through or returned from spaces or locations with different air classes shall be redesignated with the highest classification among the air classes mixed. [ASHRAE 62.1:5.13.2.2] 7. Classification. Air leaving each space or location shall be designated at an expected air-quality classification not less than that shown in Tables 120.1-A, 120.1-B or 120.1-C. Air leaving spaces or locations that are not listed in Tables 120.1-A, 120.1-B or 120.1-C shall be designated with the same classification as air from the most similar space or location listed in terms of occupant activities and building construction. (h) Ventilation only mechanical systems. HVAC systems without mechanical cooling or mechanical heating shall meet the requirements of Section 120.2(f).

Minimum Ventilation Rates for Educational Facilities p.227 Download CSV
Occupancy Category – Educational FacilitiesMinimum Occupant Load Density (persons / 1000 ft2)Area-based Minimum Ventilation Ra (cfm/ft2)Air ClassNotes
Daycare (through age 4)140.152--
Daycare sickroom50.153--
Classrooms (ages 5-8)250.151--
Classrooms (age 9 -18)250.151--
Lecture/postsecondary classroom250.151F
Lecture hall (fixed seats)710.151F
Art classroom250.152--
Science laboratories250.152--
University/college laboratories250.152--
Wood/metal shop100.152--
Computer lab250.151--
Media center250.151A
Music/theater/dance330.151F
Multiuse assembly330.151F
Occupancy Category - GeneralMinimum Occupant Load Density (persons / 1000 ft2)Area-based Minimum Ventilation Ra (cfm/ft2)Air ClassNotes
Break rooms330.151F
Coffee Stations330.151F
Conference/meeting330.151F
Corridors50.151F
Occupiable storage rooms for liquids or gels20.152B
Occupancy Category - Office BuildingsMinimum Occupant Load Density (persons / 1000 ft2)Area-based Minimum Ventilation Ra (cfm/ft2)Air ClassNotes
Breakrooms330.151--
Main entry lobbies330.151F
Occupiable storage rooms for dry materials20.151--
Office space50.151F
Reception areas50.151F
Telephone/data entry330.151F
Occupancy Category -Minimum Occupant Load Density (persons / 1000 ft2)Area-based Minimum Ventilation Ra (cfm/ft2)Air ClassNotes
General manufacturing (excludes heavy industrial and process using chemicals50.153
Pharmacy (prep. Area)50.152--
Photo studios50.151--
Shipping/receiving20.152B
Sorting, packing, light assembly20.152--
Telephone closets50.151--
Transportation waiting330.151F
Warehouses10.152B
All others50.152--
Occupancy Category - ResidentialMinimum Occupant Load Density (persons / 1000 ft2)Area-based Minimum Ventilation Ra (cfm/ft2)Air ClassNotes
Common corridors50.151F
Occupancy Category - Sports and EntertainmentMinimum Occupant Load Density (persons / 1000 ft2)Area-based Minimum Ventilation Ra (cfm/ft2)Air ClassNotes
Gym, sports arena (play area)100.152E
Spectator areas330.151F
Swimming (pool)100.152C
Swimming (deck)330.152C
Disco/dance floors1000.152F
Health club/aerobics room100.152
Health club/weight rooms100.152
Bowling alley (seating)70.151
Gambling casinos450.151
Game arcades450.151
Stages, studios330.151D, F
Minimum Ventilation Rates for Food and Beverage Service p.227 Download CSV
Occupancy Category - Food and Beverage ServiceMinimum Occupant Load Density (persons / 1000 ft2)Area-based Minimum Ventilation Ra (cfm/ft2)Air ClassNotes
Restaurant dining rooms330.152--
Cafeteria/fast-food dining330.152--
Bars, cocktail lounges330.22--
Kitchen (cooking)30.152--
Occupancy Category - Hotels, Motels, Resorts, DormitoriesMinimum Occupant Load Density (persons / 1000 ft2)Area-based Minimum Ventilation Ra (cfm/ft2)Air ClassNotes
Bedroom/living room30.151F
Barracks sleeping areas50.151F
Laundry rooms, central50.152--
Laundry rooms within dwelling units50.151--
Lobbies/pre-function330.151F
Multipurpose assembly330.151F
Occupancy Category - Miscellaneous SpacesMinimum Occupant Load Density (persons / 1000 ft2)Area-based Minimum Ventilation Ra (cfm/ft2)Air ClassNotes
Bank vaults/safe deposit50.152F
Banks or bank lobbies50.151F
Computer (not printing)50.151F
Freezer and refrigerated spaces (<50oF)002E
Occupancy Category - Public Assembly SpacesMinimum Occupant Load Density (persons / 1000 ft2)Area-based Minimum Ventilation Ra (cfm/ft2)Air ClassNotes
Auditorium seating area710.151F
Places of religious worship710.151F
Courtrooms130.151F
Legislative chambers130.151F
Libraries (reading rooms and stack areas)100.151--
Lobbies330.151F
Museums (children’s)170.151--
Museums/galleries170.151F
Occupancy Category - RetailMinimum Occupant Load Density (persons / 1000 ft2)Area-based Minimum Ventilation Ra (cfm/ft2)Air ClassNotes
Sales (except as below)170.22--
Mall common areas170.151F
Barbershop170.42--
Beauty and nail salons170.42--
Pet shops (animal areas)170.22--
Supermarket170.21F
Coin-operated laundries170.32--

p.2253. All mechanical ventilation and space-conditioning systems shall be tested to confirm their ability to operate within 10 percent of the design minimum outside air rate.

p.221Aface = Qfilter /Vface (Equation 120.1-A)

p.224A. Space conditioning zones shall include occupied standby controls complying with Section 120.1(d)5B

p.223A. an air economizer; or

p.224when all of the following are true:

p.225(g) Air classification and recirculation limitations. Air classification and recirculation limitations of air shall be

p.221Where:

p.223B. modulating outside air control; or

p.225based on the air classification as listed in Table 120.1-A or Table 120.1-C, and in accordance with the requirements of Sections 120.1(g)1 through 4.

p.224i. All rooms served by the zone are permitted to have their ventilation air reduced to zero while in

Equation on PDF page 221: Aface = air filter face area, the product of air filter nominal length × nominal width, ft2

Equation text: Aface = air filter face area, the product of air filter nominal length × nominal width, ft2

Needs visual review

p.221

p.224occupied-standby mode per Table 120.1-A; and

p.223C. design outdoor airflow rate > 3,000 cfm

Equation on PDF page 221: Qfilter = design airflow rate for the air filter, ft3/min

Equation text: Qfilter = design airflow rate for the air filter, ft3/min

Needs visual review

p.221

p.2223. Mechanical ventilation. Occupiable spaces shall be ventilated with a mechanical ventilation system capable of providing an outdoor airflow rate to the zone (Vz) no less than Equation 120.1-F as described below:

p.224ii. Occupant sensors are required by Section 130.1(c)5 and 6; and

Equation on PDF page 221: Vface = air filter face velocity ≤ 150, ft/min

Equation text: Vface = air filter face velocity ≤ 150, ft/min

Needs visual review

p.221

p.2251. Class 1 Air is air with low contaminant concentration, low sensory-irritation intensity or inoffensive odor. Recirculation or transfer of Class 1 air to any space shall be permitted; [ASHRAE 62.1:5.13.3.1]p.226

p.224iii. The zone and ventilation system is not served by pneumatic controls.

p.221D. Filter racks or grilles shall use gaskets, sealing or other means to close gaps around inserted filters and

p.224B. Occupied-standby zone controls shall comply with the following:p.225

Equation on PDF page 222: Vz = The larger of Rp × Pz or Ra × Az (Equation 120.1-F)

Equation text: Vz = The larger of Rp × Pz or Ra × Az (Equation 120.1-F)

Needs visual review

p.222

p.221prevent air from bypassing the filter.p.222

p.221SECTION 120.1 – REQUIREMENTS FOR VENTILATION AND INDOOR AIR QUALITY

p.222SECTION 120.1 – REQUIREMENTS FOR VENTILATION AND INDOOR AIR QUALITY

p.223SECTION 120.1 – REQUIREMENTS FOR VENTILATION AND INDOOR AIR QUALITY

p.224SECTION 120.1 – REQUIREMENTS FOR VENTILATION AND INDOOR AIR QUALITY

p.225SECTION 120.1 – REQUIREMENTS FOR VENTILATION AND INDOOR AIR QUALITY

p.226SECTION 120.1 – REQUIREMENTS FOR VENTILATION AND INDOOR AIR QUALITY

p.227SECTION 120.1 – REQUIREMENTS FOR VENTILATION AND INDOOR AIR QUALITY

p.228SECTION 120.1 – REQUIREMENTS FOR VENTILATION AND INDOOR AIR QUALITY