p.381A = PV capacity factor in W/square foot as specified in Table 140.10-A for the
p.382EQUATION 140.10-C - BATTERY ENERGY STORAGE SYSTEM MINIMUM RATED USABLE ENERGY CAPACITY, SARA-ADJUSTED
p.380SECTION 140.10 – PRESCRIPTIVE REQUIREMENTS FOR PHOTOVOLTAIC AND BATTERY ENERGY STORAGE SYSTEMS
p.381building type.
p.383Table 140.10-A PV Capacity Factors (W/ft2 of conditioned floor area)
p.384Table 140.10-B BESS Capacity Factors (Wh/ft2 of conditioned floor area)
Equation text: kWhbatt = [(CFA x B)/(1,000 x C0.5)] x (kWPVdc,SARA/kWPVdc)
Needs visual review
| Building Type | CZ 1 | CZ 2 | CZ 3 | CZ 4 | CZ 5 | CZ 6 | CZ 7 | CZ 8 | CZ 9 | CZ 10 | CZ 11 | CZ 12 | CZ 13 | CZ 14 | CZ 15 | CZ 16 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Events & Exhibits | 3.48 | 4.28 | 3.66 | 4.32 | 3.77 | 4.05 | 4.28 | 4.83 | 4.63 | 4.80 | 5.04 | 4.44 | 4.95 | 4.36 | 5.48 | 3.38 |
| Library | 0.39 | 3.23 | 2.59 | 3.25 | 2.48 | 2.74 | 3.04 | 3.49 | 3.32 | 3.69 | 3.79 | 3.32 | 3.79 | 3.37 | 4.49 | 2.84 |
| Hotel/Motel | 1.69 | 1.90 | 1.66 | 1.97 | 1.69 | 1.87 | 1.94 | 2.22 | 2.09 | 2.20 | 2.30 | 2.05 | 2.30 | 2.02 | 2.72 | 1.73 |
| Office, Financial Institution, Unleased Tenant Space, Medical Office Building/Clinic | 2.59 | 3.13 | 2.59 | 3.13 | 2.59 | 3.13 | 3.13 | 3.13 | 3.13 | 3.13 | 3.13 | 3.13 | 3.13 | 3.13 | 3.80 | 2.59 |
| Restaurants | 8.55 | 9.32 | 8.16 | 9.65 | 8.21 | 8.73 | 9.11 | 10.18 | 9.75 | 10.28 | 10.85 | 9.73 | 10.69 | 9.73 | 12.25 | 8.47 |
| Retail, Grocery | 3.14 | 3.49 | 3.01 | 3.61 | 3.05 | 3.27 | 3.45 | 3.83 | 3.65 | 3.81 | 4.09 | 3.64 | 3.99 | 3.71 | 4.60 | 3.21 |
| School | 1.27 | 1.63 | 1.27 | 1.63 | 1.27 | 1.63 | 1.63 | 1.63 | 1.63 | 1.63 | 1.63 | 1.63 | 1.63 | 1.63 | 2.46 | 1.27 |
| Warehouse | 0.39 | 0.44 | 0.39 | 0.44 | 0.39 | 0.44 | 0.44 | 0.44 | 0.44 | 0.44 | 0.44 | 0.44 | 0.44 | 0.44 | 0.58 | 0.39 |
| Religious Worship | 4.25 | 4.65 | 3.49 | 4.52 | 3.72 | 4.29 | 4.64 | 5.89 | 5.30 | 5.67 | 5.89 | 4.99 | 5.78 | 4.63 | 7.57 | 3.90 |
| Sports & Recreation | 2.47 | 1.97 | 1.54 | 2.03 | 1.60 | 1.84 | 1.98 | 2.63 | 2.47 | 2.60 | 2.75 | 2.20 | 2.72 | 2.15 | 4.03 | 1.81 |
| Multifamily > 3 stories | 1.82 | 2.21 | 1.82 | 2.21 | 1.82 | 2.21 | 2.21 | 2.21 | 2.21 | 2.21 | 2.21 | 2.21 | 2.21 | 2.21 | 2.77 | 1.82 |
| Building Type | CZ 1 | CZ 2 | CZ 3 | CZ 4 | CZ 5 | CZ 6 | CZ 7 | CZ 8 | CZ 9 | CZ 10 | CZ 11 | CZ 12 | CZ 13 | CZ 14 | CZ 15 | CZ 16 |
| Events & Exhibits | 1.82 | 1.95 | 1.74 | 2.12 | 1.91 | 2.13 | 2.24 | 2.30 | 2.36 | 2.47 | 2.62 | 2.16 | 2.64 | 2.68 | 3.22 | 1.89 |
| Library | 0.37 | 7.17 | 5.97 | 6.75 | 5.64 | 6.08 | 6.19 | 7.13 | 7.18 | 7.56 | 7.17 | 6.93 | 6.88 | 6.81 | 7.93 | 6.40 |
| Hotel/Motel | 0.86 | 0.84 | 0.77 | 0.92 | 0.81 | 0.89 | 0.90 | 1.01 | 1.00 | 1.11 | 1.14 | 0.96 | 1.18 | 1.18 | 1.49 | 0.85 |
| Office, Financial Institution, Unleased Tenant Space, Medical Office Building/Clinic | NR1 | 5.26 | 4.35 | 5.26 | 4.35 | 5.26 | 5.26 | 5.26 | 5.26 | 5.26 | 5.26 | 5.26 | 5.26 | 5.26 | 6.39 | 4.35 |
| Restaurants | 4.36 | 4.11 | 3.78 | 4.37 | 3.89 | 4.02 | 4.11 | 4.49 | 4.47 | 4.82 | 5.05 | 4.43 | 5.05 | 5.24 | 6.23 | 4.11 |
| Retail, Grocery | 1.89 | 1.82 | 1.71 | 1.82 | 1.72 | 1.80 | 1.76 | 1.92 | 1.97 | 2.05 | 2.22 | 1.95 | 2.16 | 2.29 | 2.66 | 1.91 |
| School | NR1 | 3.05 | 2.38 | 3.05 | 2.38 | 3.05 | 3.05 | 3.05 | 3.05 | 3.05 | 3.05 | 3.05 | 3.05 | 3.05 | 4.60 | 2.38 |
| Warehouse | NR1 | 0.41 | 0.37 | 0.41 | 0.37 | 0.41 | 0.41 | 0.41 | 0.41 | 0.41 | 0.41 | 0.41 | 0.41 | 0.41 | 0.54 | 0.37 |
| Religious Worship | 2.21 | 2.25 | 1.74 | 2.42 | 2.08 | 2.75 | 2.94 | 3.37 | 3.17 | 3.37 | 3.58 | 2.72 | 3.62 | 3.21 | 4.89 | 2.37 |
| Sports & Recreation | 1.26 | 0.98 | 0.76 | 1.14 | 0.86 | 1.20 | 1.23 | 1.57 | 1.53 | 1.65 | 1.83 | 1.27 | 1.86 | 1.57 | 3.02 | 1.13 |
| Multifamily > 3 stories | 1.88 | 2.27 | 1.88 | 2.27 | 1.88 | 2.27 | 2.27 | 2.27 | 2.27 | 2.27 | 2.27 | 2.27 | 2.27 | 2.27 | 2.85 | 1.88 |
p.380(a) Photovoltaic requirements. All newly constructed building types specified in Table
p.380140.10-A, or mixed occupancy buildings where at least 80 percent of the floor area of the building serves one or more of these building types shall have a newly installed photovoltaic (PV) system meeting the minimum qualification requirements of Reference Joint Appendix JA11. The PV capacity in kWdc shall not be less than the smaller of the minimum rated PV system capacity determined by Equation 140.10-A, or the total of all available solar access roof areas (SARA) multiplied by 18 for steep-sloped roofs or multiplied by 14 for low-sloped roofs. In mixed occupancy buildings, the minimum rated PV system capacity for the building shall be determined by applying Equation 140.10-A to the conditioned floor area of each of the listed building types and summing the capacities determined for each.
p.382kWhbatt = Minimum Rated Usable Energy Capacity of the BESS in kWh.
p.382CFA = Conditioned floor area that is subject to the PV system requirements of
p.382Section 140.10(a) in square feet.
p.382kWPVdc, = Minimum Rated PV System Capacity in kW from Equation 140.10-A
p.384Footnote to TABLE 140.10-B:
p.382kWPVdc, SARA = Minimum Rated PV System Capacity in kW from the SARA calculation.
p.382B = BESS Capacity Factor in Wh/square foot as specified in Table 140.10-B
p.382for the building type.
p.382C = Rated single charge-discharge cycle AC to AC (round-trip) efficiency of
p.382the BESS.
p.3801. SARA includes the area of the building’s roof space capable of structurally supporting a PV system, and the area of all roof space on covered parking areas, carports and all other newly constructed structures on the site that are compatible with supporting a PV system per Title 24, Part 2, Section 1511.10. 2. SARA does NOT include:
p.382EQUATION 140.10-D - BESS MINIMUM RATED POWER CAPACITY
p.381i. The tenant space is less than or equal to 2,000 square feet of conditioned space; ii. The tenant space is served by an HVAC system that does not serve other tenant
p.3841. NR = Not Required.
p.382kWbatt = kWhbatt / 4
p.381spaces in the building; and iii. The tenant space has an individual utility meter to track electricity consumption that
p.381does not include the electricity consumption of other tenant spaces in the building. This exception does not apply where the Commission has approved a community solar program for showing compliance as specified in Title 24, Part 1, Section 10-115, or where a load-serving entity provides a program where PV generation is compensated through virtual energy bill credits for occupants of nonresidential and hotel/motel tenant spaces to receive energy bill benefits from netting of energy generation and consumption.
p.380A. Any area that has less than 70 percent annual solar access. Annual solar access is
p.382kWbatt = Minimum Rated Power Capacity of the BESS in kWdc.
p.380determined by dividing the total annual solar insolation (accounting for shading obstructions) by the total annual solar insolation if the same areas were unshaded by those obstructions. For all roofs, all obstructions, including those that are external to the building, and obstructions that are part of the building design and elevation features may be considered for the annual solar access calculations.
p.382kWhbatt = Minimum Rated Useable Energy Capacity of the BESS in kWh .
p.381(b) Battery energy storage system (BESS) requirements. All buildings that are required by
p.380B. Occupied roofs as specified by CBC Section 503.1.4.
p.381Section 140.10(a) to have a PV system shall also have a BESS meeting the minimum qualification requirements of Reference Joint Appendix JA12. The rated energy capacity shall be not less than the Minimum Rated Useable Energy Capacity determined using Equation 140.10-B or 140.10-C if SARA was used to determine the PV capacity in Section 140.10(a). The rated power capacity shall be not less than the Minimum Power Capacity determined using Equation 140.10-D. In mixed occupancy buildings, the total battery system capacity for the building shall be determined by applying the Minimum Rated Usable Energy Capacity to each of the listed building types and summing the capacities determined for each.
p.380C. Roof area that is otherwise not available due to compliance with:
p.380a. Other state building code requirements, or
p.380b. Local building code requirements if the local building code requirements are confirmed by the Executive Director.
p.383SECTION 140.10 – PRESCRIPTIVE REQUIREMENTS FOR PHOTOVOLTAIC AND BATTERY ENERGY STORAGE SYSTEMS
p.384SECTION 140.10 – PRESCRIPTIVE REQUIREMENTS FOR PHOTOVOLTAIC AND BATTERY ENERGY STORAGE SYSTEMS
p.380EQUATION 140.10-A PHOTOVOLTAIC DIRECT CURRENT CAPACITY kWPVdc = (CFA x A)/1000
p.381EQUATION 140.10-B - BATTERY ENERGY STORAGE SYSTEM MINIMUM RATED USABLE ENERGY CAPACITY
p.380kWPVdc = Minimum rated PV system capacity in kW.
Equation text: kWhbatt= [(CFA x B)/(1,000 x C0.5)]
Needs visual review
p.380CFA = Conditioned floor area in square feet.p.381
p.380SECTION 140.10 – PRESCRIPTIVE REQUIREMENTS FOR PHOTOVOLTAIC AND BATTERY ENERGY STORAGE SYSTEMS
p.381SECTION 140.10 – PRESCRIPTIVE REQUIREMENTS FOR PHOTOVOLTAIC AND BATTERY ENERGY STORAGE SYSTEMS
p.382SECTION 140.10 – PRESCRIPTIVE REQUIREMENTS FOR PHOTOVOLTAIC AND BATTERY ENERGY STORAGE SYSTEMS