SECTION 120.2 – REQUIRED CONTROLS FOR SPACE-CONDITIONING SYSTEMS

p.236C. Meet the requirements of Section 110.2(c).

p.2374. Hotel and motel guest rooms shall have captive card key controls, occupancy sensing controls or automatic controls such that, no longer than 30 minutes after the guest room has been vacated, setpoints are set up at least +5°F (+3°C) in cooling mode and set down at least -5°F (-3°C) in heating mode.

p.238B. Annunciated locally on one or more zone thermostats, or a device within five (5) feet of zone

p.239Table 120.2-A DDC Applications and Qualifications

p.235SECTION 120.2 – REQUIRED CONTROLS FOR SPACE-CONDITIONING SYSTEMS

p.238thermostat(s), clearly visible, at eye level, and meeting the following requirements:

Building StatusApplicationsQualifications
Newly Constructed BuildingsAir-handling system and all zones served by the systemIndividual systems supplying more than three zones and with design heating or cooling capacity of 300 kBtu/h and larger
Newly Constructed BuildingsChilled water plant and all coils and terminal units served by the systemIndividual plants supplying more than three zones and with design cooling capacity of 300 kBtu/h (87.9 kW) and larger
Newly Constructed BuildingsHot water plant and all coils and terminal units served by the systemIndividual plants supplying more than three zones and with design heating capacity of 300 kBtu/h (87.9 kW) and larger
Additions or AlterationsZone terminal unit such as VAV boxWhere existing zones served by the same air-handling, chilled water, or hot water systems that have DDC
Additions or AlterationsAir-handling system or fan coilWhere existing air-handling system(s) and fan coil(s) served by the same chilled or hot water plant have DDC
Additions or AlterationsNew air-handling system and all new zones served by the systemIndividual systems with design heating or cooling capacity of 300 kBtu/h and larger and supplying more than three zones and more than 75 percent of zones are new
Additions or AlterationsNew or upgraded chilled water plantWhere all chillers are new and plant design cooling capacity is 300 kBtu/h (87.9 kW) and larger
Additions or AlterationsNew or upgraded hot water plantWhere all boilers are new and plant design heating capacity is 300 kBtu/h (87.9 kW) and larger

p.235Nonresidential and hotel/motel buildings shall comply with the applicable requirements of Sections 120.2(a) through 120.2(l).

p.238i. On the thermostat, device, or an adjacent written sign, display instructions to contact appropriate building personnel or an HVAC technician; and

p.236(d) Heat pump controls. All heat pumps with supplementary electric resistance heaters shall be installed with

p.235(a) Thermostatic controls for each zone. The supply of heating and cooling energy to each space-conditioning

p.237(f) Dampers for air supply and exhaust equipment. Outdoor air supply and exhaust equipment shall be

p.238ii. In buildings with multiple tenants, the annunciation shall either be within property management offices or in a common space accessible by the property or building manager.

p.236controls that comply with Section 110.2(b).

p.235zone or dwelling unit shall be controlled by an individual thermostatic control that responds to temperature within the zone and that meets the applicable requirements of Section 120.2(b). An Energy Management Control System (EMCS) may be installed to comply with the requirements of one or more thermostatic controls if it complies with all applicable requirements for each thermostatic control.

p.237installed with dampers that automatically close upon fan shutdown.

p.236(e) Shut-off and reset controls for space-conditioning systems. Each space-conditioning system shall be

p.238C. Reported to a fault management application which automatically provides notification of the fault to a remote HVAC service provider.

p.236installed with controls that comply with the following:

p.2361. The control shall be capable of automatically shutting off the system during periods of nonuse and shall

p.2387. The FDD system shall detect the following faults:

p.238A. Air temperature sensor failure/fault;

p.236A. An automatic time switch control device complying with Section 110.9 with an accessible manual

p.236override that allows operation of the system for up to 4 hours; or

p.238B. Not economizing when it should;

p.2351. All zones are also served by an interior cooling system; and

p.236B. An occupancy sensor; or

p.238C. Economizing when it should not;

p.2352. The perimeter system is designed solely to offset envelope heat losses or gains; and

p.237(g) Isolation area devices. Each space-conditioning system serving multiple zones with a combined conditioned

p.236C. A 4-hour timer that can be manually operated.

p.238D. Damper not modulating; and

p.2353. The perimeter system has at least one thermostatic control for each building orientation of 50 feet or

p.237floor area of more than 25,000 square feet shall be designed, installed, and controlled to serve isolation areas.

p.238E. Excess outdoor air.

p.2371. Each zone, or any combination of zones not exceeding 25,000 square feet, shall be a separate isolation area.

p.2354. The perimeter system is controlled by at least one thermostat located in one of the zones served by the

p.2388. The FDD System shall be certified to the Energy Commission as meeting requirements of Subsections 120.2(i)1 through 120.2(i)7 in accordance with Section 110.0 and JA6.3.

p.2362. The control shall automatically restart and temporarily operate the system as required to maintain:

p.2372. Each isolation area shall be provided with isolation devices, such as valves or dampers, that allow the supply of heating or cooling to be reduced or shut off independently of other isolation areas.

p.235(b) Criteria for zonal thermostatic controls. The individual thermostatic controls required by Section 120.2(a)

p.236A. A setback heating thermostat setpoint if the system provides mechanical heating; and

p.235shall meet the following requirements as applicable:

p.2373. Each isolation area shall be controlled by a device meeting the requirements of Section 120.2(e)1.

p.2351. Where used to control comfort heating, the thermostatic controls shall be capable of being set, locally or remotely, down to 55°F or lower.

p.238(j) Direct Digital Controls (DDC). Direct Digital Controls to the zone shall be provided as specified by Table 120.2-A.

p.238The provided DDC system shall meet the control logic requirements of Sections 120.1(d), 110.12(a) and 110.12(b), and be capable of the following:

p.2352. Where used to control comfort cooling, the thermostatic controls shall be capable of being set, locally or remotely, up to 85°F or higher.

p.237(h) Automatic demand shed controls. See Section 110.12 for requirements for automatic demand shed

p.236B. A setup cooling thermostat setpoint if the system provides mechanical cooling.

p.237controls.

p.2381. Monitoring zone and system demand for fan pressure, pump pressure, heating and cooling;

p.2353. Where used to control both comfort heating and comfort cooling, the thermostatic controls shall meet Items 1 and 2 and shall be capable of providing a temperature range or dead band of at least 5°F within which the supply of heating and cooling energy to the zone is shut off or reduced to a minimum.

p.237(i) Economizer fault detection and diagnostics (FDD). All newly installed air handlers with a mechanical

p.2382. Transferring zone and system demand information from zones to air distribution system controllers and from air distribution systems to heating and cooling plant controllers;

p.237cooling capacity over 33,000 Btu/hr and an installed air economizer shall include a stand-alone or integrated Fault Detection and Diagnostics (FDD) system in accordance with Subsections 120.2(i)1 through 120.2(i)8.

p.2363. Occupant sensing zone controls. Where the system providing space conditioning also provides the ventilation required by Section 120.1 and includes occupant sensor ventilation control as specified in Section 120.1(d)5, the occupant sensing zone controls shall additionally comply with the following:

p.2383. Automatically detecting the zones and systems that may be excessively driving the reset logic and generate an alarm or other indication to the system operator;

p.2371. The following temperature sensors shall be permanently installed to monitor system operation: outside air, supply air, and when required for differential economizer operation a return air sensor, and

p.2384. Readily allow operator removal of zone(s) from the reset algorithm;

p.236A. In 5 minutes or less after entering occupied-standby mode as described in Section 120.1(d).

p.2372. Temperature sensors shall have an accuracy of ±2°F over the range of 40°F to 80°F; and

p.2385. For new buildings, trending and graphically displaying input and output points; and

p.2354. Thermostatic controls for all single zone, air conditioners and heat pumps shall comply with the requirements of Sections 110.2(c) and 110.12(a) and, if equipped with DDC to the Zone level, with the Automatic Demand Shed Controls of Section 110.12(b).

p.236i. Automatically set up the operating cooling temperature set point by 2°F or more and set back the operating heating temperature set point by 2°F or more; or

p.2373. The controller shall have the capability of displaying the value of each sensor; and

p.2386. Resetting heating and cooling setpoints in all noncritical zones upon receipt of a signal from a centralized contact or software point as described in Section 110.12(b).p.239

p.2374. The controller shall provide system status by indicating the following conditions:

p.236ii. For multiple zone systems with Direct Digital Controls (DDC) to the zone level, setup the operating cooling temperature setpoint by 0.5°F or more and setback the operating heating temperature setpoint by 0.5°F or more.

p.237A. Free cooling available;

p.237B. Economizer enabled;

p.239(k) Optimum start/stop controls. Space conditioning systems with DDC to the zone level shall have optimum

p.236B. In 5 minutes or less after entering occupied-standby mode, mechanical ventilation to the zone shall

p.237C. Compressor enabled;

p.239start/stop controls. The control algorithm shall, as a minimum, be a function of the difference between space temperature and occupied setpoint, the outdoor air temperature, and the amount of time prior to scheduled occupancy. Mass radiant floor slab systems shall incorporate floor temperature onto the optimum start algorithm.

p.236remain off whenever the space temperature is between the active heating and cooling setpoints.

p.237D. Heating enabled, if the system is capable of heating; and

p.237E. Mixed-air low limit cycle active.

p.235(c) Hotel/motel guest room thermostats.

p.2375. The unit controller shall allow manual initiation of each operating mode so that the operation of cooling systems, economizers, fans and heating system can be independently tested and verified; and

p.2351. Hotel/motel guest room thermostats shall:

p.239(l) HVAC Hot Water Temperature. Zones that use hot water for space heating shall be designed for a hot water

p.2376. Faults shall be reported in one of the following ways:

p.235A. Have numeric temperature setpoints in °F and °C; and

p.237A. Reported to an Energy Management Control System regularly monitored by facility personnel.p.238

p.239supply temperature of no greater than 130 °F.p.240

p.235B. Have setpoint stops, which are accessible only to authorized personnel, such that guest room

p.235occupants cannot adjust the setpoint more than ±5°F (±3°C); andp.236

p.235SECTION 120.2 – REQUIRED CONTROLS FOR SPACE-CONDITIONING SYSTEMS

p.236SECTION 120.2 – REQUIRED CONTROLS FOR SPACE-CONDITIONING SYSTEMS

p.237SECTION 120.2 – REQUIRED CONTROLS FOR SPACE-CONDITIONING SYSTEMS

p.238SECTION 120.2 – REQUIRED CONTROLS FOR SPACE-CONDITIONING SYSTEMS

p.239SECTION 120.2 – REQUIRED CONTROLS FOR SPACE-CONDITIONING SYSTEMS

p.240SECTION 120.2 – REQUIRED CONTROLS FOR SPACE-CONDITIONING SYSTEMS