SECTION 120.1 – REQUIREMENTS FOR VENTILATION AND INDOOR AIR QUALITY (part 2 of 2)

p.234H – Rate is per showerhead

Minimum Exhaust Rates p.233 Download CSV
Occupancy CategoryExhaust Rate, cfm/unitExhaust Rate, cfm/ft2Air ClassNotes
Animal imaging(MRI/CT/PET)-0.93-
Animal operating rooms-3.003-
Animal postoperative recovery room-1.53-
Animal preparation rooms-1.53-
Animal procedure room-2.253-
Animal surgery scrub-1.503-
Large-animal holding room-2.253-
Animal Necropsy-2.253-
Small-animal-cage room (static cages)-2.253-
Small-animal-cage room (ventilated cages)-1.503-
Arenas-0.501B
Art classrooms-0.702-
Auto repair rooms-1.52A
Barber shops-0.502-
Beauty and nail salons-0.602-
Cells with toilet-1.002-
Copy, printing rooms-0.502-
Darkrooms-1.002-
Educational science laboratories-1.002-
Janitor closets, trash rooms, recycling-1.003-
Kitchenettes-0.302-
Kitchens – commercial-0.702-
Locker rooms for athletic or industrial facilities-0.502-
All other locker rooms-0.252-
Shower rooms20/50-2G,H
Paint spray booths--4F
Parking garages-0.752C
Pet shops (animal areas)-0.902-
Refrigerating machinery rooms--3F
Soiled laundry storage rooms-1.003F
Storage rooms, chemical-1.504F
Toilets – private25/50-2E
Toilets – public50/70-2D
Woodwork shop/classrooms-0.502-

p.234Table 120.1-C – Airstreams or Sources [ASHRAE 62.1: Table 6-3]

Airstreams or Sources [ASHRAE 62.1:Table 5.16.16-3] p.234 Download CSV
DescriptionAir Class
Commercial kitchen grease hoods4
Commercial kitchen hoods other than grease3
Diazo printing equipment discharge4
Hydraulic elevator machine room2
Laboratory hoods4a
Paint spray booths4
Refrigerating machinery rooms3

p.234a. Air Class 4 unless determined otherwise by the Environmental Health and Safety professional responsible to

p.234the owner or to the owner’s designee.

p.233A – Stands where engines are run shall have exhaust systems that directly connect to the engine exhaust and

p.233prevent escape of fumes. B – Where combustion equipment is intended to be used on the playing surface, additional dilution

p.233ventilation, source control, or both shall be provided. C – Exhaust shall not be required where two or more sides comprise walls that are at least 50% open to the

p.233outside. D – Rate is per water closet, urinal, or both. Provide the higher rate where periods of heavy use are expected

p.233to occur. The lower rate shall be permitted to be used otherwise. E – Rate is for a toilet room intended to be occupied by one person at a time. For continuous systems

p.233operation during hours of use, the lower rate shall be permitted to be used. Otherwise the higher rate shall be used. F – See other applicable standards for exhaust rate. G – For continuous system operation, the lower rate shall be permitted to be used. Otherwise the higher rate

p.233shall be used.p.234

p.233SECTION 120.1 – REQUIREMENTS FOR VENTILATION AND INDOOR AIR QUALITY

p.234SECTION 120.1 – REQUIREMENTS FOR VENTILATION AND INDOOR AIR QUALITY