SECTION 130.1 – MANDATORY INDOOR LIGHTING CONTROLS

p.280ii. No more than 500 watts of rated lighting power shall be controlled together as a single

p.281A. All skylit daylit zones, primary sidelit daylit zones, secondary sidelit daylit zones, and the

p.2783. If an automatic time-switch control is installed to comply with Section 130.1(c)1, it shall incorporate a manual override lighting control that allows the lighting to remain ON for no more than 2 hours when an override is initiated.

p.276SECTION 130.1 – MANDATORY INDOOR LIGHTING CONTROLS

p.280zone; and

p.281combined primary and secondary sidelit daylit zones in parking garages shall be shown on the plans”; and

p.276Nonresidential and hotel/motel buildings shall comply with the applicable requirements of Sections 130.1(a) through 130.1(f), in addition to the applicable requirements of Sections 110.9 and 130.0.

p.280iii. The occupant sensing controls shall be capable of automatically turning the lighting fully

p.279B. In library book stack aisles 10 feet or longer that are accessible from only one end, and

p.280ON only in the separately controlled zone and shall be automatically activated from all designed paths of egress.

p.277(c) Shut-OFF Controls. All installed indoor lighting shall be equipped with controls able to

p.276(a) Manual controls. Each space shall be provided with lighting controls that allow the lighting in that

p.279library book stack aisles 20 feet or longer that are accessible from both ends, lighting shall be controlled with occupant sensing controls that automatically reduce lighting power by at least 50 percent when the areas are unoccupied. The occupant sensing controls shall independently control lighting in each aisle way, and shall not control lighting beyond the aisle way being controlled by the sensor.

p.277automatically reduce lighting power when the space is typically unoccupied.

p.276space to be manually turned on and off. The manual control shall:

p.280Interior areas of parking garages are under the classification of indoor lighting and shall comply with Section 130.1(c)6E. Parking areas on the roof of a parking structure are under the classification of outdoor hardscape and shall comply with Section 130.2.

p.281B. The daylight responsive controls shall provide separate control for general lighting in each type

p.2761. Be readily accessible; and

p.281of daylit zone. The daylight responsive controls shall meet the following:

p.2784. If an automatic time-switch control is installed to comply with Section 130.1(c)1, it shall incorporate an automatic holiday “shut-OFF” feature that turns OFF all loads for at least 24 hours, and then resumes the normally scheduled operation.

p.281i. General lighting in overlapping skylit daylit zone and sidelit daylit zone shall be controlled as part of the skylit daylit zone.

p.2807. Reserved.

p.279C. In corridors and stairwells, lighting shall be controlled by occupant sensing controls that

p.2808. Hotel/motel guest rooms shall be controlled with one of the following controls such that, no longer than 20 minutes after the guest room has been vacated, lighting power is switched off:

p.281ii. General lighting in overlapping primary and secondary sidelit daylit zones shall be controlled as part of the primary sidelit daylit zone.

p.279separately reduce the lighting power in each space by at least 50 percent when the space is unoccupied. The occupant sensing controls shall be capable of automatically turning the lighting fully ON only in the separately controlled space, and shall be automatically activated from all designed paths of egress. Lighting in stairwells and common area corridors that provide access to guestrooms of hotel/motels shall meet the requirements of this section instead of complying with Section 130.1(c)1.

p.2762. Be located in the same space, or be located such that the controlled lighting or the status of the controlled lighting can be seen when operating the controls; and

p.280i. Captive card key controls; or

p.281iii. General lighting luminaires longer than 8 feet shall be controlled as segments of 8 feet or less according to the type of the daylit zone in which the segment is primarily located; and

p.2771. All installed indoor lighting shall be equipped with controls that meet the following requirements:

p.280ii. Occupant sensing controls; or

p.2785. Occupant sensing controls. In offices 250 square feet or smaller, multipurpose rooms of less than 1,000 square feet, classrooms, conference rooms, and restrooms, lighting shall be controlled with occupant sensing controls to automatically shut OFF all of the lighting in 20 minutes or less after the control zone is unoccupied.

p.280iii. Other automatic controls.

p.277A. Shall be controlled with an occupant sensing control set to no more than a 20-minute time

p.2763. Provide separate control of general, floor display, wall display, window display, case display, ornamental, and special effects lighting, such that each type of lighting can be turned on or off without turning on or off other types of lighting. Scene controllers may comply with this requirement provided that at least one scene turns on general lighting only, and the control provides a means to manually turn off all lighting.

p.279D. In office spaces greater than 250 square feet, general lighting shall be controlled with

p.277delay, automatic time-switch control, or other control capable of automatically shutting OFF all of the lighting when the space is typically unoccupied; and

p.279occupant sensing controls that meet all of the following:

p.279i. The occupant sensing controls shall be configured so that lighting shall be controlled

p.281C. The daylight responsive controls shall meet the following:

p.277B. Separate controls for the lighting on each floor, other than lighting in stairwells; and

p.278In areas required by Section 130.1(b) to have multi-level lighting controls, the occupant sensing controls shall function either as a:

p.279separately in control zones not greater than 600 square feet. All control zones in offices greater than 250 square feet shall be shown on the plans; and

p.280(d) Daylight responsive controls.

p.282(e) Demand responsive controls. See Section 110.12 for requirements for demand responsive lighting

p.277C. Separate control zones for a space enclosed by ceiling height partitions not exceeding 5,000

p.281i. For spaces where the installation of multilevel lighting controls is required under Section

p.282controls.

p.2801. Daylight responsive controls shall be installed in the following locations as applicable:

p.277square feet.

p.278A. Partial-ON occupant sensing controls capable of automatically activating between 50 and

p.281130.1(b), allow the multilevel lighting controls to adjust the light level with continuous dimming;

p.279ii. In 20 minutes or less after the control zone is unoccupied, the occupant sensing

p.282(f) Occupancy sensing controls interactions with space-conditioning systems. For space-conditioning

p.27870 percent of controlled lighting power, or

p.280A. In any enclosed space where the total installed wattage of general lighting luminaires

p.279controls shall uniformly reduce lighting power in the control zone to no more than 20 percent of full power. Control functions that switch control zone lights completely off when the zone is vacant meet this requirement; and

p.282system zones serving only spaces that are required to have occupant sensing controls as specified in Sections 130.1(c)5 and 6, and where Table 120.1-A allows the ventilation air to be reduced to zero when the space is in occupied-standby mode, the space-conditioning system shall be permitted to be controlled by occupancy sensing controls as specified in Section 120.2(e)3.

p.280completely or partially within skylit daylit zones is 75 watts or greater, the general lighting in the skylit daylit zones shall be controlled by daylight responsive controls.

p.278B. Vacancy sensing controls, where all lighting responds to a manual ON input only.

p.281ii. For each space, ensure the combined illuminance from the controlled lighting and daylight is

p.281not less than the illuminance from controlled lighting when no daylight is available;

p.278In areas not required by Section 130.1(b) to have multilevel lighting controls, the occupant sensing controls shall function either as:

p.2761. The space is designated for means of egress on the plans and specifications submitted to the enforcement agency under Section 10-103(a)2 of Part 1; and

p.280B. In any enclosed space where the total installed wattage of general lighting luminaires

p.281iii. For areas other than parking garages, ensure that, when the daylight illuminance is greater

p.279iii. In 20 minutes or less after the entire office space is unoccupied, the occupant sensing

p.280completely or partially within primary sidelit daylit zones is 75 watts or greater, the general lighting in the primary sidelit daylit zones shall be controlled by daylight responsive controls.

p.281than 150 percent of the illuminance provided by the controlled lighting when no daylight is available, the controlled lighting power in that daylight zone shall be reduced by a minimum of 90 percent; and

p.279controls shall automatically turn off lighting in all control zones in the space; and

p.278A. Automatic full-on occupant sensing controls; or

p.2762. The egress lighting controls shall not be controllable by unauthorized personnel during a normal power failure.

p.279iv. In each control zone, lighting shall be allowed to automatically turn on to any level up to

p.278B. Partial-ON occupant sensing controls, or

p.279full power upon occupancy within the control zone. When occupancy is detected in any control zone in the space, the lighting in other control zones that are unoccupied shall operate at no more than 20 percent of full power.

p.278C. Vacancy sensing controls, where all lighting responds to a manual ON input only.

p.280C. In any enclosed space where the total wattage of general lighting luminaires in the

p.281iv. For parking garages, ensure that when daylight illuminance levels measured at the farthest

p.276(b) Multilevel lighting controls. The general lighting of any space with a size of 100 square feet or

p.280secondary zones is 75 watts or greater, the general lighting in the secondary sidelit daylit zones shall be controlled by daylight responsive controls. General lighting in the secondary sidelit daylit zones shall be controlled independently of general lighting in the primary sidelit daylit zones.

p.281edge of the secondary sidelit zone away from the glazing or opening are greater than 150 percent of the illuminance provided by the controlled lighting when no daylight is available, the controlled lighting power in the combined primary and secondary sidelit daylit zones shall be reduced by 100 percent; and

p.278In addition, controls shall be provided that allow the lights to be manually shut OFF in accordance with Section 130.1(a) regardless of the sensor status.

p.276larger and with a connected lighting load greater than 0.5 watts per square foot shall be provided with multilevel lighting controls. The multilevel lighting controls shall provide and enable continuous dimming from 100 percent to 10 percent or lower of lighting power.

p.2786. Full or partial-OFF occupant sensing controls. For warehouse aisle ways, warehouse open areas, library book stack aisles, corridors, stairwells, offices greater than 250 square feet, parking garages, parking areas, loading areas, and unloading areas, the installed lighting shall meet the following requirements:

p.279E. In parking garages, parking areas and loading and unloading areas, general lighting shall be

p.280D. For skylights located in an atrium, the skylit daylit zone definition shall apply to the floor

p.281D. Photosensors shall be located so that they are not readily accessible to unauthorized

p.279controlled by occupant sensing controls that meet the requirements below instead of complying with Section 130.1(c)1:

p.280area directly under the atrium and the top floor area directly adjacent to the atrium.

p.281personnel; and

p.2772. Countdown timer switches may be used to comply with the automatic shut-OFF control requirements in Section 130.1(c)1 only in closets less than 70 square feet, and server aisles in server rooms. The maximum timer setting shall be 10 minutes for closets, and 30 minutes for server aisles.p.278

p.280E. Parking garage areas where the total installed wattage of the general lighting in the primary

p.281E. The location where calibration adjustments are made to the daylight responsive controls shall

p.278A. In warehouse aisle ways and warehouse open areas, lighting shall be controlled with

p.279i. The occupant sensing controls shall uniformly reduce lighting power in the control zone

p.280and the secondary sidelit daylit zones is 60 watts or greater, the general lighting in the primary and secondary sidelit daylit zones shall be controlled by daylight responsive controls.

p.281be readily accessible to authorized personnel but may be inside a locked case or under a cover which requires a tool for access; and

p.278occupant sensing controls that automatically reduce lighting power by at least 50 percent when the areas are unoccupied. The occupant sensing controls shall independently control lighting in each warehouse aisle way, and shall not control lighting beyond the aisle way being controlled by the sensor.p.279

p.279to between 20 percent and 50 percent of full power and with at least one control step; andp.280

p.281F. The automatic daylighting control shall permit the multilevel lighting control to adjust the level

p.2802. All daylight responsive controls shall meet the following requirements:p.281

p.281of lighting.p.282

p.276SECTION 130.1 – MANDATORY INDOOR LIGHTING CONTROLS

p.277SECTION 130.1 – MANDATORY INDOOR LIGHTING CONTROLS

p.278SECTION 130.1 – MANDATORY INDOOR LIGHTING CONTROLS

p.279SECTION 130.1 – MANDATORY INDOOR LIGHTING CONTROLS

p.280SECTION 130.1 – MANDATORY INDOOR LIGHTING CONTROLS

p.281SECTION 130.1 – MANDATORY INDOOR LIGHTING CONTROLS

p.282SECTION 130.1 – MANDATORY INDOOR LIGHTING CONTROLS