SECTION 120.6 – MANDATORY REQUIREMENTS FOR COVERED PROCESSES (part 1 of 2)
TRANSCRITICAL CO2 FAN-POWERED GAS COOLERS – MINIMUM EFFICIENCY REQUIREMENTS p.256 Download CSV
| CONDENSER TYPE | REFRIGERANT TYPE | MINIMUM EFFICIENCY | RATING CONDITION |
| Outdoor Air-Cooled | Transcritical CO2 | 160 Btuh/watt | 1400 psig, 100°F Outlet Gas Temperature, 90°F Outdoor Dry bulb Temperature |
|---|
| Adiabatic Dry Mode | Transcritical CO2 | 90 Btuh/watt | 1100 psig, 100°F Outlet Gas Temperature, 90°F Outdoor Dry bulb Temperature |
FAN-POWERED CONDENSERS –SPECIFIC EFFICIENCY REQUIREMENTS p.257 Download CSV
| CONDENSER TYPE | MINIMUM SPECIFIC EFFICIENCYa | RATING CONDITION |
| Evaporative-Cooled | 160 Btuh/watt | 100°F Saturated Condensing Temperature (SCT), 70°F Entering Wetbulb Temperature |
|---|
| Air-Cooled | 65 Btuh/watt | 105°F Saturated Condensing Temperature (SCT), 95°F Entering Drybulb Temperature |
|---|
| Adiabatic Dry Mode | 45 Btu/watt (halocarbon) | 105°F Saturated Condensing Temperature (SCT), 95°F Entering Drybulb Temperature |
FAN-POWERED CONDENSERS – MINIMUM EFFICIENCY REQUIREMENTS p.254 Download CSV
| CONDENSER TYPE | REFRIGERANT TYPE | MINIMUM EFFICIENCY | RATING CONDITION |
| Outdoor Evaporative- Cooled with THR Capacity > 8,000 MBH | All | 350 Btuh/watt | 100°F Saturated Condensing Temperature (SCT), 70°F Outdoor Wetbulb Temperature |
|---|
| Outdoor Evaporative- Cooled with THR Capacity < 8,000 MBH and Indoor Evaporative-Cooled | All | 160 Btuh/watt | 100°F Saturated Condensing Temperature (SCT), 70°F Outdoor Wetbulb Temperature |
|---|
| Outdoor Air-Cooled | Ammonia | 75 Btuh/watt | 105°F Saturated Condensing Temperature (SCT), 95°F Outdoor Drybulb Temperature |
|---|
| Outdoor Air-Cooled | Halocarbon | 65 Btuh/watt | 105°F Saturated Condensing Temperature (SCT), 95°F Outdoor Drybulb Temperature |
|---|
| Adiabatic Dry Mode | Halocarbon | 45 Btuh/watt | 105°F Saturated Condensing Temperature (SCT), 95°F Outdoor Drybulb Temperature |
|---|
| Indoor Air-Cooled | All | No requirement | No requirement |
FAN-POWERED EVAPORATORS – MINIMUM SPECIFIC EFFICIENCY REQUIREMENTS p.251 Download CSV
| Evaporator Type1, 2 | Rating Condition | Efficiency (Btuh/Watt) | Test Procedure3 |
| Direct Expansion, Ammonia Refrigerant, Cooler/Dock | Dry Coil +25°F saturated evaporating temperature +35°F entering drybulb temperature 0 in. water static pressure | 35 | AHRI 420 |
|---|
| Direct Expansion, Ammonia Refrigerant, Freezer | Dry Coil -20°F saturated evaporating temperature -10°F entering drybulb temperature 0 in. water static pressure | 25 | AHRI 420 |
|---|
| Liquid Overfeed, Ammonia Refrigerant, Cooler/Dock | Dry Coil +25°F saturated evaporating temperature +35°F entering drybulb temperature 0 in. water static pressure | 50 | AHRI 420 |
|---|
| Liquid Overfeed, Ammonia Refrigerant, Freezer | Dry Coil -20°F saturated evaporating temperature -10°F entering drybulb temperature 0 in. water static pressure | 45 | AHRI 420 |
|---|
| Direct Expansion, CO2 Refrigerant, Cooler/Dock | Dry Coil +25°F saturated evaporating temperature +35°F entering drybulb temperature 0 in. water static pressure | 35 | AHRI 420 |
|---|
| Direct Expansion, CO2 Refrigerant, Freezer | Dry Coil -20°F saturated evaporating temperature -10°F entering drybulb temperature 0 in. water static pressure | 25 | AHRI 420 |
|---|
| Liquid Overfeed, CO2 Refrigerant, Cooler/Dock | Dry Coil +25°F saturated evaporating temperature +35°F entering drybulb temperature 0 in. water static pressure | 50 | AHRI 420 |
|---|
| Liquid Overfeed, CO2 Refrigerant, Freezer | Dry Coil -20°F saturated evaporating temperature -10°F entering drybulb temperature 0 in. water static pressure | 45 | AHRI 420 |
|---|
| Direct Expansion, Halocarbon Refrigerant, Cooler/Dock | Dry Coil +25°F saturated evaporating dew point temperature +35°F entering drybulb temperature 0 in. water static pressure | 45 | AHRI 1250 |
|---|
| Direct Expansion, Halocarbon Refrigerant, Freezer | Dry Coil -20°F saturated evaporating dew point temperature -10°F entering drybulb temperature 0 in. water static pressure | 40 | AHRI 1250 |
TRANSCRITICAL CO2 FAN-POWERED GAS COOLERS – MINIMUM EFFICIENCY REQUIREMENTS p.259 Download CSV
| CONDENSER TYPE | REFRIGERANT TYPE | MINIMUM EFFICIENCY | RATING CONDITION |
| Outdoor Air-Cooled | Transcritical CO2 | 160 Btuh/watt | 1400 psig, 100°F Outlet Gas Temperature, 90°F Outdoor Dry bulb Temperature |
|---|
| Adiabatic Dry Mode | Transcritical CO2 | 90 Btuh/watt | 1100 psig, 100°F Outlet Gas Temperature, 90°F Outdoor Dry bulb Temperature |
REFRIGERATED WAREHOUSE INSULATION p.249 Download CSV
| SPACE | SURFACE | MINIMUM R-VALUE (ºF·hr·sf/Btu) |
| Freezers | Roof/Ceiling | R-40 |
|---|
| Freezers | Wall | R-36 |
|---|
| Freezers | Floor | R-35 |
|---|
| Freezers | Floor with all heating from productive refrigeration capacity1 | R-20 |
|---|
| Coolers | Roof/Ceiling | R-28 |
|---|
| Coolers | Wall | R-28 |