SECTION 120.6 – MANDATORY REQUIREMENTS FOR COVERED PROCESSES (part 1 of 2)

Scanned crop of table from PDF page 255
TRANSCRITICAL CO2 FAN-POWERED GAS COOLERS – MINIMUM EFFICIENCY REQUIREMENTS p.256 Download CSV
CONDENSER TYPEREFRIGERANT TYPEMINIMUM EFFICIENCYRATING CONDITION
Outdoor Air-CooledTranscritical CO2160 Btuh/watt1400 psig, 100°F Outlet Gas Temperature, 90°F Outdoor Dry bulb Temperature
Adiabatic Dry ModeTranscritical CO290 Btuh/watt1100 psig, 100°F Outlet Gas Temperature, 90°F Outdoor Dry bulb Temperature
FAN-POWERED CONDENSERS –SPECIFIC EFFICIENCY REQUIREMENTS p.257 Download CSV
CONDENSER TYPEMINIMUM SPECIFIC EFFICIENCYaRATING CONDITION
Evaporative-Cooled160 Btuh/watt100°F Saturated Condensing Temperature (SCT), 70°F Entering Wetbulb Temperature
Air-Cooled65 Btuh/watt105°F Saturated Condensing Temperature (SCT), 95°F Entering Drybulb Temperature
Adiabatic Dry Mode45 Btu/watt (halocarbon)105°F Saturated Condensing Temperature (SCT), 95°F Entering Drybulb Temperature
FAN-POWERED CONDENSERS – MINIMUM EFFICIENCY REQUIREMENTS p.254 Download CSV
CONDENSER TYPEREFRIGERANT TYPEMINIMUM EFFICIENCYRATING CONDITION
Outdoor Evaporative- Cooled with THR Capacity > 8,000 MBHAll350 Btuh/watt100°F Saturated Condensing Temperature (SCT), 70°F Outdoor Wetbulb Temperature
Outdoor Evaporative- Cooled with THR Capacity < 8,000 MBH and Indoor Evaporative-CooledAll160 Btuh/watt100°F Saturated Condensing Temperature (SCT), 70°F Outdoor Wetbulb Temperature
Outdoor Air-CooledAmmonia75 Btuh/watt105°F Saturated Condensing Temperature (SCT), 95°F Outdoor Drybulb Temperature
Outdoor Air-CooledHalocarbon65 Btuh/watt105°F Saturated Condensing Temperature (SCT), 95°F Outdoor Drybulb Temperature
Adiabatic Dry ModeHalocarbon45 Btuh/watt105°F Saturated Condensing Temperature (SCT), 95°F Outdoor Drybulb Temperature
Indoor Air-CooledAllNo requirementNo requirement
FAN-POWERED EVAPORATORS – MINIMUM SPECIFIC EFFICIENCY REQUIREMENTS p.251 Download CSV
Evaporator Type1, 2Rating ConditionEfficiency (Btuh/Watt)Test Procedure3
Direct Expansion, Ammonia Refrigerant, Cooler/DockDry Coil +25°F saturated evaporating temperature +35°F entering drybulb temperature 0 in. water static pressure35AHRI 420
Direct Expansion, Ammonia Refrigerant, FreezerDry Coil -20°F saturated evaporating temperature -10°F entering drybulb temperature 0 in. water static pressure25AHRI 420
Liquid Overfeed, Ammonia Refrigerant, Cooler/DockDry Coil +25°F saturated evaporating temperature +35°F entering drybulb temperature 0 in. water static pressure50AHRI 420
Liquid Overfeed, Ammonia Refrigerant, FreezerDry Coil -20°F saturated evaporating temperature -10°F entering drybulb temperature 0 in. water static pressure45AHRI 420
Direct Expansion, CO2 Refrigerant, Cooler/DockDry Coil +25°F saturated evaporating temperature +35°F entering drybulb temperature 0 in. water static pressure35AHRI 420
Direct Expansion, CO2 Refrigerant, FreezerDry Coil -20°F saturated evaporating temperature -10°F entering drybulb temperature 0 in. water static pressure25AHRI 420
Liquid Overfeed, CO2 Refrigerant, Cooler/DockDry Coil +25°F saturated evaporating temperature +35°F entering drybulb temperature 0 in. water static pressure50AHRI 420
Liquid Overfeed, CO2 Refrigerant, FreezerDry Coil -20°F saturated evaporating temperature -10°F entering drybulb temperature 0 in. water static pressure45AHRI 420
Direct Expansion, Halocarbon Refrigerant, Cooler/DockDry Coil +25°F saturated evaporating dew point temperature +35°F entering drybulb temperature 0 in. water static pressure45AHRI 1250
Direct Expansion, Halocarbon Refrigerant, FreezerDry Coil -20°F saturated evaporating dew point temperature -10°F entering drybulb temperature 0 in. water static pressure40AHRI 1250
TRANSCRITICAL CO2 FAN-POWERED GAS COOLERS – MINIMUM EFFICIENCY REQUIREMENTS p.259 Download CSV
CONDENSER TYPEREFRIGERANT TYPEMINIMUM EFFICIENCYRATING CONDITION
Outdoor Air-CooledTranscritical CO2160 Btuh/watt1400 psig, 100°F Outlet Gas Temperature, 90°F Outdoor Dry bulb Temperature
Adiabatic Dry ModeTranscritical CO290 Btuh/watt1100 psig, 100°F Outlet Gas Temperature, 90°F Outdoor Dry bulb Temperature
REFRIGERATED WAREHOUSE INSULATION p.249 Download CSV
SPACESURFACEMINIMUM R-VALUE (ºF·hr·sf/Btu)
FreezersRoof/CeilingR-40
FreezersWallR-36
FreezersFloorR-35
FreezersFloor with all heating from productive refrigeration capacity1R-20
CoolersRoof/CeilingR-28
CoolersWallR-28