SECTION 120.7 – MANDATORY REQUIREMENTS FOR BUILDING ENVELOPES

p.266(c) Floor and soffit insulation. The opaque portions of floors and soffits that separate conditioned spaces from

p.265SECTION 120.7 – MANDATORY REQUIREMENTS FOR BUILDING ENVELOPES

p.266unconditioned spaces or ambient air shall meet the applicable requirements of Items 1 and 2 below:

p.265Nonresidential and hotel/motel buildings shall comply with the applicable requirements in Sections 120.7(a) through 120.7(e).

p.2661. Raised mass floors. Shall have a minimum of 3 inches of lightweight concrete over a metal deck, or the weighted average U-factor of the floor assembly shall not exceed 0.269.

p.265(a) Roof/Ceiling insulation. The opaque portions of the roof/ceiling that separates conditioned spaces from

p.2662. Other floors. The weighted average U-factor of the floor assembly shall not exceed 0.071.

p.265unconditioned spaces or ambient air shall meet the applicable requirements of Items 1 through 3 below:

p.2663. Heated slab on grade floor. A heated slab on grade floor shall be insulated to meet the requirements of Section 110.8(g).

p.2651. Metal building. The weighted average U-factor of the roof assembly shall not exceed 0.098.

p.2652. Wood framed and others. The weighted average U-factor of the roof assembly shall not exceed 0.075.

p.266(d) Exterior Windows. Vertical fenestration assemblies shall have an area weighted average U-factor no greater than

p.2653. Insulation placement. Insulation installed to limit heat loss and gain from conditioned spaces to unconditioned spaces shall comply with all of the following:

p.2660.47.

p.265A. Insulation shall be installed in direct contact with a roof or ceiling that is sealed to limit infiltration and

p.265exfiltration as specified in Section 110.7. This may include, but is not limited to, placing insulation either above or below the roof deck or on top of the finished ceiling.

p.265B. When insulation is installed at the roof in nonresidential buildings, fixed vents or openings to the

p.265outdoors or to unconditioned spaces shall not be installed. When the space between the ceiling and the roof is either directly or indirectly conditioned space, it shall not be considered an attic for the purposes of complying with CBC attic ventilation requirements.

p.266(e) Vestibules. Public entrances in newly constructed buildings of Group A, B, E, I, and M occupancies shall include an

p.266enclosed vestibule meeting the applicable requirements of Items 1 and 2 below:

p.265C. Insulation placed on top of a suspended ceiling with removable ceiling panels shall not be used to meet

p.2661. All doors opening into and out of the vestibule shall be equipped with self-closing devices. Vestibules shall be designed so that in passing through the vestibule it is not necessary for the interior and exterior doors to open at the same time. The installation of one or more revolving doors in the building entrance shall not eliminate the requirement that a vestibule be provided on any main entrance doors adjacent to revolving doors.

p.265the Roof/Ceiling requirement of Sections 140.3 and 141.0.

p.2662. Where provided, the heating system for heated vestibules and air curtains with integral heating shall be provided with controls configured to shut off the source of heating when the outdoor air temperature is greater than 45°F. Vestibules heating and cooling systems shall be controlled by a thermostat located in the vestibule which is configured to limit heating to a temperature not greater than 60°F and cooling to a temperature not less than 85°F.

p.265(b) Wall insulation. The opaque portions of walls that separate conditioned spaces from unconditioned spaces or

p.266EXCEPTIONS to Section 120.7(e): Vestibules are not required for the following:

p.265ambient air shall meet the applicable requirements of Items 1 through 7 below:

p.2661. Doors not intended to be used by the public, such as doors to mechanical or electrical equipment rooms, or intended solely for employee use.

p.2651. Metal building. The weighted average U-factor of the wall assembly shall not exceed 0.113.

p.2652. Metal framed. The weighted average U-factor of the wall assembly shall not exceed 0.151.

p.2662. Doors opening directly from a sleeping unit or dwelling unit.

p.2653. Light mass walls. A 6-inch or greater hollow core concrete masonry unit shall have a U-factor not to exceed 0.440.

p.2663. Doors that open directly from a space less than 3,000 square feet in area.

p.2664. Revolving doors installed where a public entrance to a newly constructed building is required.

p.2654. Heavy mass walls. An 8-inch or greater hollow core concrete masonry unit shall have a U-factor not to exceed 0.690.

p.2665. Doors used primarily to facilitate vehicular movement or material handling and adjacent personnel doors.

p.2655. Wood framed and others. The weighted average U-factor of the wall assembly shall not exceed 0.110.

p.2666. Doors that have an air curtain with a velocity of not less than 6.56 feet per second at the floor that have been tested in accordance with ANSI/AMCA 220 and installed in accordance with the manufacturer’s instructions. Manual or automatic controls shall be provided that operate the air curtain with the opening and closing of the door.

p.2656. Spandrel panels and curtain wall. The weighted average U-factor of the spandrel panels and curtain wall assembly shall not exceed 0.280.

p.2657. Demising walls. The opaque portions of framed demising walls shall meet the requirements of Item A or B below:

p.2667. Public entrances in buildings that are located in Climate Zones 2 through 13 where the building is less than four stories above grade and less than 10,000 square feet of gross conditioned floor area.

p.265A. Wood framed walls shall be insulated to meet a U-factor not greater than 0.099.

p.2668. Buildings with building plans that have been submitted to the local planning department before the effective date of the 2025 Building Energy Efficiency Standards, where compliance with the vestibule requirements of Section 120.7(e) would require a resubmittal for approval.p.267

p.265B. Metal framed walls shall be insulated to meet a U-factor not greater than 0.151.p.266

p.265SECTION 120.7 – MANDATORY REQUIREMENTS FOR BUILDING ENVELOPES

p.266SECTION 120.7 – MANDATORY REQUIREMENTS FOR BUILDING ENVELOPES

p.267SECTION 120.7 – MANDATORY REQUIREMENTS FOR BUILDING ENVELOPES