p.3734. Alternating Current-Output Uninterruptible Power Supplies (UPS). Alternating current- output UPS systems serving a computer room shall meet or exceed minimum average efficiencies in Table 140.9-B. Minimum average efficiency for alternating current-output UPS shall meet or exceed calculation and testing requirements identified in ENERGY STAR Program Requirements for Uninterruptible Power Supplies (UPSs) – Eligibility Criteria Version 2.0.
p.376iii. The minimum needed to maintain unoccupied pressurization.
p.377a. The sum of the space exhaust airflow rates served by the system, or
p.375(i) 50 percent of the total design exhaust and replacement air system airflow
p.378B. Fume Hood Automatic Sash Closure Acceptance. Before an occupancy permit is
p.372SECTION 140.9 – PRESCRIPTIVE REQUIREMENTS FOR COVERED PROCESSES
p.375rates; or
p.378granted for the fume hoods subject to 140.9(c)4, the equipment and systems shall be certified as meeting the Acceptance Requirement for Code Compliance as specified by the Reference Nonresidential Appendix NA7. A Certificate of Acceptance shall be submitted to the enforcement agency that certifies that the equipment and systems meet the acceptance requirements specified in NA7.17.
p.376C. Applicable equipment and systems shall be certified as meeting the acceptance
p.377b. The minimum acceptable exhaust fan system airflow rate.
p.372(a) Prescriptive Requirements for Computer Rooms. Computer rooms with a power density
p.375(ii) The ventilation rate required as specified by Section 120.1(c)3.
p.376requirements for code compliance, as specified by the reference Nonresidential Appendix NA7.16. A certificate of acceptance shall be submitted to the enforcement agency that certifies that the equipment and systems meet the acceptance requirements specified in Nonresidential Appendix NA7.16.
p.372greater than 20 W/ft2 shall comply with this section.
p.377v. The minimum acceptable exhaust airflow rate, using the procedures and system definitions included in ANSI Z9.5 (2022) Appendix 3, shall be one of the following:
p.3791. In Climate Zone 6 or 7; and
p.375iii. Listed energy recovery devices with a sensible heat recovery effectiveness of not
| Type of Hood | Light Duty Equipment | Medium Duty Equipment | Heavy Duty Equipment | Extra Heavy Duty Equipment |
|---|---|---|---|---|
| Wall-mounted Canopy | 140 | 210 | 280 | 385 |
| Single Island | 280 | 350 | 420 | 490 |
| Double Island | 175 | 210 | 280 | 385 |
| Eyebrow | 175 | 175 | Not Allowed | Not Allowed |
| Backshelf / Passover | 210 | 210 | 280 | Not Allowed |
p.3721. Economizers. Each individual cooling system primarily serving computer rooms shall include either:
p.375less than 40 percent on at least 50 percent of the total exhaust airflow; or
p.377a. Less than 60 percent of the exhaust fan system design airflow rate (simple
p.3792. In a jurisdiction where gas heating is allowed.
p.375iv. A minimum of 75 percent of makeup air volume that is:
p.377turndown control system), or
p.372A. An integrated air economizer capable of providing partial cooling even when
p.372additional mechanical cooling is required and capable of providing 100 percent of the expected system cooling load at 65°F to 80.6°F supply air temperature at outside air temperatures of 65°F dry-bulb and below or 50°F wet-bulb and below, and be equipped with a fault detection and diagnostic system as specified by Section 120.2(i); or
p.375a. Unheated or heated to no more than 60°F; and
p.377b. Dynamically reset based on measured wind speed and/or wind direction
p.373P is the rated output power in watts (W).
| Occupied Minimum Ventilation ACH | ≤ 4 | > 4 and ≤ 6 | > 6 and ≤ 8 | > 8 and ≤ 10 | > 10 and ≤ 12 | > 12 and ≤ 14 |
|---|---|---|---|---|---|---|
| Hood density (linear feet per 10,000 ft3 of laboratory space | ≥ 6 | ≥ 8 | ≥ 10 | ≥ 12 | ≥ 14 | ≥ 16 |
p.377and assumes worst-case emissions rate and shall be less than 60 percent of the exhaust fan system design airflow rate for at least 70 percent of the hours during a typical meteorological year (TY) for the site (wind responsive control system), or
p.375b. Uncooled or cooled without the use of mechanical cooling.
p.373EMOD is an allowance of 0.004 for modular UPSs applicable in the commercial 1,500- 10,000 W range.
p.3762. Exhaust System Transfer Air. Conditioned supply air delivered to any space with mechanical exhaust shall comply with the requirements of Section 140.4(o).
p.373ln is the natural logarithm.
p.3763. Fan System Power Consumption. All newly installed fan exhaust systems serving a laboratory or factory with a design exhaust fan system airflow rate greater than 10,000 cfm shall meet Subsection A and either B, C, or D. Exhaust air in laboratories or factories includes all indoor air and gases removed by the exhaust system, including exhaust air from fume hoods, hazardous exhaust flows, or other manifolded exhaust streams. Exhaust fan system airflow rate is the total of the airflow rates entering the exhaust fans, which includes exhaust air and bypass air but does not include entrained or induced airflow downstream of the exhaust fans.
p.3753. Kitchen exhaust system acceptance. Before an occupancy permit is granted for a commercial kitchen subject to Section 140.9(b), the following equipment and systems shall be certified as meeting the acceptance requirements for code compliance, as specified by the Reference Nonresidential Appendix NA7. A certificate of acceptance shall be submitted to the enforcement agency that certifies that the equipment and systems meet the acceptance requirements specified in NA7.11.
p.372B. An integrated water economizer capable of providing partial cooling even when
p.373The requirement shall be rounded to the third decimal place for certification and reporting.
p.3785. Reheat limitation. Air handlers in buildings with greater than 20,000 cfm of laboratory exhaust that serve multiple space-conditioning zones in laboratory spaces shall not mechanically cool air handler supply air below 80 °F and shall not heat air handler supply air above 50°F, and each zone shall include heating and cooling capacity to prevent cooling at the air handler and reheating at the zones.
p.377c. Dynamically reset based on measured contaminant concentration and
p.372additional mechanical cooling is required and capable of providing 100 percent of the expected system cooling load at 65°F to 80.6°F supply air temperature at outside air temperatures of 50°F dry-bulb and below or 45°F wet-bulb and below.
p.3742. Kitchen ventilation.
p.377shall be less than 60 percent of the exhaust fan system design airflow rate when measured contaminants in the exhaust system plenum are below the threshold contaminant concentration value (monitored control system).
p.374A. Mechanically cooled or heated makeup air delivered to any space with a kitchen
p.374hood shall not exceed the greater of:
p.374i. The supply flow required to meet the space heating and cooling load; or
p.377vi. Exhaust system design and control results in calculated outdoor contaminant concentrations in compliance with applicable federal, state, or local regulations.
p.373Table 140.9-B Alternating Current-Output Uninterruptible Power Supply Minimum Average
p.374ii. The hood exhaust flow minus the available transfer air from adjacent spaces.
p.373Efficiency
p.376A. Systems serving laboratory spaces shall meet all discharge requirements in ANSI
p.374Available transfer air is that portion of outdoor ventilation air serving adjacent spaces not required to satisfy other exhaust needs, such as restrooms, not required to maintain pressurization of adjacent spaces, and that would otherwise be relieved from the building.
p.375(c) Prescriptive requirements for laboratory and factory exhaust systems.
p.377vii. Applicable equipment and systems shall be certified as meeting the acceptance requirements for code compliance, as specified by the reference Nonresidential Appendix NA7.16. A certificate of acceptance shall be submitted to the enforcement agency that certifies that the equipment and systems meet the acceptance requirements specified in Nonresidential Appendix NA7.16.
p.376Z9.5-2022, Section 6.4.
| AC Output | Voltage and Frequency Dependent | Voltage Independent | Voltage and Frequency Independent |
|---|---|---|---|
| P≤350 W | 5.71 x 10-5 x P + 0.962 | 5.71 x 10-5 x P + 0.964 | 0.011 x ln(P) + 0.824 |
| 350 W<P≤1,500 W | 0.982 | 0.984 | 0.011 x ln(P) + 0.824 |
| 1,500 W<P≤10,000 W | 0.981 – EMOD | 0.980 – EMOD | 0.0145 x ln(P) +0.800 – EMOD |
| P>10,000 W | 0.970 | 0.940 | 0.0058 x ln(P) + 0.886 |
p.3751. Airflow reduction requirements. Building laboratory exhaust systems shall be able to reduce zone exhaust and makeup airflow rates to the occupied and unoccupied minimum exhaust airflow rates based on demand and sensed occupancy as follows:
p.376B. The exhaust fan system electrical input power (Fan kWdesign,system) determined per
p.376Section 140.4(c)1B at the fan system design airflow does not exceed Fan kWbudget as calculated per Section 140.4(c)1A.
p.372i. The economizer system is sized to meet the design cooling load of the computer
p.372room when the other spaces within the building are at 50 percent of their design load at outside air temperatures of 65°F dry-bulb and below or 50°F wet-bulb and below; and
p.375A. Occupied minimum exhaust airflow. When occupant sensing controls sense
p.376C. The exhaust fan system power shall not exceed 0.85 watts per cfm of exhaust fan
p.3781. Are located where the outdoor dew point temperature is greater than or equal to 64°F at the ASHRAE 2 percent annual dehumidification design condition, and
p.3774. Fume Hood Automatic Sash Closure. Variable air volume laboratory fume hoods with vertical only sashes located in fume hood intensive laboratories, as described in Table 140.9-D, shall have an automatic sash closure system that complies with the following:
p.375occupants in the space, the minimum exhaust and makeup airflow rates shall be the greater of:
p.376system airflow for systems with air filtration, scrubbers, or other air treatment devices. For all other exhaust fan systems the system power shall not exceed 0.65 watts per cfm of exhaust fan system airflow. Exhaust fan system power equals the sum of the power of all fans in the exhaust system that are required to operate at normal occupied design conditions in order to exhaust air from the conditioned space to the outdoors.
p.374B. A kitchen/dining facility having a total Type I and Type II kitchen hood exhaust
p.374airflow rate greater than 5,000 cfm shall have one of the following:
p.3782. Include heating and cooling capacity at each zone, and
p.372ii. An economizer system that can stop service to other spaces in the building when
p.375i. User-defined airflow not to exceed 1.0 cfm/ft2 (equivalent to 6 air changes per hour for a 10-foot high ceiling), or
p.373(b) Prescriptive requirements for commercial kitchens.
p.374i. At least 50 percent of all replacement air is transfer air that would otherwise be
p.372those spaces are unoccupied and serve only the computer rooms.
p.377A. The automatic sash closure system shall be capable of the following:
p.3783. Do not mechanically cool air handler supply air below 80°F when the outdoor dew point temperature is below 60°F.
p.374exhausted; or
p.3731. Kitchen exhaust systems.
p.3722. Power Consumption of Fans. The total fan power at design conditions of each fan system shall not exceed 27 W/kBtu·h of net sensible cooling capacity.
p.377i. The automatic sash closure system shall have a dedicated zone presence sensor
p.375ii. The regulated minimum occupied circulation rate documented to comply with code, accreditation, or facility environmental health and safety department requirements, or
p.374ii. Demand ventilation system(s) on at least 75 percent of the exhaust air. Such
p.373A. Replacement air introduced directly into the hood cavity of kitchen exhaust hoods
p.377that detects people in the area near the fume hood sash and automatically closes the sash within 5 minutes of no detection.
p.3786. Exhaust air heat recovery. Buildings with greater than 10,000 cfm of laboratory exhaust shall include an exhaust air heat recovery system that meets the following:
p.374systems shall:
p.373shall not exceed 10 percent of the hood exhaust airflow rate.
p.376D. The exhaust fan system shall comply with all of the following:
p.3723. Air Containment. Computer rooms with air-cooled computers in racks and with a ITE design load exceeding 10 kW (2.8 tons) per room shall include air barriers such that there is no significant air path for computer discharge air to recirculate back to computer inlets without passing through a cooling system.
p.374a. Include controls necessary to modulate airflow in response to appliance
p.373B. For kitchen/dining facilities having total Type I and Type II kitchen hood exhaust
p.377ii. The automatic sash closure system shall have controls to prevent the sash from
p.378A. A sensible energy recovery ratio of at least 45 percent at heating design conditions and
p.375iii. The minimum needed to maintain occupied pressurization.
p.376i. The sum of the occupied minimum circulation rates of the spaces served by the fan system shall be less than 60 percent of the exhaust fan system design airflow rate.
p.374operation and to maintain full capture and containment of smoke, effluent and combustion products during cooking and idle; and
p.373airflow rates greater than 5,000 cfm, each Type I hood shall have an exhaust rate that complies with Table 140.9-C. If a single hood or hood section is installed over appliances with different duty ratings, then the maximum allowable flow rate for the hood or hood section shall not exceed the Table 140.9-C values for the highest appliance duty rating under the hood or hood section. Refer to ASHRAE Standard 154-2011 for definitions of hood type, appliance duty and next exhaust flow rate.
p.377automatic closing when a force of no more than 10 lbs is detected.
p.37825 percent at cooling design conditions.
p.375B. Unoccupied minimum exhaust airflow. Within 20 minutes of no occupancy being
p.377iii. The automatic sash closure system shall be equipped with an obstruction sensor
p.378B. Heat is recovered from at least 75 percent of all lab exhaust air volume.
p.375detected by any occupant sensors covering the space, the minimum exhaust and makeup airflow rates shall be the greater of:
p.374b. Include failsafe controls that result in full flow upon cooking sensor failure;
p.377that prevents the sash from automatic closing with obstructions in the sash opening. Obstruction sensor shall be capable of sensing transparent materials such as laboratory glassware.
p.376ii. The design exhaust fan system power shall not exceed 1.3 watts per cfm of exhaust fan system airflow when operating under full-load design conditions.
p.378C. The system includes a run-around coil pump or other means to disable heat recovery.
p.374and
p.375i. User-defined airflow not to exceed 0.67 cfm/ft2 (equivalent to 4 air changes per hours for a 10-foot high ceiling), or
p.378D. The system includes a bypass damper or other means so that the exhaust air pressure
p.374c. Include an adjustable timed override to allow occupants the ability to
p.376iii. The system shall include variable speed controls so that exhaust system fans shall draw no more than 40 percent of the design fan power when the exhaust fan system airflow is 60 percent of the design airflow rate.
p.378drop through the heat exchanger does not exceed 0.4 inch w.g. when heat recovery is disabled.
p.374temporarily override the system to full flow; and
p.377iv. The automatic sash closure system shall be capable of being configured in a
p.375ii. The regulated minimum unoccupied circulation rate documented to comply with code, accreditation, or facility environmental health and safety department requirements, orp.376
p.374d. Be capable of reducing exhaust and replacement air system airflow rates to
p.377manual open mode where once the sash is closed, detection of people in the area near the fume hood by the zone presence sensor does not open the fume hood sash.p.378
p.374the larger of:p.375
p.376iv. The exhaust fan system airflow rate shall not exceed the larger of:p.377
p.372SECTION 140.9 – PRESCRIPTIVE REQUIREMENTS FOR COVERED PROCESSES
p.373SECTION 140.9 – PRESCRIPTIVE REQUIREMENTS FOR COVERED PROCESSES
p.374SECTION 140.9 – PRESCRIPTIVE REQUIREMENTS FOR COVERED PROCESSES
p.375SECTION 140.9 – PRESCRIPTIVE REQUIREMENTS FOR COVERED PROCESSES
p.376SECTION 140.9 – PRESCRIPTIVE REQUIREMENTS FOR COVERED PROCESSES
p.377SECTION 140.9 – PRESCRIPTIVE REQUIREMENTS FOR COVERED PROCESSES
p.378SECTION 140.9 – PRESCRIPTIVE REQUIREMENTS FOR COVERED PROCESSES
p.379SECTION 140.9 – PRESCRIPTIVE REQUIREMENTS FOR COVERED PROCESSES