p.614Section 180.1 – Additions Additions to existing multifamily buildings shall meet the applicable requirements of Sections 110.0 through 110.9; Sections 160.0, 160.1, and 160.2(c) and (d); Sections 160.3 through 160.7; and either Section 180.1(a) or 180.1(b).

p.614(a) Prescriptive approach. The envelope and lighting of the addition; any newly installed space-

p.614conditioning or ventilation system, electrical power distribution system, or water-heating system; any addition to an outdoor lighting system; and any new sign installed in conjunction with an indoor or outdoor addition shall meet the applicable requirements of Sections 110.0 through 110.12; 160.0, 160.1, and 160.2(c) and (d); and 160.3 through 170.2.

p.6141. Envelope.

p.614A. Additions that are greater than 700 square feet shall meet the requirements of

p.614Section 170.2(a), with the following modifications:

p.614i. Framed walls extension. Extensions of existing wood-framed walls may retain the

p.614dimensions of the existing walls and shall install cavity insulation of R-15 in a 2x4 framing and R-21 in a 2x6 framing.

p.614ii. The maximum allowed fenestration area shall be the greater of 175 square feet

p.614or 20 percent of the addition floor area.

p.614iii. When existing siding of a wood-framed wall is not being removed or replaced,

p.614cavity insulation of R-15 in a 2x4 framing and R-21 in a 2x6 framing shall be installed and continuous insulation is not required.