SECTION 110.9 – MANDATORY REQUIREMENTS FOR LIGHTING CONTROLS

p.211B. Provide reduced flicker operation, meaning that directly controlled light sources shall be provided

p.2122. Shall have a conspicuous factory installed label permanently affixed to the inside of the wiring compartment warning against removing, tampering with, rewiring or bypassing the device; and

p.210SECTION 110.9 – MANDATORY REQUIREMENTS FOR LIGHTING CONTROLS

p.211electrical power such that the light output has an amplitude modulation of less than 30 percent for frequencies less than 200 Hz without causing premature lamp failure;

p.210(a) All lighting control devices and systems and all light sources subject to the requirements of Section 110.9 shall

p.2123. Each electrical panel from which track lighting integral current limiters are energized shall have a factory printed label permanently affixed and prominently located, stating the following: “NOTICE: Current limiting devices installed in track lighting integral current limiters connected to this panel shall only be replaced with the same or lower amperage. Adding track or replacement of existing current limiters with higher continuous ampere rating will void the track lighting integral current limiter certification, and will require resubmittal of compliance documentation to the enforcement agency responsible for compliance with the California Title 24, Part 6 Building Energy Efficiency Standards.”

p.210meet the following requirements:

p.211C. Provide an offsetting that produces a zero lumen output; and

p.2101. Shall be installed only if the lighting control or light source complies with all of the applicable requirements of Section 110.9.

p.211D. For wall box dimmers and associated switches designed for use in three way circuits, be capable of

p.211turning lights off, and on to the level set by the dimmer if the lights are off.

p.2102. Lighting controls may be individual devices or systems consisting of two or more components.

p.2114. Occupant sensing controls. Occupant sensing controls include occupant sensors, motion sensors, and vacancy sensors, including those with a partial-ON or partial-OFF function. Occupant sensing controls shall:

p.210(b) All lighting controls. Lighting controls listed in Section 110.9(b) shall comply with the requirements listed below;

p.210and all components of the system considered together as installed shall meet all applicable requirements for the application for which they are installed as required in Sections 130.0 through 130.5, Sections 140.6 through 140.8, Section 141.0, and Section 150.0(k).

p.211A. Be capable of automatically turning the controlled lights in the area either off or down no more than

p.212(d) Track lighting supplementary overcurrent protection panel. A Track Lighting Supplementary Overcurrent

p.21120 minutes after the area has been vacated;

p.212Protection Panel shall be used only for line-voltage track lighting and shall be recognized for compliance with Part 6 only if it meets all of the following requirements:

p.211B. For manual-on controls, have a grace period of no less than 15 seconds and no more than 30 seconds

p.2101. Time-switch lighting controls. All controls that provide time-switch functionality, including all automatic and astronomical time-switch controls, shall have program backup capabilities that prevent the loss of the device’s schedule for at least 7 days, and the device’s date and time for at least 72 hours if power is interrupted. In addition:

p.211to turn on lighting automatically after the sensor has timed out; and

p.2121. Shall be listed as defined in Section 100.1; and

p.211C. Provide a visible status signal that indicates that the device is operating properly, or that it has failed

p.2122. Shall have a permanently installed label that is prominently located stating the following: “NOTICE: This Panel for Track Lighting Energy Code Compliance Only.” The overcurrent protection devices in this panel shall only be replaced with the same or lower amperage. No other overcurrent protective device shall be added to this panel. Adding to, or replacement of, existing overcurrent protective device(s) with higher continuous ampere rating will void the panel listing and require resubmittal of compliance documentation to the enforcement agency responsible for compliance with the California Title 24, Part 6 Building Energy Efficiency Standards.

p.211or malfunctioned. The visible status signal may have an override that turns off the signal.

p.210A. Time-switch controls installed in nonresidential buildings shall:

p.210i. For each connected load, be capable of providing manual override to each connected load and of resuming normally scheduled operation after a manual override is initiated within 2 hours; and

p.210ii. Provide an automatic holiday shutoff feature that turns off all connected loads for at least 24

p.2115. Reserved.

p.210hours and then resumes normally scheduled operation.

p.2116. Sensors used to detect occupants. Sensors that are used by occupant sensing controls to detect occupants shall meet all of the following requirements:

p.210B. Astronomical time-switch controls shall:

ULTRASOUND MAXIMUM DECIBEL VALUES p.212 Download CSV
MID-FREQUENCY OF SOUND PRESSURE THIRD- OCTAVE BAND (IN kHz)MAXIMUM DB LEVEL WITHIN THIRD-OCTAVE BAND (IN dB REFERENCE 20 MICROPASCALS)
Less than 2080
20 or more to less than 25105
25 or more to less than 31.5110
31.5 or more115

p.210i. Have sunrise and sunset prediction accuracy within plus-or-minus 15 minutes and timekeeping accuracy within 5 minutes per year;

p.211A. Sensors shall not incorporate switches or mechanical devices that allow the sensor to be disabled

p.211without changing the settings of the control.

p.210ii. Be capable of displaying date, current time, sunrise time, sunset time, and switching times for each step during programming;

p.211B. Sensors that utilize ultrasonic radiation for detection of occupants shall:

p.211i. comply with 21 C.F.R. part 1002.12;

p.210iii. Be capable of automatically adjusting for daylight savings time; and

p.211ii. not emit audible sound; and

p.210iv. Have the ability to independently offset the on and off for each channel by at least 90 minutes

p.211iii. not emit ultrasound in excess of the decibel levels shown in Table 110.9-A measured no more

p.210before and after sunrise or sunset.

p.211than 5 feet from the source, on axis.

p.210C. Multilevel time-switch controls shall include at least two separately programmable steps per zone.

p.211C. Sensors that utilize microwave radiation for detection of occupants shall:

p.210D. Time-switch controls installed outdoors shall have setback functions that allow the lighting on each

p.210controlled channel to be switched or dimmed to lower levels. The setback functions shall be capable of being programmed by the user for at least one specific time of day.

p.211i. comply with 47 C.F.R. parts 2 and 15; and

p.211ii. not emit radiation in excess of 1 milliwatt per square centimeter measured at no more than 5 centimeters from the emission surface of the device.

p.2102. Daylight responsive controls. Controls that provide daylight responsive controls functionality shall:

p.2117. Indicator lights. Indicator lights integral to lighting controls shall consume no more than 1 watt of power per indicator light.

p.210A. Automatically return to its most recent time delay settings within 60 minutes of the last received

p.210input when left in calibration mode;

p.210B. Have a set point control that easily distinguishes settings to within 10 percent of full-scale adjustment;

p.211(c) Track lighting integral current limiter. An integral current limiter for line-voltage track lighting shall be

p.211recognized for compliance with Part 6 only if it meets all of the following requirements:

p.210C. Provide a linear response within 5 percent accuracy over the range of illuminance measured by the

p.2111. Shall have the identical volt-ampere (VA) rating of the current limiter as installed and rated for compliance with Part 6 clearly marked as follows:

p.210light sensor; and

p.210D. Be capable of being calibrated in a manner that the person initiating the calibration is remote from

p.210the sensor during calibration to avoid influencing calibration accuracy, for example by having a light sensor that is physically separated from where the calibration adjustments are made.

p.211A. So that it is visible for the enforcement agency’s field inspection without opening coverplates, fixtures

p.211or panels; and

p.2103. Dimmers. Controls that provide dimming functionality shall:

p.211B. Permanently marked on the circuit breaker; and

p.211C. On a factory-printed label that is permanently affixed to a nonremovable base-plate inside the wiring

p.210A. Be capable of reducing lighting power consumption by a minimum of 65 percent when at its lowest

p.211compartment.p.212

p.210setting;p.211

p.210SECTION 110.9 – MANDATORY REQUIREMENTS FOR LIGHTING CONTROLS

p.211SECTION 110.9 – MANDATORY REQUIREMENTS FOR LIGHTING CONTROLS

p.212SECTION 110.9 – MANDATORY REQUIREMENTS FOR LIGHTING CONTROLS