SECTION 140.4 – PRESCRIPTIVE REQUIREMENTS FOR SPACE CONDITIONING SYSTEMS (part 1 of 3)

Scanned crop of table from PDF page 318
Scanned crop of table from PDF page 314
Text in this table

F. Office, financial institution, and library building spaces in Climate Zone 16 with cooling capacity less than 65,000 Btu/hr. The space-conditioning system shall be an air conditioner with furnace. G. Office, financial institution, and library building spaces in Climate Zone 16 with cooling capacity 65,000 Btu/hr or greater. The space-conditioning system shall be a dual-fuel heat pump. H. Office spaces in warehouses. The space-conditioning system shall be a heat pump in all climate zones. 3. Multi-zone space-conditioning system types. Space-conditioning systems in office buildings and school buildings not covered by Section 140.4(a)2 shall meet the following requirements: EXCEPTION 1 to Section 140.4(a)3: Buildings greater than 150,000 square feet or greater than five (5) habitable stories. EXCEPTION 2 to Section 140.4(a)3: School buildings in Climate Zones 6 and 7. A. Space-conditioning systems shall comply with one of the following: i. The space-conditioning system shall be a variable refrigerant flow (VRF) heat pump system that incorporates refrigerant-loop heat recovery and a dedicated outdoor air system (DOAS) providing ventilation to all zones served by the space-conditioning system. Indoor fans shall meet the requirements of Section 140.4(a)3D. The DOAS shall comply with Section 140.4(a)3E. ii. The space-conditioning system shall be four-pipe fan coil (FPFC) terminal units with a DOAS providing ventilation to all zones served by the space- conditioning system. The FPFC hot water coils shall be supplied by an air-to- water heat pump (AWHP) space-heating hot water loop that complies with Section 140.4(a)3C. Indoor fans shall meet the requirements of Section 140.4(a)3D. The DOAS shall comply with Section 140.4(a)3E. iii. For office buildings in all climate zones and school buildings in Climate Zones 2, 4 and 8 through 16, the space-conditioning system shall be a variable air volume (VAV)system that utilizes heating supplied through a hot water loop served by an AWHP that complies with Section 140.4(a)3C and the following: a. For office buildings: I. The portion of perimeter zone terminal unit heating capacity utilizing parallel fan-powered boxes complying with Section 140.4(a)3E shall be: 1) One hundred percent in Climate Zones 1 through 6 and 16. 2) Twenty-five percent in Climate Zones 7 through 15.

Supply Fan Power Allowances (watts/ cfm) p.320 Download CSV
AirflowMulti-Zone VAV Systems ≤ 5,000 cfm1Multi-Zone VAV Systems > 5,000 and ≤ 10,000 cfm1Multi-Zone VAV Systems > 10,000 cfm1All Other Fan Systems ≤ 5,000 cfmAll Other Fan Systems > 5,000 and ≤ 10,000 cfmAll Other Fan Systems > 10,000 cfm
Supply System Base Allowance for AHU serving spaces ≤ 6 floors away.0.3950.4530.4130.2320.2560.236
Supply system base allowance for AHU serving spaces > 6 floors away0.5080.5480.5010.3490.3560.325
MERV 13 to MERV 16 Filter upstream of thermal conditioning equipment (two times the clean filter pressure drop)20.1360.1140.1050.1390.1200.107
MERV 13 to MERV 16 Final filter downstream of thermal conditioning equipment. (two times the clean filter pressure drop)20.2250.1880.1760.2310.1970.177
Filtration allowance for > MERV 16 or HEPA Filter (two times the clean filter pressure drop) 20.3350.2800.2650.3420.2920.264
Central Hydronic heating coil allowance0.0460.0480.0520.0460.0500.054
Electric heat allowance0.0460.0380.0350.0460.0400.036
Gas heat allowance0.0690.0570.0700.0580.0600.072
Hydronic/DX cooling coil or heat pump coil (wet) allowance30.1350.1140.1050.1390.1200.107
Solid or liquid Desiccant system allowance0.1570.1320.1230.1630.1390.124
Reheat Coil for Dehumidification Allowance0.0450.0380.0350.0460.0400.036
Allowance for Evaporative humidifier/cooler in series with a cooling coil. Value shown is allowed watts/cfm per 1.0 Inches of water gauge (in.w.g.) Determine pressure loss (in.w.g.) at 400 fpm or maximum velocity allowed by the manufacturer, whichever is less. [Calculation required, see note 4]0.2240.1880.1760.2310.1970.177
AirflowMulti-Zone VAV Systems ≤ 5,000 cfm1Multi-Zone VAV Systems > 5,000 and ≤ 10,000 cfm1Multi-Zone VAV Systems > 10,000 cfm1All Other Fan Systems ≤ 5,000 cfmAll Other Fan Systems > 5,000 and ≤ 10,000 cfmAll Other Fan Systems > 10,000 cfm
Allowance for 100% Outdoor air system5.0.0000.0000.0000.0700.1000.107
Energy recovery allowance for 0.50 ≤ ERR <0.55 60.1350.1140.1050.1390.1200.107
Energy recovery allowance for 0.55 ≤ ERR <0.60 60.1600.1340.1240.1650.1410.126
Energy recovery allowance for 0.60 ≤ ERR <0.65 60.1840.1550.1440.1900.1630.146
Energy recovery allowance for 0.65 ≤ ERR <0.70 60.2080.1750.1630.2150.1840.165
Energy recovery allowance for 0.70 ≤ ERR <0.75 60.2320.1960.1830.2400.2050.184
Energy recovery allowance for 0.75 ≤ ERR <0.80 60.2570.2160.2020.2640.2260.203
Energy recovery allowance for ERR ≥ 0.80 60.2810.2360.2220.2890.2470.222
Coil Runaround Loop0.1350.1140.1050.1390.1200.107
Allowance for Gas phase filtration. Value shown is allowed w/cfm per 1.0 in. wg air pressure drop. [Calculation required, see note 4]0.2240.1880.1760.2310.1970.177
Economizer Return Damper0.0450.0380.0350.0460.0400.036
Air blender allowance0.0450.0380.0350.0460.0400.036
Sound attenuation section [fans serving spaces with design background noise goals below NC35]0.0340.0290.0260.0350.0300.027
Deduction for systems that feed a terminal unit with a fan with electrical input power < 1kW-0.100-0.100-0.100-0.100-0.100-0.100
Low-turndown single-zone VAV fan systems meeting the requirements in note 7.0.0000.0000.0000.0700.1000.089
EXHAUST, RETURN, RELIEF, TRANSFER FAN POWER ALLOWANCES (WATTS/ CFM) p.323 Download CSV
AirflowMulti-Zone VAV Systems1 ≤ 5,000 cfmMulti-Zone VAV Systems1 > 5,000 and ≤ 10,000 cfmMulti-Zone VAV Systems1 > 10,000 cfmAll Other Fan Systems ≤ 5,000 cfmAll Other Fan Systems > 5,000 and ≤ 10,000 cfmAll Other Fan Systems > 10,000 cfm
Exhaust System Base Allowance0.2210.2460.2360.1860.1840.190
Filter (any MERV value)20.0460.0410.0360.0460.0410.035
Energy Recovery Allowance For 0.50 ≤ ERR <0.55 30.1390.1200.1070.1390.1230.109
Energy Recovery Allowance For 0.55 ≤ ERR <0.60 30.1650.1420.1260.1650.1440.128
Energy Recovery Allowance For 0.60 ≤ ERR <0.65 30.1900.1630.1460.1910.1660.148
Energy Recovery Allowance For 0.65 ≤ ERR <0.70 30.2150.1840.1650.2160.1880.167
Energy Recovery Allowance For 0.70 ≤ ERR <0.75 30.2400.2060.1840.2410.2090.186
Energy Recovery Allowance For 0.75 ≤ ERR <0.80 30.2650.2270.2030.2660.2310.205
Energy Recovery Allowance For ERR ≥ 0.80 30.2890.2480.2220.2910.2520.225
Coil Runaround Loop0.1390.1200.1070.1390.1230.109
Return or exhaust systems required by code or accreditation standards to be fully ducted, or systems required to maintain air pressure differentials between adjacent rooms0.1160.1000.0890.1160.1020.091
Return and/or exhaust airflow control devices required for space pressurization control0.1160.1000.0890.1160.1020.091
AirflowMulti-Zone VAV Systems1 ≤ 5,000 cfmMulti-Zone VAV Systems1 > 5,000 and ≤ 10,000 cfmMulti-Zone VAV Systems1 > 10,000 cfmAll Other Fan Systems ≤ 5,000 cfmAll Other Fan Systems > 5,000 and ≤ 10,000 cfmAll Other Fan Systems > 10,000 cfm
Laboratory and vivarium exhaust systems in high- rise buildings for vertical duct exceeding 75 ft. Value shown is allowed w/cfm per 0.25 in. wg for each 100 feet exceeding 75 feet. [Calculation required, see note 4]0.0580.0510.0450.0580.0520.046
Biosafety cabinet. Value shown is allowed w/cfm per 1.0 in. wg air pressure drop. [Calculation required, see note 4]0.2310.1980.1770.2320.2020.179
Exhaust filters, scrubbers, or other exhaust treatment required by code or standard. Value shown is allowed w/cfm per 1.0 in. wg air pressure drop. [Calculation required, see note 4]0.2310.1980.1770.2320.2020.179
Healthcare facility allowance50.2310.1980.1770.2320.2020.179
Sound attenuation section [Fans serving spaces with design background noise goals below NC35.]0.0350.0300.0270.0350.0310.028
Equation on PDF page 319: Qsys = The fan system airflow in cfm

Equation text: Qsys = The fan system airflow in cfm

Needs visual review

p.319