p.3351. Hydronic variable flow systems. HVAC chilled and hot water pumping shall be designed for variable fluid flow and shall be capable of reducing pump flow rates to no more than the larger of:
p.326B. Setpoint reset. For systems with direct digital control of individual zone boxes
p.327iii. The first stage of heating consists of modulating the zone supply air temperature
p.331damper leakage rates shall be certified to the Energy Commission in accordance with Section 110.0.
p.332Systems that include a water economizer to meet Section 140.4(e)1 shall include the following:
p.336i. For systems without direct digital control of individual coils reporting to the
p.326reporting to the central control panel:
p.327setpoint up to a maximum setpoint no higher than 95oF while the airflow is maintained at the dead band flow rate.
p.336central control panel, differential pressure shall be measured at the most remote heat exchanger or the heat exchanger requiring the greatest differential pressure.
| Device Typea | Climate Zones | Required High Limit (Economizer Off When): Equationb | Description |
|---|---|---|---|
| Fixed Dry Bulb | 1, 3, 5, 11-16 | TOA > 75°F | Outdoor air temperature exceeds 75°F |
| Fixed Dry Bulb | 2, 4, 10 | TOA > 73°F | Outdoor air temperature exceeds 73°F |
| Fixed Dry Bulb | 6, 8, 9 | TOA > 71°F | Outdoor air temperature exceeds 71°F |
| Fixed Dry Bulb | 7 | TOA > 69°F | Outdoor air temperature exceeds 69°F |
| Differential Dry Bulb | 1, 3, 5, 11-16 | TOA > TRA°F | Outdoor air temperature exceeds return air temperature |
| Differential Dry Bulb | 2, 4, 10 | TOA > TRA-2°F | Outdoor air temperature exceeds return air temperature minus 2°F |
| Differential Dry Bulb | 6, 8, 9 | TOA > TRA-4°F | Outdoor air temperature exceeds return air temperature minus 4°F |
| Differential Dry Bulb | 7 | TOA > TRA-6°F | Outdoor air temperature exceeds return air temperature minus 6°F |
| Fixed Enthalpyc + Fixed Drybulb | All | hOA > 28 Btu/lbc or TOA > 75°F | Outdoor air enthalpy exceeds 28 Btu/lb of dry airc or Outdoor air temperature exceeds 75°F |
| Climate Zone | Efficiency Improvement a |
|---|---|
| 1 | 70% |
| 2 | 65% |
| 3 | 65% |
| 4 | 65% |
| 5 | 70% |
| 6 | 30% |
| 7 | 30% |
| 8 | 30% |
| 9 | 30% |
| 10 | 30% |
| 11 | 30% |
| 12 | 30% |
| 13 | 30% |
| 14 | 30% |
| 15 | 30% |
| 16 | 70% |
| Altitude (ft) | Correction Factor |
|---|---|
| < 3,000 | 1.000 |
| ≥ 3,000 and < 4,000 | 0.896 |
| ≥ 4,000 and < 5,000 | 0.864 |
| ≥ 5,000 and < 6,000 | 0.832 |
| ≥ 6,000 | 0.801 |
p.326i. Static pressure setpoints shall be reset based on the zone requiring the most pressure.
p.331iv. Adjustable setpoint. If the high-limit control is fixed dry bulb or fixed enthalpy +
p.332A. Maximum pressure drop. Precooling coils and water-to-water heat exchangers used as
p.3344. Multiple cell heat rejection equipment. Multiple cell heat rejection equipment with variable speed fan drives shall:
p.335A. 50 percent or less of the design flow rate; or
p.327iv. The second stage of heating consists of modulating the airflow rate from the
p.331fixed dry bulb, then the control shall have an adjustable setpoint.
p.332part of a water economizer shall either have a waterside pressure drop of less than 15 feet of water, or a secondary loop shall be installed so that the coil or heat exchanger pressure drop is not contributing to pressure drop when the system is in the normal cooling (non-economizer) mode.
p.327dead band flow rate up to the heating maximum flow rate.
p.336ii. For systems with direct digital control of individual coils with a central control
p.326ii. Control sequences of operation for static pressure setpoint reset shall be in accordance with ASHRAE Guideline 36.
p.331v. Sensor accuracy. Outdoor air, return air, mixed air, and supply air sensors shall be
p.334A. Operate the maximum number of fans allowed that comply with the
p.335B. the minimum flow required by the equipment manufacturer for the proper
p.336panel, the static pressure setpoint shall be reset based on the valve requiring the most pressure, and the setpoint shall be no less than 80 percent open. Pressure sensors may be mounted anywhere.
p.327v. Control sequences of operation for reheat zones shall be in accordance with
p.331calibrated within the following accuracies.
p.334manufacturer’s requirements for all system components, and
p.335operation of equipment served by the system.
p.327ASHRAE Guideline 36.
p.3263. Fractional HVAC motors for fans. HVAC motors for fans that are less than 1 hp and 1/12 hp or greater shall be electronically-commutated motors or shall have a minimum motor efficiency of 70 percent when rated in accordance with NEMA Standard MG 1-2006 at full load rating conditions. These motors shall also have the means to adjust motor speed for either balancing or remote control. Belt-driven fans may use sheave adjustments for airflow balancing in lieu of a varying motor speed.
p.3311. Drybulb and wetbulb temperatures accurate to ±2°F over the range of 40°F to 80°F;
p.334B. Control all operating fans to the same speed. Minimum fan speed shall comply
p.332B. Economizer systems shall be integrated with the mechanical cooling system so that
p.327B. For each zone without DDC, the volume of primary air that is reheated, re-cooled, or
p.334with the minimum allowable speed of the fan drive as specified by the manufacturer’s recommendation. Staging of fans is allowed once the fans are at their minimum operating speed.
p.332they are capable of providing partial cooling even when additional mechanical cooling is required to meet the remainder of the cooling load. Controls shall not false load the mechanical cooling system by limiting or disabling the economizer or by any other means, such as hot gas bypass, except at the lowest stage of mechanical cooling.
p.327mixed air supply shall not exceed the larger of the following:
p.3312. Enthalpy accurate to ±3 Btu/lb over the range of 20 Btu/lb to 36 Btu/lb;
p.328A. The DOAS unit shall meet the exhaust air heat recovery ratio as specified in Section
| Motor Nameplate HP | Default Fan kWdesign with variable speed drive (Fan kWdesign) | Default Fan kWdesign without variable speed drive(Fan kWdesign) |
|---|---|---|
| < 1 | 0.96 | 0.89 |
| ≥ 1 and < 1.5 | 1.38 | 1.29 |
| ≥ 1.5 and < 2 | 1.84 | 1.72 |
| ≥ 2 and < 3 | 2.73 | 2.57 |
| ≥ 3 and < 5 | 4.38 | 4.17 |
| ≥ 5 and < 7.5 | 6.43 | 6.15 |
| ≥ 7.5 and < 10 | 8.46 | 8.13 |
| ≥ 10 and < 15 | 12.47 | 12.03 |
| ≥ 15 and < 20 | 16.55 | 16.04 |
| ≥ 20 and < 25 | 20.58 | 19.92 |
| ≥ 25 and < 30 | 24.59 | 23.77 |
| ≥ 30 and < 40 | 32.74 | 31.70 |
| ≥ 40 and < 50 | 40.71 | 39.46 |
| ≥ 50 and < 60 | 48.50 | 47.10 |
| ≥ 60 and < 75 | 60.45 | 58.87 |
| ≥ 75 and ≤ 100 | 80.40 | 78.17 |
p.327i. 30 percent of the peak primary airflow; or
p.3313. Relative humidity (RH) accurate to ±5 percent over the range of 20 percent to 80 percent RH;
p.328140.4(q)1 and include bypass or control to disable energy recovery as specified in Section 140.4(q)2.
p.3345. Cooling tower efficiency. Axial fan, open-circuit cooling towers serving condenser water loops for chilled water plants with a total of 900 gpm or greater, shall have a minimum rated efficiency based on Table 140.4-H-2 when rated in accordance with the conditions as listed in Table 110.2-F.
p.327ii. The design zone outdoor airflow rate as specified by Section 120.1(c)3.
p.3352. Chiller isolation. When a chilled water system includes more than one chiller, provisions shall be made so that flow through any chiller is automatically shut off when that chiller is shut off while still maintaining flow through other operating chiller(s). Chillers that are piped in series for the purpose of increased temperature differential shall be considered as one chiller.
p.3367. Hydronic heat pump (WLHP) controls. Hydronic heat pumps connected to a common heat pump water loop with central devices for heat rejection and heat addition shall have controls that are capable of providing a heat pump water supply temperature dead band of at least 20°F between initiation of heat rejection and heat addition by the central devices.
p.332(f) Supply air temperature reset controls. Space-conditioning systems supplying heated or
p.331vi. Sensor calibration data. Data used for control of the economizer shall be plotted on
p.328B. The DOAS unit shall provide at least the minimum ventilation air flow rate as
p.332cooled air to multiple zones shall include controls that automatically reset supply air temperatures. Air distribution systems serving zones that are likely to have constant loads shall be designed for the air flows resulting from the fully reset supply air temperature. Supply air temperature reset controls shall be:
p.331a sensor performance curve.
p.328specified in Section 120.1(c)3 and provide no less than 0.3 cfm/ft2 during economizer conditions.
p.331vii. Sensor high limit control. Sensors used for the high limit control shall be located to
p.333(h) Heat rejection systems. Heat rejection equipment used in comfort cooling systems, such as
p.331prevent false readings, including but not limited to being properly shielded from direct sunlight.
p.333air-cooled condensers, open cooling towers, closed-circuit cooling towers and evaporative condensers shall include the following:
p.334TOWERS (GPM/hp)
p.3353. Boiler isolation. When a hot water plant includes more than one boiler, provisions shall be made so that flow through any boiler is automatically shut off when that boiler is shut off while still maintaining flow through other operating boiler(s).
| CZ 1 | CZ 2 | CZ 3 | CZ 4 | CZ 5 | CZ 6 | CZ 7 | CZ 8 | CZ 9 | CZ 10 | CZ 11 | CZ 12 | CZ 13 | CZ 14 | CZ 15 | CZ 16 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 42.1 | 70 | 60 | 70 | 70 | 80 | 80 | 80 | 80 | 80 | 60 | 70 | 80 | 60 | 80 | 42.1 |
p.3321. In response to representative building loads or to outdoor air temperature; and
p.331viii. Relief air system. Relief air systems shall be capable of providing 100 percent
p.3331. Fan speed control. Each fan powered by a motor of 7.5 hp (5.6 kW) or larger shall have the capability to operate that fan at two thirds of full speed or less and shall have controls that automatically change the fan speed to control the leaving fluid temperature or condensing temperature or pressure of the heat rejection device.
p.326(d) Space-conditioning zone controls. Each space-conditioning zone shall have controls
p.3322. At least 25 percent of the difference between the design supply-air temperature and the design room air temperature.
p.331outside air without over-pressurizing the building.
p.326designed in accordance with 1 or 2:
p.329a If a unit is rated with an annualized or part-load metric, then to eliminate the required economizer, only the applicable minimum cooling efficiency of the unit must be increased by the percentage shown. If the unit is only rated with a full load metric, like EER or COP cooling, then that metric must be increased by the percentage shown. To determine the efficiency required to eliminate the economizer, when the unit equipment efficiency is rated with an energy-input divided by work-output metric, the metric shall first be converted to COP prior to multiplying by the efficiency improvement percentage and then converted back to the rated metric.
p.3354. Chilled and hot water temperature reset controls. Systems with a design capacity exceeding 500,000 Btu/hr supplying chilled or heated water shall include controls that automatically reset supply water temperatures as a function of representative building loads or outside air temperature.
p.3368. High capacity space heating gas boiler systems. In Climate Zones 1 through 6, 9 through 14, and 16, gas hot water boiler systems for space heating with a total system input of at least 1 MMBtu/h but no more than 10 MMBtu/h shall meet all of the following requirements.
p.331F. The space-conditioning system shall include the following:
p.3261. Each space-conditioning zone shall have controls that prevent:
p.3323. Configured with control sequences of operation in accordance with ASHRAE Guideline 36.
p.331i. Unit controls shall have mechanical capacity controls interlocked with economizer
p.334(i) Minimum chiller efficiency. Chillers shall meet or exceed Path B from Table 110.2-D.
p.330a Only the high limit control devices listed are allowed to be used and at the setpoints listed. Others such as Dew Point, Fixed Enthalpy, Electronic Enthalpy, and Differential Enthalpy Controls, may not be used in any Climate Zone for compliance with Section 140.4(e)1 unless approval for use is provided by the Energy Commission Executive Director.
p.331controls such that the economizer is at 100 percent open position when mechanical cooling is on and does not begin to close until the leaving air temperature is less than 45°F.
p.328Total Building Chilled Water System Capacity, Minus Capacity of the Cooling units with Air
p.327(e) Economizers.
p.328Economizers
p.336A. Boiler system efficiency. Gas hot water boilers shall have a minimum thermal
p.326C. Simultaneous provisions of heating and cooling to the same zone, such as mixing or simultaneous supply of air that has been previously mechanically heated and air that has been previously cooled, either by cooling equipment or by economizer systems; or
p.336efficiency of 90 percent. Systems with multiple boilers can meet this requirement if the space-heating input provided by equipment with thermal efficiencies above and below 90 percent has an input capacity-weighted average thermal efficiency of at least 90 percent. For boilers federally regulated by combustion efficiency, the calculation for the input capacity-weighted average thermal efficiency shall use the combustion efficiency value.
p.3271. Each cooling air handler that has a design total mechanical cooling capacity over 33,000 Btu/hr or chilled-water cooling systems without a fan or that use induced airflow that has a cooling capacity greater than the systems listed in Table 140.4-C, shall include either:
| Climate Zones | Building Water-Cooled Chilled Water System | Air-Cooled Chilled Water Systems or District Chilled Water Systems |
|---|---|---|
| 15 | ≥ 960,000 Btu/h (280 kW) | ≥ 1,250,000 Btu/h (365 kW) |
| 1-14 | ≥720,000 Btu/h (210 kW) | ≥940,000 Btu/h (275 kW) |
| 16 | ≥1,320,000 Btu/h (385 kW) | ≥1,720,000 Bu/h (505 kW) |
p.331ii. Direct Expansion (DX) units greater than 65,000 Btu/hr that control the capacity of
p.330b Devices with selectable (rather than adjustable) setpoints shall be capable of being set to within 2°F and 2 Btu/lb of the setpoint listed.
p.3292. If an economizer is required by Section 140.4(e)1, and an air economizer is used to meet the requirement, then it shall be:
p.331the mechanical cooling directly based on occupied space temperature shall have a minimum of two stages of mechanical cooling capacity.
p.325Footnotes to TABLE 140.4-D:
p.3355. Water-cooled air conditioner and hydronic heat pump systems. Water circulation systems serving water-cooled air conditioners, hydronic heat pumps, or both that have total pump system power exceeding 5 hp shall have flow controls that meet the requirements of Section 140.4(k)6. Each such air conditioner or heat pump shall have a two-position automatic valve interlocked to shut off water flow when the compressor is off.
p.330c At altitudes substantially different than sea level, the Fixed Enthalpy limit value shall be set to the enthalpy value at 75°F and 50% relative humidity. As an example, at approximately 6,000 foot elevation, the fixed enthalpy limit is approximately 30.7 Btu/lb.
p.3251. This table cannot be used for Motor Nameplate Horsepower values greater than 100. 2. This table is to be used only with motors with a service factor ≤ 1.15. If the service factor is not provided, this table may not be used.
p.329A. Designed and equipped with controls so that economizer operation does not
p.3262. Zones served by variable air-volume systems that are designed and controlled to reduce, to a minimum, the volume of reheated, recooled, or mixed air are allowed only if the controls meet all of the following requirements:
p.331iii. DX units not within the scope of Section 140.4(e)2Fii shall comply with the
p.327A. An air economizer capable of modulating outside-air and return-air dampers to
p.3332. Tower flow turndown. Open cooling towers configured with multiple condenser water pumps shall be designed so that all cells can be run in parallel with the larger of:
p.329increase the building heating energy use during normal operation; and
p.331requirements in Table 140.4-H and have controls that do not false load the mechanical cooling system by limiting or disabling the economizer or by any other means except at the lowest stage of mechanical cooling capacity.
p.327supply 100 percent of the design supply air quantity as outside air; or
p.330E. The air economizer and all air dampers shall have the following features:
p.334(j) Limitation of air-cooled chillers. Chilled water plants shall not have more than 300 tons
p.336B. Hot water distribution design. The hot water distribution system shall be designed to comply with Items i and ii.
p.327B. A water economizer capable of providing 100 percent of the expected system cooling
p.333A. The flow that is produced by the smallest pump, or
p.330i. Warranty. 5-year manufacturer warranty of economizer assembly.
p.334provided by air-cooled chillers.
p.3252. Variable air volume (VAV) systems.
p.326A. For each zone with direct digital controls (DDC):
p.332(g) Electric resistance heating. Electric resistance heating systems shall not be used for space
p.327load at outside air temperatures of 50°F dry-bulb and 45°F wet-bulb and below.
p.330ii. Damper reliability testing. Suppliers of economizers shall certify that the economizer
p.333B. 50 percent of the design flow for the cell.
p.332heating.
p.3356. Variable flow controls.
p.325A. Static pressure sensor location. Static pressure sensors used to control variable air
p.336i. Coils and other heat exchangers shall be selected so that at design conditions the
p.326i. The volume of primary air that is reheated, recooled, or mixed air supply shall not
p.331TABLE 140.4-H – DIRECT EXPANSION (DX) UNIT REQUIREMENTS FOR COOLING STAGES AND
p.330assembly, including but not limited to outdoor air damper, return air damper, drive linkage and actuator, have been tested and are able to open and close against the rated airflow and pressure of the system for 60,000 damper opening and closing cycles.
p.329B. Capable of providing partial cooling even when additional mechanical cooling is
p.325volume fans shall be placed in a position such that the controller setpoint is no greater than one-third the total design fan static pressure, except for systems with zone reset control complying with Section 140.4(c)2B. If this results in the sensor being located downstream of any major duct split, multiple sensors shall be installed in each major branch with fan capacity controlled to satisfy the sensor furthest below its setpoint; andp.326
p.336hot water return temperature entering the boilers is 120°F or less.
p.326exceed the larger of:
p.331COMPRESSOR DISPLACEMENT
p.3333. Limitation on centrifugal fan cooling towers. Open cooling towers with a combined rated capacity of 900 gpm and greater at 95°F condenser water return, 85°F condenser water supply and 75°F outdoor wet-bulb temperature shall use propeller fans and shall not use centrifugal fans.
p.335A. Variable speed drives. Individual pumps serving variable flow systems and having a
p.329required to meet the remainder of the cooling load.
p.335motor horsepower exceeding 5 hp shall have controls or devices (such as variable speed control) that will result in pump motor demand of no more than 30 percent of design wattage at 50 percent of design water flow. The pumps shall be controlled as a function of required differential pressure.
p.326a. 50 percent of the peak primary airflow; or
p.336ii. Under all operating conditions, the water temperature entering the boiler is 120°F
| COOLING CAPACITY | MINIMUM NUMBER OF MECHANICAL COOLING STAGES | MINIMUM COMPRESSOR DISPLACEMENT |
|---|---|---|
| ≥ 65,000 Btu/h and < 240,000 Btu/h | 3 stages | ≤ 35% full load |
| ≥ 240,000 Btu/h | 4 stages | ≤ 25% full load |
p.329C. Designed and equipped with a device type and high limit shut off complying with
p.336or less or the flow rate of supply hot water that recirculates directly into the return system, such as by three-way valves or minimum flow bypass controls, shall be no greater than 20 percent of the design flow of the operating boilers.
p.326b. The design zone outdoor airflow rate as specified by Section 120.1(c)3.
p.330iii. Damper leakage. Economizer outdoor air and return air dampers shall have a
p.326ii. The volume of primary air in the deadband shall not exceed the design zone
p.329D. If controlled by a DDC system, configured with control sequences of operation in
p.330maximum leakage rate of 10 cfm/sf at 250 Pascals (1.0 in. of water) when tested in accordance with AMCA Standard 500-D. The economizer outside air and return airp.331
p.334(k) Hydronic system measures.p.335
p.326outdoor airflow rate as specified by Section 120.1(c)3.p.327
p.329accordance with ASHRAE Guideline 36.p.330
p.335B. Pressure sensor location and setpoint.p.336
p.325SECTION 140.4 – PRESCRIPTIVE REQUIREMENTS FOR SPACE CONDITIONING SYSTEMS
p.326SECTION 140.4 – PRESCRIPTIVE REQUIREMENTS FOR SPACE CONDITIONING SYSTEMS
p.327SECTION 140.4 – PRESCRIPTIVE REQUIREMENTS FOR SPACE CONDITIONING SYSTEMS
p.328SECTION 140.4 – PRESCRIPTIVE REQUIREMENTS FOR SPACE CONDITIONING SYSTEMS
p.329SECTION 140.4 – PRESCRIPTIVE REQUIREMENTS FOR SPACE CONDITIONING SYSTEMS
p.330SECTION 140.4 – PRESCRIPTIVE REQUIREMENTS FOR SPACE CONDITIONING SYSTEMS
p.331SECTION 140.4 – PRESCRIPTIVE REQUIREMENTS FOR SPACE CONDITIONING SYSTEMS
p.332SECTION 140.4 – PRESCRIPTIVE REQUIREMENTS FOR SPACE CONDITIONING SYSTEMS
p.333SECTION 140.4 – PRESCRIPTIVE REQUIREMENTS FOR SPACE CONDITIONING SYSTEMS
p.334SECTION 140.4 – PRESCRIPTIVE REQUIREMENTS FOR SPACE CONDITIONING SYSTEMS
p.335SECTION 140.4 – PRESCRIPTIVE REQUIREMENTS FOR SPACE CONDITIONING SYSTEMS
p.336SECTION 140.4 – PRESCRIPTIVE REQUIREMENTS FOR SPACE CONDITIONING SYSTEMS