p.181TABLE 110.2-G Electrically Operated Variable Refrigerant Flow Air-to-Air and Applied Heat Pumps - Minimum Efficiency
p.182CONTINUED: TABLE 110.2-G Electrically Operated Variable Refrigerant Flow Air-to-Air and Applied Heat Pumps - Minimum
p.183CONTINUED: TABLE 110.2-G Electrically Operated Variable Refrigerant Flow Air-to-Air and Applied Heat Pumps - Minimum Efficiency Requirements
p.180Minimum Efficiency Requirements
p.181Requirements
p.182Efficiency Requirements
p.187e. For heat recovery heating chilling package applications where there is simultaneous cooling and heating, compliance with the heating performance heat
p.188(CONTINUED) TABLE 110.2-J Heat Pump and Heat Recovery Chiller Packages, Heat Pump, Heating Operation– Minimum Efficiency Requirements
p.189(CONTINUED) TABLE 110.2-J Heat Pump and Heat Recovery Chiller Packages, Heat Pump, Heating Operation– Minimum Efficiency Requirements
p.190i. Source leaving liquid temperature.
p.191(CONTINUED) TABLE 110.2-K Heat Pump and Heat Recovery Chiller Packages, Simultaneous Cooling and Heating, Heating Operation– Minimum Efficiency
p.186TABLE 110.2-I Heat Pump and Heat Recovery Chiller Packages, Cooling Operation - Minimum Efficiency Requirements
| Equipment Type | Energy Recovery | Subcategory or Rating Condition | Minimum Efficiency | Test Procedurea |
|---|---|---|---|---|
| Water cooled (dehumidification mode) | With energy recovery | Cooling tower condenser water | 5.1 ISMRE2 | AHRI 920 |
| Water source heat pump (dehumidification mode) | With energy recovery | Ground source, closed and open loop | 5.0 ISMRE2 | AHRI 920 |
| Water source heat pump (dehumidification mode) | With energy recovery | Water source | 4.6 ISMRE2 | AHRI 920 |
| Air source heat pumps (heating mode) | With energy recovery | 3.2 ISCOP2 | AHRI 920 | |
| Water source heat pump (heating mode) | With energy recovery | Ground source, closed and open loop | 3.5 ISCOP2 | AHRI 920 |
| Water source heat pump (heating mode) | With energy recovery | Water source | 4.04 ISCOP2 | AHRI 920 |
p.187recover COPHR is only required at one of the four heating AHRI 550/590 (I-P) standard ratings conditions of Low, Medium, Hot-Water 1 or Hot-Water 2. Compliance with the cooling only performance is required as defined in footnotes b and c. f. Water to water heat pumps with a capacity less than 135,000 Btu/h are included in Table 110.2-B Heat Pumps, Minimum Efficiency Requirements.
p.191Requirements
| Equipment Type | Size Category | Heating Section Type | Sub-Category or Rating Condition | Minimum Efficiency | Test Procedure b |
|---|---|---|---|---|---|
| VRF Groundwater source (cooling mode) | <135,000 Btu/h | All | VRF Multi-split System a 59ºF entering water | 16.2 EER | AHRI 1230 |
| VRF Groundwater source (cooling mode) | ≥135,000 Btu/h | All | VRF Multi-split System a 59ºF entering water | 13.8 EER | AHRI 1230 |
| VRF Ground source (cooling mode) | <135,000 Btu/h | All | VRF Multi-split System a 77ºF entering water | 13.4 EER | AHRI 1230 |
| VRF Ground source (cooling mode) | ≥135,000 Btu/h | All | VRF Multi-split System a 77ºF entering water | 11.0 EER | AHRI 1230 |
| VRF Air Cooled (heating mode) | <65,000 Btu/h (cooling capacity) | --- | VRF Multi-split System | 7.7 HSPF Before 1/1/2025 7.5 HSPF2 On or after 1/1/2025 | AHRI 1230 Before 1/1/2025 AHRI 210/240 On or After 1/1/2025 |
| VRF Air Cooled (heating mode) | ≥65,000 Btu/h and <135,000 Btu/h (cooling capacity) | --- | VRF Multi-split system 47ºF db/ 43ºF wb outdoor air | Federal Minimum COP | AHRI 1230 |
| VRF Air Cooled (heating mode) | ≥65,000 Btu/h and <135,000 Btu/h (cooling capacity) | --- | VRF Multi-split system 17ºF db/15ºF wb outdoor air | 2.25 COP | AHRI 1230 |
| VRF Air Cooled (heating mode) | ≥135,000 Btu/h (cooling capacity) | --- | VRF Multi-split system 47ºF db/ 43ºF wb outdoor air | Federal Minimum COP | AHRI 1230 |
| Equipment Type | Size Category | Heating Section Type | Sub-Category or Rating Condition | Minimum Efficiency | Test Procedure b |
| VRF Air Cooled (heating mode) | ≥135,000 Btu/h (cooling capacity) | --- | VRF Multi-split system 17ºF db/15ºF wb outdoor air | 2.05 COP | AHRI 1230 |
| VRF Water source (heating mode) | < 65,000 Btu/h (cooling capacity) | --- | VRF Multi-split System 68oF entering water | Federal Minimum COP | AHRI 1230 |
| VRF Water source (heating mode) | ≥65,000 Btu/h and <135,000 Btu/h (cooling capacity) | --- | VRF Multi-split System 68ºF entering water | Federal Minimum COP | AHRI 1230 |
| VRF Water source (heating mode) | ≥135,000 Btu/h and < 240,000 Btu/h (cooling capacity) | --- | VRF Multi-split System 68ºF entering water | Federal Minimum COP | AHRI 1230 |
| VRF Water source (heating mode) | ≥ 240,000 Btu/h (cooling capacity) | --- | VRF Multi-split System 68oF entering water | Federal Minimum COP | AHRI 1230 |
| VRF Groundwater source (heating mode) | <135,000 Btu/h (cooling capacity) | --- | VRF Multi-split System 50ºF entering water | 3.6 COP | AHRI 1230 |
| VRF Groundwater source (heating mode) | ≥135,000 Btu/h (cooling capacity) | --- | VRF Multi-split System 50ºF entering water | 3.3 COP | AHRI 1230 |
| VRF Ground source (heating mode) | <135,000 Btu/h (cooling capacity) | --- | VRF Multi-split System 32ºF entering water | 3.1 COP | AHRI 1230 |
| VRF Ground source (heating mode) | ≥135,000 Btu/h (cooling capacity) | --- | VRF Multi-split System 32ºF entering water | 2.8 COP | AHRI 1230 |
| Equipment Type | Size Category | Heating Section Type | Sub-Category or Rating Condition | Minimum Efficiency | Test Procedurea |
|---|---|---|---|---|---|
| VRF Air Conditioners, Air Cooled | <65,000 Btu/h | All | VRF Multi-split System | 13.0 SEER Before 1/1/2023 Federal Minimum SEER2 On or After 1/1/2023 | AHRI 1230 Before 1/1/2023 AHRI 210/240 On or After 1/1/2023 |
| VRF Air Conditioners, Air Cooled | ≥65,000 Btu/h and <135,000 Btu/h | Electric Resistance (or none) | VRF Multi-split System | 10.5 EER Federal Minimum IEER b | AHRI 1230 |
| VRF Air Conditioners, Air Cooled | ≥135,000 Btu/h and <240,000 Btu/h | Electric Resistance (or none) | VRF Multi-split System | 10.3 EER Federal Minimum IEER b | AHRI 1230 |
| VRF Air Conditioners, Air Cooled | ≥240,000 Btu/h | Electric Resistance (or none) | VRF Multi-split System | 9.5 EER Federal Minimum IEER b | AHRI 1230 |
| Equipment Type | Size Category | Heating Section Type | Sub-Category or Rating Condition | Minimum Efficiency | Test Procedure b |
|---|---|---|---|---|---|
| VRF Air Cooled, (cooling mode) | <65,000 Btu/h | All | VRF Multi-split System | 13.0 SEER Before 1/1/2023 Federal Minimum =SEER2 On or after 1/1/2023 | AHRI 1230 Before 1/1/2023 AHRI 210/240 On or After 1/1/2023 |
| VRF Air Cooled, (cooling mode) | ≥65,000 Btu/h and <135,000 Btu/h | Electric Resistance (or none) | VRF Multi-split System a | 10.3 EER Federal Minimum IEER c | AHRI 1230 |
| VRF Air Cooled, (cooling mode) | ≥135,000 Btu/h and <240,000 Btu/h | Electric Resistance (or none) | VRF Multi-split System a | 9.9 EER Federal Minimum IEER c | AHRI 1230 |
| VRF Air Cooled, (cooling mode) | ≥240,000 Btu/h | Electric Resistance (or none) | VRF Multi-split System a | 9.1 EER Federal Minimum IEER c | AHRI 1230 |
| VRF Water source (cooling mode) | <65,000 Btu/h | All | VRF Multi-split systems a 86ºF entering water | 12.0 EER Federal Minimum IEER c | AHRI 1230 |
| VRF Water source (cooling mode) | ≥65,000 Btu/h and <135,000 Btu/h | All | VRF Multi-split System a 86ºF entering water | 12.0 EER Federal Minimum IEER c | AHRI 1230 |
| VRF Water source (cooling mode) | ≥135,000 Btu/h and < 240,000 | All | VRF Multi-split System a 86ºF entering water | 10.0 EER Federal Minimum IEER c | AHRI 1230 |
| VRF Water source (cooling mode) | ≥ 240,000 Btu/h | All | VRF Multi-split Systema 86oF entering water | 10.0 EER Federal Minimum IEER | AHRI 1230 |
| Equipment Type | Energy Recovery | Subcategory or Rating Condition | Minimum Efficiency | Test Procedurea |
|---|---|---|---|---|
| Air cooled (dehumidification mode) | Without energy recovery | NA | 3.8 ISMRE2 | AHRI 920 |
| Air source heat pumps (dehumidification mode) | Without energy recovery | NA | 3.8 ISMRE2 | AHRI 920 |
| Water cooled (dehumidification mode) | Without energy recovery | Cooling Tower Condenser Water | 4.7 ISMRE2 | AHRI 920 |
| Water source heat pump (dehumidification mode) | Without energy recovery | Ground source, closed and open loop | 4.6 ISMRE2 | AHRI 920 |
| Water source heat pump (dehumidification mode) | Without energy recovery | Water source | 3.8 ISMRE2 | AHRI 920 |
| Air source heat pumps (heating mode) | Without energy recovery | NA | 2.05 ISCOP2 | AHRI 920 |
| Water source heat pump (heating mode) | Without energy recovery | Ground source, closed and open loop | 2.13 ISCOP2 | AHRI 920 |
| Water source heat pump (heating mode) | Without energy recovery | Water source | 2.13 ISCOP2 | AHRI 920 |
| Air cooled (dehumidification mode) | With energy recovery | NA | 5.0 ISMRE2 | AHRI 920 |
| Air source heat pumps (dehumidification mode) | With energy recovery | NA | 5.0 ISMRE2 | AHRI 920 |
p.1901. The cooling evaporator liquid flow rate used for the heating rating for a reverse cycle air to water heat pump shall be the flow rate determined during the full load cooling rating.
| Equipment Type | Size Category Refrigerating Capacitya, tonR | Cooling Operation Efficiencyb,c,d,e , Air Source EER (FL/IPLV), Btu/W h, Liquid Source Power Input per Capacity (FL/IPLV), kW/tonR Path A | Cooling Operation Efficiencyb,c,d,e, Air Source EER (FL/IPLV), Btu/W h, Liquid Source Power Input per Capacity (FL/IPLV), kW/tonR Path B | Test Procedure |
|---|---|---|---|---|
| Air Source | < 150 | > 5.595 FL > 13.02 IPLV.IP | > 9.215 FL > 15.01 IPLV.IP | AHRI/550/590 |
| Air Source | > 150 | > 5.595 FL > 13.30 IPLV.IP | > 9.215 FL > 15.30 IPLV.IP | AHRI/550/590 |
| Liquid source electrically operated positive displacement | > 11.25f and < 150 | < 0.7895 FL < 0.6316 IPLV.IP | < 0.8211 FL < 0.5263 IPLV.IP | AHRI/550/590 |
| Liquid source electrically operated positive displacement | > 150 and < 300 | < 0.7579 FL < 0.5895 IPLV.IP | < 0.7895 FL < 0.5158 IPLV.IP | AHRI/550/590 |
| Liquid source electrically operated positive displacement | > 300 and < 400 | < 0.6947 FL < 0.5684 IPLV.IP | < 0.7158 FL < 0.4632 IPLV.IP | AHRI/550/590 |
| Liquid source electrically operated positive displacement | > 400 and < 600 | < 0.6421 FL < 0.5474 IPLV.IP | < 0.6579 FL < 0.4316 IPLV.IP | AHRI/550/590 |
| Liquid source electrically operated positive displacement | > 600 | < 0.5895 FL < 0.5263 IPLV.IP | < 0.6158 FL < 0.4000 IPLV.IP | AHRI/550/590 |
| Liquid source electrically operated centrifugal | > 11.25f and < 150 | < 0.6421 FL < 0.5789 IPLV.IP | < 0.7316 FL < 0.4632 IPLV.IP | AHRI/550/590 |
| Liquid source electrically operated centrifugal | > 150 and < 300 | < 0.6190 FL < 0.5748 IPLV.IP | < 0.6684 FL < 0.4211 IPLV.IP | AHRI/550/590 |
| Liquid source electrically operated centrifugal | > 300 and < 400 | < 0.5895 FL < 0.5526 IPLV.IP | < 0.6263 FL < 0.4105 IPLV.IP | AHRI/550/590 |
| Liquid source electrically operated centrifugal | > 400 and < 600 | < 0.5895 FL < 0.5263 IPLV.IP | < 0.6158 FL < 0.4000 IPLV.IP | AHRI/550/590 |
| Liquid source electrically operated centrifugal | > 600 | < 0.5895 FL < 0.5263 IPLV.IP | < 0.6158 FL < 0.4000 IPLV.IP | AHRI/550/590 |
p.188Heat Pump Heating Full
p.188Heat Pump Heating Full
p.188Heat Pump Heating Full
p.188Heat Pump Heating Full
p.189Heat Pump Heating Full
p.189Heat Pump Heating Full
p.189Heat Pump Heating Full
p.189Heat Pump Heating Full
p.1902. The cooling evaporator liquid flow rate for the simultaneous cooling and heating and heat recovery liquid cooled chilling packages rating shall be the liquid flow rates from the cooling operation full load rating.
| Size Category Refrigerating Capacitya, TonR | Heating Source Conditions (leaving liquid) or OAT (db/wb)b, F | Simultaneous Cooling and Heating Full Load Efficiency (COPSHC) c,d,e,f,g, W/W, Entering/Leaving Heating Liquid Temperature, Low, 95 F/105 F | Simultaneous Cooling and Heating Full Load Efficiency (COPSHC) c,d,e,f,g, W/W, Entering/Leaving Heating Liquid Temperature, Medium, 105 F/120 F | Simultaneous Cooling and Heating Full Load Efficiency (COPSHC) c,d,e,f,g, W/W, Entering/Leaving Heating Liquid Temperature, High, 120 F/140 F | Simultaneous Cooling and Heating Full Load Efficiency (COPSHC) c,d,e,f,g, W/W, Entering/Leaving Heating Liquid Temperature, Boost, 120 F/140 F | Test Procedure |
|---|---|---|---|---|---|---|
| < 150 | 47 db 43 wb | NAj | NAj | NAj | NAj | AHRI 550/590 |
| < 150 | 17 db 15 wb | NAj | NAj | NAj | NAj | AHRI 550/590 |
| > 150 | 47 db 43 wb | NAj | NAj | NAj | NAj | AHRI 550/590 |
| > 150 | 17 db 15 wb | NAj | NAj | NAj | NAj | AHRI 550/590 |
| Size Category Refrigerating Capacitya, TonR | Heating Source Conditions (leaving liquid) or OAT (db/wb)b, F | Simultaneous Cooling and Heating Full Load Efficiency (COPSHC) c,d,e,f,g, W/W, Entering/Leaving Heating Liquid Temperature, Low, 95 F/105 F | Simultaneous Cooling and Heating Full Load Efficiency (COPSHC) c,d,e,f,g, W/W, Entering/Leaving Heating Liquid Temperature, Medium, 105 F/120 F | Simultaneous Cooling and Heating Full Load Efficiency (COPSHC) c,d,e,f,g, W/W, Entering/Leaving Heating Liquid Temperature, High, 120 F/140 F | Simultaneous Cooling and Heating Full Load Efficiency (COPSHC) c,d,e,f,g, W/W, Entering/Leaving Heating Liquid Temperature, Boost, 120 F/140 F | Test Procedure |
| > 11.25h and < 150 | 44i | > 8.33 | > 6.41 | > 4.42 | NAj | AHRI 550/590 |
| > 11.25 h and < 150 | 65 i | NAj | NAj | NAj | > 6.150 | AHRI 550/590 |
| > 150 and < 300 | 44i | > 8.33 | > 6.41 | > 4.42 | NAj | AHRI 550/590 |
| > 150 and < 300 | 65 i | NAj | NAj | NAj | > 6.150 | AHRI 550/590 |
| > 300 and < 400 | 44i | > 8.33 | > 6.41 | > 4.42 | NAj | AHRI 550/590 |
| > 300 and < 400 | 65 i | NAj | NAj | NAj | > 6.150 | AHRI 550/590 |
| > 400 and < 600 | 44i | > 8.9 | > 6.98 | > 5 | NAj | AHRI 550/590 |
| > 400 and < 600 | 65 i | NAj | NAj | NAj | > 6.85 | AHRI 550/590 |
| > 600 | 44i | > 8.9 | > 6.98 | > 5 | NAj | AHRI 550/590 |
| > 600 | 65 i | NAj | NAj | NAj | > 6.85 | AHRI 550/590 |
p.187TABLE 110.2-J Heat Pump and Heat Recovery Chiller Packages, Heat Pump, Heating Operation– Minimum Efficiency Requirements
p.188(COPH) c,d,e,f,g, W/W,
p.188(COPH) c,d,e,f,g, W/W,
p.188(COPH) c,d,e,f,g, W/W,
p.189(COPH) c,d,e,f,g, W/W,
p.189(COPH) c,d,e,f,g, W/W,
p.189(COPH) c,d,e,f,g, W/W,
p.1903. For heating only fluid to fluid chiller packages, the evaporator flow rate obtained with an entering liquid temperature of 54 F and a leaving liquid temperature of 44 F shall be used.
| Size Category Refrigerating Capacitya, TonR | Heating Source Conditions (leaving liquid) or OAT (db/wb)b, F | Heat Pump Heating Full Load Heating Efficiency (COPH) c,d,e,f,g, W/W, Entering/Leaving Heating Liquid Temperature, Low, 95 F/105 F | Heat Pump Heating Full Load Heating Efficiency (COPH) c,d,e,f,g, W/W, Entering/Leaving Heating Liquid Temperature, Medium, 105 F/120 F | Heat Pump Heating Full Load Heating Efficiency (COPH) c,d,e,f,g, W/W, Entering/Leaving Heating Liquid Temperature, High, 120 F/140 F | Heat Pump Heating Full Load Heating Efficiency (COPH) c,d,e,f,g, W/W, Entering/Leaving Heating Liquid Temperature, Boost, 120 F/140 F | Test Procedure |
|---|---|---|---|---|---|---|
| < 150 | 47 db 43 wb | > 3.29 | > 2.77 | > 2.31 | NAj | AHRI 550/590 |
| < 150 | 17 db 15 wb | > 2.029 | > 1.775 | > 1.483 | NAj | AHRI 550/590 |
| > 150 | 47 db 43 wb | > 3.29 | > 2.77 | > 2.31 | NAj | AHRI 550/590 |
| > 150 | 17 db 15 wb | > 2.029 | > 1.775 | > 1.483 | NAj | AHRI 550/590 |
| Size Category Refrigerating Capacitya, TonR | Heating Source Conditions (leaving liquid) or OAT (db/wb)b, F | Heat Pump Heating Full Load Heating Efficiency (COPH) c,d,e,f,g, W/W, Entering/Leaving Heating Liquid Temperature, Low, 95 F/105 F | Heat Pump Heating Full Load Heating Efficiency (COPH) c,d,e,f,g, W/W, Entering/Leaving Heating Liquid Temperature, Medium, 105 F/120 F | Heat Pump Heating Full Load Heating Efficiency (COPH) c,d,e,f,g, W/W, Entering/Leaving Heating Liquid Temperature, High, 120 F/140 F | Heat Pump Heating Full Load Heating Efficiency (COPH) c,d,e,f,g, W/W, Entering/Leaving Heating Liquid Temperature, Boost, 120 F/140 F | Test Procedure |
| > 11.25h and < 150 | 44i | > 4.64 | > 3.68 | > 2.68 | NAj | AHRI 550/590 |
| > 11.25 h and < 150 | 65 i | NAj | NAj | NAj | > 3.55 | AHRI 550/590 |
| > 150 and < 300 | 44i | > 4.64 | > 3.68 | > 2.68 | NAj | AHRI 550/590 |
| > 150 and < 300 | 65 i | NAj | NAj | NAj | > 3.55 | AHRI 550/590 |
| > 300 and < 400 | 44i | > 4.64 | > 3.68 | > 2.68 | NAj | AHRI 550/590 |
| > 300 and < 400 | 65 i | NAj | NAj | NAj | > 3.55 | AHRI 550/590 |
| > 400 and < 600 | 44i | > 4.93 | > 3.96 | > 2.97 | NAj | AHRI 550/590 |
| > 400 and < 600 | 65 i | NAj | NAj | NAj | > 3.9 | AHRI 550/590 |
| > 600 | 44i | > 4.93 | > 3.96 | > 2.97 | NAg | AHRI 550/590 |
| > 600 | 65 i | NAj | NAj | NAj | > 3.9 | AHRI 550/590 |
| Size Category Refrigerating Capacitya, TonR | Heating Source Conditions (leaving liquid) or OAT (db/wb)b, F | Heat Pump Heating Full Load Heating Efficiency (COPH) c,d,e,f,g, W/W, Entering/Leaving Heating Liquid Temperature, Low, 95 F/105 F | Heat Pump Heating Full Load Heating Efficiency (COPH) c,d,e,f,g, W/W, Entering/Leaving Heating Liquid Temperature, Medium, 105 F/120 F | Heat Pump Heating Full Load Heating Efficiency (COPH) c,d,e,f,g, W/W, Entering/Leaving Heating Liquid Temperature, High, 120 F/140 F | Heat Pump Heating Full Load Heating Efficiency (COPH) c,d,e,f,g, W/W, Entering/Leaving Heating Liquid Temperature, Boost, 120 F/140 F | Test Procedure |
| > 11.25 h and < 150 | 44i | > 4.64 | > 3.68 | > 2.68 | NAj | AHRI 550/590 |
| > 11.25 h and < 150 | 65 i | NAj | NAj | NAj | > 3.55 | AHRI 550/590 |
| > 150 and < 300 | 44i | > 4.64 | > 3.68 | > 2.68 | NAj | AHRI 550/590 |
| > 150 and < 300 | 65 i | NAj | NAj | NAj | > 3.55 | AHRI 550/590 |
| > 300 and < 400 | 44i | > 4.64 | > 3.68 | > 2.68 | NAj | AHRI 550/590 |
| > 300 and < 400 | 65 i | NAg | NAg | NAg | > 3.55 | AHRI 550/590 |
| > 400 and < 600 | 44i | > 4.93 | > 3.96 | > 2.97 | NAj | AHRI 550/590 |
| > 400 and < 600 | 65 i | NAj | NAj | NAj | > 3.9 | AHRI 550/590 |
| > 600 | 44i | > 4.93 | > 3.96 | > 2.97 | NAj | AHRI 550/590 |
| > 600 | 65 i | NAj | NAj | NAj | > 3.9 | AHRI 550/590 |
p.190j. NA means the requirements are not applicable.
p.189a. The size category is the full-load net refrigeration cooling mode capacity, which is the capacity of the evaporator available for cooling of the thermal load
p.189external to the chilling package.
p.189b. For air source heat pumps, compliance with both the 47 F and 17 F heating source outdoor air temperature (OAT) rating efficiency is required for heating.
p.185a Applicable test procedure and reference year are provided under the definitions.
p.189Heating full load rating conditions are at standard rating conditions defined in AHRI 550/590 (I-P), Table 4, includes the impact of defrost for air source heating ratings.
p.180a Applicable test procedure and reference year are provided under the definitions.
p.189d. For units that operate in both cooling and heating, compliance with both the cooling and heating efficiency is required.
p.180b IEERs are only applicable to equipment with capacity control as specified by AHRI 1230 test procedures.p.181
p.189e. For heat recovery heating chilling package applications where there is simultaneous cooling and heating, compliance with the heating performance heat
p.189recover COPHR is only required at one of the four heating AHRI 550/590 (I-P) standard ratings conditions of Low, Medium, Hot-Water 1 or Hot-Water 2. Compliance with the cooling only performance is required as defined in footnotes b and c of Table 110.2-I.
p.189f. For applications where the chilling package is installed to operate only in heating, compliance only with the heating performance COPH is required at only one of the heating AHRI 550/590 (I-P) standard rating conditions of Low, Medium, High, or Boost. Compliance with cooling performance is not required.
p.186a. The size category is the full-load net refrigeration cooling mode capacity, which is the capacity of the evaporator available for cooling of the thermal load
p.186external to the chilling package. b. Cooling rating conditions are standard rating conditions defined in AHRI 550/590 (I-P), Table 4, except for liquid cooled centrifugal chilling packages which
p.189g. For heat pump chilling package applications where the cooling capacity is not being used for conditioning, compliance with the heating performance COPH is only required at one of the heating AHRI 550/590 (I-P) standard rating conditions of Low, Medium, High, or Boost. Compliance with the cooling performance is required as defined in footnotes b and c of Table 110.2-I, except as noted in footnote f.
p.186can adjust cooling efficiency for nonstandard rating conditions using the Kadj procedure in accordance with Section 110.2(a). For cooling operation, compliance with both the FL and IPLV is required, but only compliance with Path A or Path B cooling efficiency is required. d. For units that operate in both cooling and heating, compliance with both the cooling and heating efficiency is required.p.187
p.189h. Water to water heat pumps with a capacity less than 135,000 Btu/h are included in Table 110.2-B Heat Pumps, Minimum Efficiency Requirements.p.190
p.186SECTION 110.2 – MANDATORY REQUIREMENTS FOR SPACE-CONDITIONING EQUIPMENT
p.187SECTION 110.2 – MANDATORY REQUIREMENTS FOR SPACE-CONDITIONING EQUIPMENT
p.188SECTION 110.2 – MANDATORY REQUIREMENTS FOR SPACE-CONDITIONING EQUIPMENT
p.189SECTION 110.2 – MANDATORY REQUIREMENTS FOR SPACE-CONDITIONING EQUIPMENT
p.190SECTION 110.2 – MANDATORY REQUIREMENTS FOR SPACE-CONDITIONING EQUIPMENT
p.191SECTION 110.2 – MANDATORY REQUIREMENTS FOR SPACE-CONDITIONING EQUIPMENT
p.183a. Deduct 0.2 from the required EERs and IEERs for Variable Refrigerant Flow (VRF) Multi-split system units with a
p.183heating recovery section. b. Applicable test procedure and reference year are provided under the definitions. c. IEERs are only applicable to equipment with capacity control as specified by AHRI 1230 test procedures.p.184
p.180SECTION 110.2 – MANDATORY REQUIREMENTS FOR SPACE-CONDITIONING EQUIPMENT
p.181SECTION 110.2 – MANDATORY REQUIREMENTS FOR SPACE-CONDITIONING EQUIPMENT
p.182SECTION 110.2 – MANDATORY REQUIREMENTS FOR SPACE-CONDITIONING EQUIPMENT
p.183SECTION 110.2 – MANDATORY REQUIREMENTS FOR SPACE-CONDITIONING EQUIPMENT
p.184SECTION 110.2 – MANDATORY REQUIREMENTS FOR SPACE-CONDITIONING EQUIPMENT
p.185SECTION 110.2 – MANDATORY REQUIREMENTS FOR SPACE-CONDITIONING EQUIPMENT