SECTION 110.2 – MANDATORY REQUIREMENTS FOR SPACE-CONDITIONING EQUIPMENT (part 2 of 3)

p.181TABLE 110.2-G Electrically Operated Variable Refrigerant Flow Air-to-Air and Applied Heat Pumps - Minimum Efficiency

p.182CONTINUED: TABLE 110.2-G Electrically Operated Variable Refrigerant Flow Air-to-Air and Applied Heat Pumps - Minimum

p.183CONTINUED: TABLE 110.2-G Electrically Operated Variable Refrigerant Flow Air-to-Air and Applied Heat Pumps - Minimum Efficiency Requirements

p.180Minimum Efficiency Requirements

p.181Requirements

p.182Efficiency Requirements

p.187e. For heat recovery heating chilling package applications where there is simultaneous cooling and heating, compliance with the heating performance heat

p.188(CONTINUED) TABLE 110.2-J Heat Pump and Heat Recovery Chiller Packages, Heat Pump, Heating Operation– Minimum Efficiency Requirements

p.189(CONTINUED) TABLE 110.2-J Heat Pump and Heat Recovery Chiller Packages, Heat Pump, Heating Operation– Minimum Efficiency Requirements

p.190i. Source leaving liquid temperature.

p.191(CONTINUED) TABLE 110.2-K Heat Pump and Heat Recovery Chiller Packages, Simultaneous Cooling and Heating, Heating Operation– Minimum Efficiency

p.186TABLE 110.2-I Heat Pump and Heat Recovery Chiller Packages, Cooling Operation - Minimum Efficiency Requirements

DX-DOAS Units, Single-Package and Remote Condenser – Minimum Efficiency Requirements p.185 Download CSV
Equipment TypeEnergy RecoverySubcategory or Rating ConditionMinimum EfficiencyTest Procedurea
Water cooled (dehumidification mode)With energy recoveryCooling tower condenser water5.1 ISMRE2AHRI 920
Water source heat pump (dehumidification mode)With energy recoveryGround source, closed and open loop5.0 ISMRE2AHRI 920
Water source heat pump (dehumidification mode)With energy recoveryWater source4.6 ISMRE2AHRI 920
Air source heat pumps (heating mode)With energy recovery3.2 ISCOP2AHRI 920
Water source heat pump (heating mode)With energy recoveryGround source, closed and open loop3.5 ISCOP2AHRI 920
Water source heat pump (heating mode)With energy recoveryWater source4.04 ISCOP2AHRI 920

p.187recover COPHR is only required at one of the four heating AHRI 550/590 (I-P) standard ratings conditions of Low, Medium, Hot-Water 1 or Hot-Water 2. Compliance with the cooling only performance is required as defined in footnotes b and c. f. Water to water heat pumps with a capacity less than 135,000 Btu/h are included in Table 110.2-B Heat Pumps, Minimum Efficiency Requirements.

p.191Requirements

Electrically Operated Variable Refrigerant Flow Air-to-Air and Applied Heat Pumps - Minimum Efficiency Requirements p.182 Download CSV
Equipment TypeSize CategoryHeating Section TypeSub-Category or Rating ConditionMinimum EfficiencyTest Procedure b
VRF Groundwater source (cooling mode)<135,000 Btu/hAllVRF Multi-split System a 59ºF entering water16.2 EERAHRI 1230
VRF Groundwater source (cooling mode)≥135,000 Btu/hAllVRF Multi-split System a 59ºF entering water13.8 EERAHRI 1230
VRF Ground source (cooling mode)<135,000 Btu/hAllVRF Multi-split System a 77ºF entering water13.4 EERAHRI 1230
VRF Ground source (cooling mode)≥135,000 Btu/hAllVRF Multi-split System a 77ºF entering water11.0 EERAHRI 1230
VRF Air Cooled (heating mode)<65,000 Btu/h (cooling capacity)---VRF Multi-split System7.7 HSPF Before 1/1/2025 7.5 HSPF2 On or after 1/1/2025AHRI 1230 Before 1/1/2025 AHRI 210/240 On or After 1/1/2025
VRF Air Cooled (heating mode)≥65,000 Btu/h and <135,000 Btu/h (cooling capacity)---VRF Multi-split system 47ºF db/ 43ºF wb outdoor airFederal Minimum COPAHRI 1230
VRF Air Cooled (heating mode)≥65,000 Btu/h and <135,000 Btu/h (cooling capacity)---VRF Multi-split system 17ºF db/15ºF wb outdoor air2.25 COPAHRI 1230
VRF Air Cooled (heating mode)≥135,000 Btu/h (cooling capacity)---VRF Multi-split system 47ºF db/ 43ºF wb outdoor airFederal Minimum COPAHRI 1230
Equipment TypeSize CategoryHeating Section TypeSub-Category or Rating ConditionMinimum EfficiencyTest Procedure b
VRF Air Cooled (heating mode)≥135,000 Btu/h (cooling capacity)---VRF Multi-split system 17ºF db/15ºF wb outdoor air2.05 COPAHRI 1230
VRF Water source (heating mode)< 65,000 Btu/h (cooling capacity)---VRF Multi-split System 68oF entering waterFederal Minimum COPAHRI 1230
VRF Water source (heating mode)≥65,000 Btu/h and <135,000 Btu/h (cooling capacity)---VRF Multi-split System 68ºF entering waterFederal Minimum COPAHRI 1230
VRF Water source (heating mode)≥135,000 Btu/h and < 240,000 Btu/h (cooling capacity)---VRF Multi-split System 68ºF entering waterFederal Minimum COPAHRI 1230
VRF Water source (heating mode)≥ 240,000 Btu/h (cooling capacity)---VRF Multi-split System 68oF entering waterFederal Minimum COPAHRI 1230
VRF Groundwater source (heating mode)<135,000 Btu/h (cooling capacity)---VRF Multi-split System 50ºF entering water3.6 COPAHRI 1230
VRF Groundwater source (heating mode)≥135,000 Btu/h (cooling capacity)---VRF Multi-split System 50ºF entering water3.3 COPAHRI 1230
VRF Ground source (heating mode)<135,000 Btu/h (cooling capacity)---VRF Multi-split System 32ºF entering water3.1 COPAHRI 1230
VRF Ground source (heating mode)≥135,000 Btu/h (cooling capacity)---VRF Multi-split System 32ºF entering water2.8 COPAHRI 1230
Electrically Operated Variable Refrigerant Flow (VRF) Air Conditioners p.180 Download CSV
Equipment TypeSize CategoryHeating Section TypeSub-Category or Rating ConditionMinimum EfficiencyTest Procedurea
VRF Air Conditioners, Air Cooled<65,000 Btu/hAllVRF Multi-split System13.0 SEER Before 1/1/2023 Federal Minimum SEER2 On or After 1/1/2023AHRI 1230 Before 1/1/2023 AHRI 210/240 On or After 1/1/2023
VRF Air Conditioners, Air Cooled≥65,000 Btu/h and <135,000 Btu/hElectric Resistance (or none)VRF Multi-split System10.5 EER Federal Minimum IEER bAHRI 1230
VRF Air Conditioners, Air Cooled≥135,000 Btu/h and <240,000 Btu/hElectric Resistance (or none)VRF Multi-split System10.3 EER Federal Minimum IEER bAHRI 1230
VRF Air Conditioners, Air Cooled≥240,000 Btu/hElectric Resistance (or none)VRF Multi-split System9.5 EER Federal Minimum IEER bAHRI 1230
Electrically Operated Variable Refrigerant Flow Air-to-Air and Applied Heat Pumps - Minimum Efficiency Requirements p.181 Download CSV
Equipment TypeSize CategoryHeating Section TypeSub-Category or Rating ConditionMinimum EfficiencyTest Procedure b
VRF Air Cooled, (cooling mode)<65,000 Btu/hAllVRF Multi-split System13.0 SEER Before 1/1/2023 Federal Minimum =SEER2 On or after 1/1/2023AHRI 1230 Before 1/1/2023 AHRI 210/240 On or After 1/1/2023
VRF Air Cooled, (cooling mode)≥65,000 Btu/h and <135,000 Btu/hElectric Resistance (or none)VRF Multi-split System a10.3 EER Federal Minimum IEER cAHRI 1230
VRF Air Cooled, (cooling mode)≥135,000 Btu/h and <240,000 Btu/hElectric Resistance (or none)VRF Multi-split System a9.9 EER Federal Minimum IEER cAHRI 1230
VRF Air Cooled, (cooling mode)≥240,000 Btu/hElectric Resistance (or none)VRF Multi-split System a9.1 EER Federal Minimum IEER cAHRI 1230
VRF Water source (cooling mode)<65,000 Btu/hAllVRF Multi-split systems a 86ºF entering water12.0 EER Federal Minimum IEER cAHRI 1230
VRF Water source (cooling mode)≥65,000 Btu/h and <135,000 Btu/hAllVRF Multi-split System a 86ºF entering water12.0 EER Federal Minimum IEER cAHRI 1230
VRF Water source (cooling mode)≥135,000 Btu/h and < 240,000AllVRF Multi-split System a 86ºF entering water10.0 EER Federal Minimum IEER cAHRI 1230
VRF Water source (cooling mode)≥ 240,000 Btu/hAllVRF Multi-split Systema 86oF entering water10.0 EER Federal Minimum IEERAHRI 1230
DX-DOAS Units, Single-Package and Remote Condenser – Minimum Efficiency Requirements p.184 Download CSV
Equipment TypeEnergy RecoverySubcategory or Rating ConditionMinimum EfficiencyTest Procedurea
Air cooled (dehumidification mode)Without energy recoveryNA3.8 ISMRE2AHRI 920
Air source heat pumps (dehumidification mode)Without energy recoveryNA3.8 ISMRE2AHRI 920
Water cooled (dehumidification mode)Without energy recoveryCooling Tower Condenser Water4.7 ISMRE2AHRI 920
Water source heat pump (dehumidification mode)Without energy recoveryGround source, closed and open loop4.6 ISMRE2AHRI 920
Water source heat pump (dehumidification mode)Without energy recoveryWater source3.8 ISMRE2AHRI 920
Air source heat pumps (heating mode)Without energy recoveryNA2.05 ISCOP2AHRI 920
Water source heat pump (heating mode)Without energy recoveryGround source, closed and open loop2.13 ISCOP2AHRI 920
Water source heat pump (heating mode)Without energy recoveryWater source2.13 ISCOP2AHRI 920
Air cooled (dehumidification mode)With energy recoveryNA5.0 ISMRE2AHRI 920
Air source heat pumps (dehumidification mode)With energy recoveryNA5.0 ISMRE2AHRI 920

p.1901. The cooling evaporator liquid flow rate used for the heating rating for a reverse cycle air to water heat pump shall be the flow rate determined during the full load cooling rating.

Cooling operation minimum efficiency based on type of equipment and capacity. p.186 Download CSV
Equipment TypeSize Category Refrigerating Capacitya, tonRCooling Operation Efficiencyb,c,d,e , Air Source EER (FL/IPLV), Btu/W h, Liquid Source Power Input per Capacity (FL/IPLV), kW/tonR Path ACooling Operation Efficiencyb,c,d,e, Air Source EER (FL/IPLV), Btu/W h, Liquid Source Power Input per Capacity (FL/IPLV), kW/tonR Path BTest Procedure
Air Source< 150> 5.595 FL > 13.02 IPLV.IP> 9.215 FL > 15.01 IPLV.IPAHRI/550/590
Air Source> 150> 5.595 FL > 13.30 IPLV.IP> 9.215 FL > 15.30 IPLV.IPAHRI/550/590
Liquid source electrically operated positive displacement> 11.25f and < 150< 0.7895 FL < 0.6316 IPLV.IP< 0.8211 FL < 0.5263 IPLV.IPAHRI/550/590
Liquid source electrically operated positive displacement> 150 and < 300< 0.7579 FL < 0.5895 IPLV.IP< 0.7895 FL < 0.5158 IPLV.IPAHRI/550/590
Liquid source electrically operated positive displacement> 300 and < 400< 0.6947 FL < 0.5684 IPLV.IP< 0.7158 FL < 0.4632 IPLV.IPAHRI/550/590
Liquid source electrically operated positive displacement> 400 and < 600< 0.6421 FL < 0.5474 IPLV.IP< 0.6579 FL < 0.4316 IPLV.IPAHRI/550/590
Liquid source electrically operated positive displacement> 600< 0.5895 FL < 0.5263 IPLV.IP< 0.6158 FL < 0.4000 IPLV.IPAHRI/550/590
Liquid source electrically operated centrifugal> 11.25f and < 150< 0.6421 FL < 0.5789 IPLV.IP< 0.7316 FL < 0.4632 IPLV.IPAHRI/550/590
Liquid source electrically operated centrifugal> 150 and < 300< 0.6190 FL < 0.5748 IPLV.IP< 0.6684 FL < 0.4211 IPLV.IPAHRI/550/590
Liquid source electrically operated centrifugal> 300 and < 400< 0.5895 FL < 0.5526 IPLV.IP< 0.6263 FL < 0.4105 IPLV.IPAHRI/550/590
Liquid source electrically operated centrifugal> 400 and < 600< 0.5895 FL < 0.5263 IPLV.IP< 0.6158 FL < 0.4000 IPLV.IPAHRI/550/590
Liquid source electrically operated centrifugal> 600< 0.5895 FL < 0.5263 IPLV.IP< 0.6158 FL < 0.4000 IPLV.IPAHRI/550/590

p.188Heat Pump Heating Full

p.188Heat Pump Heating Full

p.188Heat Pump Heating Full

p.188Heat Pump Heating Full

p.189Heat Pump Heating Full

p.189Heat Pump Heating Full

p.189Heat Pump Heating Full

p.189Heat Pump Heating Full

p.1902. The cooling evaporator liquid flow rate for the simultaneous cooling and heating and heat recovery liquid cooled chilling packages rating shall be the liquid flow rates from the cooling operation full load rating.

TABLE 110.2-K Heat Pump and Heat Recovery Chiller Packages, Simultaneous Cooling and Heating, Heating Operation– Minimum Efficiency Requirements p.190 Download CSV
Size Category Refrigerating Capacitya, TonRHeating Source Conditions (leaving liquid) or OAT (db/wb)b, FSimultaneous Cooling and Heating Full Load Efficiency (COPSHC) c,d,e,f,g, W/W, Entering/Leaving Heating Liquid Temperature, Low, 95 F/105 FSimultaneous Cooling and Heating Full Load Efficiency (COPSHC) c,d,e,f,g, W/W, Entering/Leaving Heating Liquid Temperature, Medium, 105 F/120 FSimultaneous Cooling and Heating Full Load Efficiency (COPSHC) c,d,e,f,g, W/W, Entering/Leaving Heating Liquid Temperature, High, 120 F/140 FSimultaneous Cooling and Heating Full Load Efficiency (COPSHC) c,d,e,f,g, W/W, Entering/Leaving Heating Liquid Temperature, Boost, 120 F/140 FTest Procedure
< 15047 db 43 wbNAjNAjNAjNAjAHRI 550/590
< 15017 db 15 wbNAjNAjNAjNAjAHRI 550/590
> 15047 db 43 wbNAjNAjNAjNAjAHRI 550/590
> 15017 db 15 wbNAjNAjNAjNAjAHRI 550/590
Size Category Refrigerating Capacitya, TonRHeating Source Conditions (leaving liquid) or OAT (db/wb)b, FSimultaneous Cooling and Heating Full Load Efficiency (COPSHC) c,d,e,f,g, W/W, Entering/Leaving Heating Liquid Temperature, Low, 95 F/105 FSimultaneous Cooling and Heating Full Load Efficiency (COPSHC) c,d,e,f,g, W/W, Entering/Leaving Heating Liquid Temperature, Medium, 105 F/120 FSimultaneous Cooling and Heating Full Load Efficiency (COPSHC) c,d,e,f,g, W/W, Entering/Leaving Heating Liquid Temperature, High, 120 F/140 FSimultaneous Cooling and Heating Full Load Efficiency (COPSHC) c,d,e,f,g, W/W, Entering/Leaving Heating Liquid Temperature, Boost, 120 F/140 FTest Procedure
> 11.25h and < 15044i> 8.33> 6.41> 4.42NAjAHRI 550/590
> 11.25 h and < 15065 iNAjNAjNAj> 6.150AHRI 550/590
> 150 and < 30044i> 8.33> 6.41> 4.42NAjAHRI 550/590
> 150 and < 30065 iNAjNAjNAj> 6.150AHRI 550/590
> 300 and < 40044i> 8.33> 6.41> 4.42NAjAHRI 550/590
> 300 and < 40065 iNAjNAjNAj> 6.150AHRI 550/590
> 400 and < 60044i> 8.9> 6.98> 5NAjAHRI 550/590
> 400 and < 60065 iNAjNAjNAj> 6.85AHRI 550/590
> 60044i> 8.9> 6.98> 5NAjAHRI 550/590
> 60065 iNAjNAjNAj> 6.85AHRI 550/590

p.187TABLE 110.2-J Heat Pump and Heat Recovery Chiller Packages, Heat Pump, Heating Operation– Minimum Efficiency Requirements

p.188(COPH) c,d,e,f,g, W/W,

p.188(COPH) c,d,e,f,g, W/W,

p.188(COPH) c,d,e,f,g, W/W,

p.189(COPH) c,d,e,f,g, W/W,

p.189(COPH) c,d,e,f,g, W/W,

p.189(COPH) c,d,e,f,g, W/W,

p.1903. For heating only fluid to fluid chiller packages, the evaporator flow rate obtained with an entering liquid temperature of 54 F and a leaving liquid temperature of 44 F shall be used.

Heat Pump and Heat Recovery Chiller Packages, Heat Pump, Heating Operation– Minimum Efficiency RequirementsEquipment Type: Air Source p.187 Download CSV
Size Category Refrigerating Capacitya, TonRHeating Source Conditions (leaving liquid) or OAT (db/wb)b, FHeat Pump Heating Full Load Heating Efficiency (COPH) c,d,e,f,g, W/W, Entering/Leaving Heating Liquid Temperature, Low, 95 F/105 FHeat Pump Heating Full Load Heating Efficiency (COPH) c,d,e,f,g, W/W, Entering/Leaving Heating Liquid Temperature, Medium, 105 F/120 FHeat Pump Heating Full Load Heating Efficiency (COPH) c,d,e,f,g, W/W, Entering/Leaving Heating Liquid Temperature, High, 120 F/140 FHeat Pump Heating Full Load Heating Efficiency (COPH) c,d,e,f,g, W/W, Entering/Leaving Heating Liquid Temperature, Boost, 120 F/140 FTest Procedure
< 15047 db 43 wb> 3.29> 2.77> 2.31NAjAHRI 550/590
< 15017 db 15 wb> 2.029> 1.775> 1.483NAjAHRI 550/590
> 15047 db 43 wb> 3.29> 2.77> 2.31NAjAHRI 550/590
> 15017 db 15 wb> 2.029> 1.775> 1.483NAjAHRI 550/590
Size Category Refrigerating Capacitya, TonRHeating Source Conditions (leaving liquid) or OAT (db/wb)b, FHeat Pump Heating Full Load Heating Efficiency (COPH) c,d,e,f,g, W/W, Entering/Leaving Heating Liquid Temperature, Low, 95 F/105 FHeat Pump Heating Full Load Heating Efficiency (COPH) c,d,e,f,g, W/W, Entering/Leaving Heating Liquid Temperature, Medium, 105 F/120 FHeat Pump Heating Full Load Heating Efficiency (COPH) c,d,e,f,g, W/W, Entering/Leaving Heating Liquid Temperature, High, 120 F/140 FHeat Pump Heating Full Load Heating Efficiency (COPH) c,d,e,f,g, W/W, Entering/Leaving Heating Liquid Temperature, Boost, 120 F/140 FTest Procedure
> 11.25h and < 15044i> 4.64> 3.68> 2.68NAjAHRI 550/590
> 11.25 h and < 15065 iNAjNAjNAj> 3.55AHRI 550/590
> 150 and < 30044i> 4.64> 3.68> 2.68NAjAHRI 550/590
> 150 and < 30065 iNAjNAjNAj> 3.55AHRI 550/590
> 300 and < 40044i> 4.64> 3.68> 2.68NAjAHRI 550/590
> 300 and < 40065 iNAjNAjNAj> 3.55AHRI 550/590
> 400 and < 60044i> 4.93> 3.96> 2.97NAjAHRI 550/590
> 400 and < 60065 iNAjNAjNAj> 3.9AHRI 550/590
> 60044i> 4.93> 3.96> 2.97NAgAHRI 550/590
> 60065 iNAjNAjNAj> 3.9AHRI 550/590
Size Category Refrigerating Capacitya, TonRHeating Source Conditions (leaving liquid) or OAT (db/wb)b, FHeat Pump Heating Full Load Heating Efficiency (COPH) c,d,e,f,g, W/W, Entering/Leaving Heating Liquid Temperature, Low, 95 F/105 FHeat Pump Heating Full Load Heating Efficiency (COPH) c,d,e,f,g, W/W, Entering/Leaving Heating Liquid Temperature, Medium, 105 F/120 FHeat Pump Heating Full Load Heating Efficiency (COPH) c,d,e,f,g, W/W, Entering/Leaving Heating Liquid Temperature, High, 120 F/140 FHeat Pump Heating Full Load Heating Efficiency (COPH) c,d,e,f,g, W/W, Entering/Leaving Heating Liquid Temperature, Boost, 120 F/140 FTest Procedure
> 11.25 h and < 15044i> 4.64> 3.68> 2.68NAjAHRI 550/590
> 11.25 h and < 15065 iNAjNAjNAj> 3.55AHRI 550/590
> 150 and < 30044i> 4.64> 3.68> 2.68NAjAHRI 550/590
> 150 and < 30065 iNAjNAjNAj> 3.55AHRI 550/590
> 300 and < 40044i> 4.64> 3.68> 2.68NAjAHRI 550/590
> 300 and < 40065 iNAgNAgNAg> 3.55AHRI 550/590
> 400 and < 60044i> 4.93> 3.96> 2.97NAjAHRI 550/590
> 400 and < 60065 iNAjNAjNAj> 3.9AHRI 550/590
> 60044i> 4.93> 3.96> 2.97NAjAHRI 550/590
> 60065 iNAjNAjNAj> 3.9AHRI 550/590

p.190j. NA means the requirements are not applicable.

p.189a. The size category is the full-load net refrigeration cooling mode capacity, which is the capacity of the evaporator available for cooling of the thermal load

p.189external to the chilling package.

p.189b. For air source heat pumps, compliance with both the 47 F and 17 F heating source outdoor air temperature (OAT) rating efficiency is required for heating.

p.185a Applicable test procedure and reference year are provided under the definitions.

p.189Heating full load rating conditions are at standard rating conditions defined in AHRI 550/590 (I-P), Table 4, includes the impact of defrost for air source heating ratings.

p.180a Applicable test procedure and reference year are provided under the definitions.

p.189d. For units that operate in both cooling and heating, compliance with both the cooling and heating efficiency is required.

p.180b IEERs are only applicable to equipment with capacity control as specified by AHRI 1230 test procedures.p.181

p.189e. For heat recovery heating chilling package applications where there is simultaneous cooling and heating, compliance with the heating performance heat

p.189recover COPHR is only required at one of the four heating AHRI 550/590 (I-P) standard ratings conditions of Low, Medium, Hot-Water 1 or Hot-Water 2. Compliance with the cooling only performance is required as defined in footnotes b and c of Table 110.2-I.

p.189f. For applications where the chilling package is installed to operate only in heating, compliance only with the heating performance COPH is required at only one of the heating AHRI 550/590 (I-P) standard rating conditions of Low, Medium, High, or Boost. Compliance with cooling performance is not required.

p.186a. The size category is the full-load net refrigeration cooling mode capacity, which is the capacity of the evaporator available for cooling of the thermal load

p.186external to the chilling package. b. Cooling rating conditions are standard rating conditions defined in AHRI 550/590 (I-P), Table 4, except for liquid cooled centrifugal chilling packages which

p.189g. For heat pump chilling package applications where the cooling capacity is not being used for conditioning, compliance with the heating performance COPH is only required at one of the heating AHRI 550/590 (I-P) standard rating conditions of Low, Medium, High, or Boost. Compliance with the cooling performance is required as defined in footnotes b and c of Table 110.2-I, except as noted in footnote f.

p.186can adjust cooling efficiency for nonstandard rating conditions using the Kadj procedure in accordance with Section 110.2(a). For cooling operation, compliance with both the FL and IPLV is required, but only compliance with Path A or Path B cooling efficiency is required. d. For units that operate in both cooling and heating, compliance with both the cooling and heating efficiency is required.p.187

p.189h. Water to water heat pumps with a capacity less than 135,000 Btu/h are included in Table 110.2-B Heat Pumps, Minimum Efficiency Requirements.p.190

p.186SECTION 110.2 – MANDATORY REQUIREMENTS FOR SPACE-CONDITIONING EQUIPMENT

p.187SECTION 110.2 – MANDATORY REQUIREMENTS FOR SPACE-CONDITIONING EQUIPMENT

p.188SECTION 110.2 – MANDATORY REQUIREMENTS FOR SPACE-CONDITIONING EQUIPMENT

p.189SECTION 110.2 – MANDATORY REQUIREMENTS FOR SPACE-CONDITIONING EQUIPMENT

p.190SECTION 110.2 – MANDATORY REQUIREMENTS FOR SPACE-CONDITIONING EQUIPMENT

p.191SECTION 110.2 – MANDATORY REQUIREMENTS FOR SPACE-CONDITIONING EQUIPMENT

p.183a. Deduct 0.2 from the required EERs and IEERs for Variable Refrigerant Flow (VRF) Multi-split system units with a

p.183heating recovery section. b. Applicable test procedure and reference year are provided under the definitions. c. IEERs are only applicable to equipment with capacity control as specified by AHRI 1230 test procedures.p.184

p.180SECTION 110.2 – MANDATORY REQUIREMENTS FOR SPACE-CONDITIONING EQUIPMENT

p.181SECTION 110.2 – MANDATORY REQUIREMENTS FOR SPACE-CONDITIONING EQUIPMENT

p.182SECTION 110.2 – MANDATORY REQUIREMENTS FOR SPACE-CONDITIONING EQUIPMENT

p.183SECTION 110.2 – MANDATORY REQUIREMENTS FOR SPACE-CONDITIONING EQUIPMENT

p.184SECTION 110.2 – MANDATORY REQUIREMENTS FOR SPACE-CONDITIONING EQUIPMENT

p.185SECTION 110.2 – MANDATORY REQUIREMENTS FOR SPACE-CONDITIONING EQUIPMENT