SECTION 110.2 – MANDATORY REQUIREMENTS FOR SPACE-CONDITIONING EQUIPMENT (part 3 of 3)

p.192(CONTINUED) TABLE 110.2-K Heat Pump and Heat Recovery Chiller Packages, Simultaneous Cooling and Heating, Heating Operation– Minimum Efficiency

p.1931. The cooling evaporator liquid flow rate used for the heating rating for a reverse cycle air to water heat pump shall be the flow rate determined during the full load cooling rating. 2. The cooling evaporator liquid flow rate for the simultaneous cooling and heating and heat recovery liquid cooled chilling packages rating shall be the liquid flow rates from the cooling operation full load rating. 3. For heating only fluid to fluid chiller packages, the evaporator flow rate obtained with an entering liquid temperature of 54 F and a leaving liquid temperature of 44 F shall be used. j. NA means the requirements are not applicable.

p.194(CONTINUED) TABLE 110.2-L Heat Pump and Heat Recovery Chiller Packages, Heat Recovery, Heating Operation– Minimum Efficiency Requirements Equipment Type: Liquid source electrically operated positive displacement

p.195(CONTINUED) TABLE 110.2-L Heat Pump and Heat Recovery Chiller Packages, Heat Recovery, Heating Operation– Minimum Efficiency Requirements Equipment Type: Liquid source electrically operated centrifugal

p.1962. The cooling evaporator liquid flow rate for the simultaneous cooling and heating and heat recovery liquid cooled chilling packages rating shall be the liquid flow rates from the cooling operation full load rating. 3. For heating only fluid to fluid chiller packages, the evaporator flow rate obtained with an entering liquid temperature of 54 F and a leaving liquid temperature of 44 F shall be used. j. NA means the requirements are not applicable.

p.192Requirements

p.194Heat Recovery Heating

p.194Heat Recovery Heating

p.194Heat Recovery Heating

p.194Heat Recovery Heating

p.195Heat Recovery Heating

p.195Heat Recovery Heating

p.195Heat Recovery Heating

p.195Heat Recovery Heating

p.192Equipment Type: Liquid source electrically operated centrifugal

TABLE 110.2-K Heat Pump and Heat Recovery Chiller Packages, Simultaneous Cooling and Heating, Heating Operation– Minimum Efficiency Requirements p.192 Download CSV
Size Category Refrigerating Capacitya, TonRHeating Source Conditions (leaving liquid) or OAT (db/wb)b, FSimultaneous Cooling and Heating Full Load Efficiency (COPSHC) c,d,e,f,g, W/W, Entering/Leaving Heating Liquid Temperature, Low, 95 F/105 FSimultaneous Cooling and Heating Full Load Efficiency (COPSHC) c,d,e,f,g, W/W, Entering/Leaving Heating Liquid Temperature, Medium, 105 F/120 FSimultaneous Cooling and Heating Full Load Efficiency (COPSHC) c,d,e,f,g, W/W, Entering/Leaving Heating Liquid Temperature, High, 120 F/140 FSimultaneous Cooling and Heating Full Load Efficiency (COPSHC) c,d,e,f,g, W/W, Entering/Leaving Heating Liquid Temperature, Boost, 120 F/140 FTest Procedure
Size Category Refrigerating Capacitya, TonRHeating Source Conditions (leaving liquid) or OAT (db/wb)b, FSimultaneous Cooling and Heating Full Load Efficiency (COPSHC) c,d,e,f,g, W/W, Entering/Leaving Heating Liquid Temperature, Low, 95 F/105 FSimultaneous Cooling and Heating Full Load Efficiency (COPSHC) c,d,e,f,g, W/W, Entering/Leaving Heating Liquid Temperature, Medium, 105 F/120 FSimultaneous Cooling and Heating Full Load Efficiency (COPSHC) c,d,e,f,g, W/W, Entering/Leaving Heating Liquid Temperature, High, 120 F/140 FSimultaneous Cooling and Heating Full Load Efficiency (COPSHC) c,d,e,f,g, W/W, Entering/Leaving Heating Liquid Temperature, Boost, 120 F/140 FTest Procedure
> 11.25 h and < 15044i> 8.33> 6.41> 4.42NAjAHRI 550/590
> 11.25 h and < 15065 iNAjNAjNAj> 6.150AHRI 550/590
> 150 and < 30044i> 8.33> 6.41> 4.42NAjAHRI 550/590
> 150 and < 30065 iNAjNAjNAj> 6.150AHRI 550/590
> 300 and < 40044i> 8.33> 6.41> 4.42NAjAHRI 550/590
> 300 and < 40065 iNAjNAjNAj> 6.150AHRI 550/590
> 400 and < 60044i> 8.9> 6.98> 5NAjAHRI 550/590
> 400 and < 60065 iNAjNAjNAj> 6.85AHRI 550/590
> 60044i> 8.9> 6.98> 5NAjAHRI 550/590
> 60065 iNAjNAjNAj> 6.85AHRI 550/590

p.193TABLE 110.2-L Heat Pump and Heat Recovery Chiller Packages, Heat Recovery, Heating Operation– Minimum Efficiency Requirements Equipment Type: Air Source

p.195a. The size category is the full-load net refrigeration cooling mode capacity, which is the capacity of the evaporator available for cooling of the thermal load

Heat Pump and Heat Recovery Chiller Packages, Heat Recovery, Heating Operation– Minimum Efficiency RequirementsEquipment Type: Air Source p.193 Download CSV
Size Category Refrigerating Capacitya, TonRHeating Source Conditions (leaving liquid) or OAT (db/wb)b, FHeat Recovery Heating Full Load Efficiency (COPSHC) c,d,e,f,g, W/W, Entering/Leaving Heating Liquid Temperature, Low, 95 F/105 FHeat Recovery Heating Full Load Efficiency (COPSHC) c,d,e,f,g, W/W, Entering/Leaving Heating Liquid Temperature, Medium, 105 F/120 FHeat Recovery Heating Full Load Efficiency (COPSHC) c,d,e,f,g, W/W, Entering/Leaving Heating Liquid Temperature, High, 120 F/140 FHeat Recovery Heating Full Load Efficiency (COPSHC) c,d,e,f,g, W/W, Entering/Leaving Heating Liquid Temperature, Boost, 120 F/140 FTest Procedure
< 15047 db 43 wbNAjNAjNAjNAjAHRI 550/590
< 15017 db 15 wbNAjNAjNAjNAjAHRI 550/590
> 15047 db 43 wbNAjNAjNAjNAjAHRI 550/590
> 15017 db 15 wbNAjNAjNAjNAjAHRI 550/590
Size Category Refrigerating Capacitya, TonRHeating Source Conditions (leaving liquid) or OAT (db/wb)b, FHeat Recovery Heating Full Load Efficiency (COPSHC) c,d,e,f,g, W/W, Entering/Leaving Heating Liquid Temperature, Low, 95 F/105 FHeat Recovery Heating Full Load Efficiency (COPSHC) c,d,e,f,g, W/W, Entering/Leaving Heating Liquid Temperature, Medium, 105 F/120 FHeat Recovery Heating Full Load Efficiency (COPSHC) c,d,e,f,g, W/W, Entering/Leaving Heating Liquid Temperature, High, 120 F/140 FHeat Recovery Heating Full Load Efficiency (COPSHC) c,d,e,f,g, W/W, Entering/Leaving Heating Liquid Temperature, Boost, 120 F/140 FTest Procedure
> 11.25h and < 15044i> 8.33> 6.41> 4.862> 4.42AHRI 550/590
> 11.25 h and < 15065 iNAjNAjNAjNAjAHRI 550/590
> 150 and < 30044i> 8.33> 6.41> 4.862> 4.42AHRI 550/590
> 150 and < 30065 iNAjNAjNAjNAjAHRI 550/590
> 300 and < 40044i> 8.33> 6.41> 4.862> 4.42AHRI 550/590
> 300 and < 40065 iNAjNAjNAjNAjAHRI 550/590
> 400 and < 60044i> 8.9> 6.98> 5.5> 5AHRI 550/590
> 400 and < 60065 iNAjNAjNAjNAjAHRI 550/590
> 60044i> 8.9> 6.98> 5.5> 5AHRI 550/590
> 60065 iNAjNAjNAjNAjAHRI 550/590
Size Category Refrigerating Capacitya, TonRHeating Source Conditions (leaving liquid) or OAT (db/wb)b, FHeat Recovery Heating Full Load Efficiency (COPSHC) c,d,e,f,g, W/W, Entering/Leaving Heating Liquid Temperature, Low, 95 F/105 FHeat Recovery Heating Full Load Efficiency (COPSHC) c,d,e,f,g, W/W, Entering/Leaving Heating Liquid Temperature, Medium, 105 F/120 FHeat Recovery Heating Full Load Efficiency (COPSHC) c,d,e,f,g, W/W, Entering/Leaving Heating Liquid Temperature, High, 120 F/140 FHeat Recovery Heating Full Load Efficiency (COPSHC) c,d,e,f,g, W/W, Entering/Leaving Heating Liquid Temperature, Boost, 120 F/140 FTest Procedure
> 11.25 h and < 15044i> 8.33> 6.41> 4.862> 4.42AHRI 550/590
> 11.25 h and < 15065 iNAjNAjNAjNAjAHRI 550/590
> 150 and < 30044i> 8.33> 6.41> 4.862> 4.42AHRI 550/590
> 150 and < 30065 iNAjNAjNAjNAjAHRI 550/590
> 300 and < 40044i> 8.33> 6.41> 4.862> 4.42AHRI 550/590
> 300 and < 40065 iNAjNAjNAjNAjAHRI 550/590
> 400 and < 60044i> 8.9> 6.98> 5.5> 5AHRI 550/590
> 400 and < 60065 iNAjNAjNAjNAjAHRI 550/590
> 60044i> 8.9> 6.98> 5.5> 5AHRI 550/590
> 60065 iNAjNAjNAjNAjAHRI 550/590

p.192a. The size category is the full-load net refrigeration cooling mode capacity, which is the capacity of the evaporator available for cooling of the thermal

p.195external to the chilling package. b. For air source heat pumps, compliance with both the 47 F and 17 F heating source outdoor air temperature (OAT) rating efficiency is required for heating. Heating full load rating conditions are at standard rating conditions defined in AHRI 550/590 (I-P), Table 4, which includes the impact of defrost for air source heating ratings. d. For units that operate in both cooling and heating, compliance with both the cooling and heating efficiency is required. e. For heat recovery heating chilling package applications where there is simultaneous cooling and heating, compliance with the heating performance heat

p.192load external to the chilling package. b. For air source heat pumps, compliance with both the 47 F and 17 F heating source outdoor air temperature (OAT) rating efficiency is required for

p.192heating. c. Heating full load rating conditions are at standard rating conditions defined in AHRI 550/590 (I-P), Table 4, which includes the impact of defrost for air source heating ratings. d. For units that operate in both cooling and heating, compliance with both the cooling and heating efficiency is required. e. For heat recovery heating chilling package applications where there is simultaneous cooling and heating, compliance with the heating performance

p.195recover COPHR is only required at one of the four heating AHRI 550/590 (I-P) standard ratings conditions of Low, Medium, Hot-Water 1 or Hot-Water 2. Compliance with the cooling only performance is required as defined in footnotes b and c of Table 110.2-I. f. For liquid source heat recovery chilling packages that have capabilities for heat rejection to a heat recovery condenser and a tower condenser the COPHR applies to operation at full load with 100 percent heat recovery (no tower rejection). Units that only have capabilities for partial heat recovery shall meet the requirements of Table 110.2-D Water Chilling Packages Minimum Efficiency. g. For heat recovery heating chilling package applications where there is simultaneous cooling and heating, compliance with the heating performance heat recover COPHR is only required at one of the four heating AHRI 550/590 (I-P) standard ratings conditions of Low, Medium, Hot-Water 1 or Hot-Water 2. Compliance with the cooling only performance is required as defined in footnotes b and c of Table 110.2-I. h. Water to water heat pumps with a capacity less than 135,000 Btu/h are included in Table 110.2-B Heat Pumps, Minimum Efficiency Requirements. i. Source leaving liquid temperature.

p.192heat recover COPHR is only required at one of the four heating AHRI 550/590 (I-P) standard ratings conditions of Low, Medium, Hot-Water 1 or Hot- Water 2. Compliance with the cooling only performance is required as defined in footnotes b and c of Table 110.2-I. f. Heating full load rating conditions are at standard rating conditions defined in AHRI 550/590 (I-P), Table 4, which includes the impact of defrost for air source heating ratings. g. For simultaneous cooling and heating chillers applications where there is simultaneous cooling and heating, compliance with the simultaneous cooling performance heat recovery COPSHC is only required at one of the heating AHRI 550/590 (I-P) standard ratings conditions of Low, Medium, High, or Boost. Compliance with cooling performance is required as defined in footnotes b and c of Table 110.2-I. h. Water to water heat pumps with a capacity less than 135,000 Btu/h are included in Table 110.2-B Heat Pumps, Minimum Efficiency Requirements. i. Source leaving liquid temperature.p.193

p.1951. The cooling evaporator liquid flow rate used for the heating rating for a reverse cycle air to water heat pump shall be the flow rate determined during the full load cooling rating.p.196

p.192SECTION 110.2 – MANDATORY REQUIREMENTS FOR SPACE-CONDITIONING EQUIPMENT

p.193SECTION 110.2 – MANDATORY REQUIREMENTS FOR SPACE-CONDITIONING EQUIPMENT

p.194SECTION 110.2 – MANDATORY REQUIREMENTS FOR SPACE-CONDITIONING EQUIPMENT

p.195SECTION 110.2 – MANDATORY REQUIREMENTS FOR SPACE-CONDITIONING EQUIPMENT

p.196SECTION 110.2 – MANDATORY REQUIREMENTS FOR SPACE-CONDITIONING EQUIPMENT