p.192(CONTINUED) TABLE 110.2-K Heat Pump and Heat Recovery Chiller Packages, Simultaneous Cooling and Heating, Heating Operation– Minimum Efficiency
p.1931. The cooling evaporator liquid flow rate used for the heating rating for a reverse cycle air to water heat pump shall be the flow rate determined during the full load cooling rating. 2. The cooling evaporator liquid flow rate for the simultaneous cooling and heating and heat recovery liquid cooled chilling packages rating shall be the liquid flow rates from the cooling operation full load rating. 3. For heating only fluid to fluid chiller packages, the evaporator flow rate obtained with an entering liquid temperature of 54 F and a leaving liquid temperature of 44 F shall be used. j. NA means the requirements are not applicable.
p.194(CONTINUED) TABLE 110.2-L Heat Pump and Heat Recovery Chiller Packages, Heat Recovery, Heating Operation– Minimum Efficiency Requirements Equipment Type: Liquid source electrically operated positive displacement
p.195(CONTINUED) TABLE 110.2-L Heat Pump and Heat Recovery Chiller Packages, Heat Recovery, Heating Operation– Minimum Efficiency Requirements Equipment Type: Liquid source electrically operated centrifugal
p.1962. The cooling evaporator liquid flow rate for the simultaneous cooling and heating and heat recovery liquid cooled chilling packages rating shall be the liquid flow rates from the cooling operation full load rating. 3. For heating only fluid to fluid chiller packages, the evaporator flow rate obtained with an entering liquid temperature of 54 F and a leaving liquid temperature of 44 F shall be used. j. NA means the requirements are not applicable.
p.192Requirements
p.194Heat Recovery Heating
p.194Heat Recovery Heating
p.194Heat Recovery Heating
p.194Heat Recovery Heating
p.195Heat Recovery Heating
p.195Heat Recovery Heating
p.195Heat Recovery Heating
p.195Heat Recovery Heating
p.192Equipment Type: Liquid source electrically operated centrifugal
| Size Category Refrigerating Capacitya, TonR | Heating Source Conditions (leaving liquid) or OAT (db/wb)b, F | Simultaneous Cooling and Heating Full Load Efficiency (COPSHC) c,d,e,f,g, W/W, Entering/Leaving Heating Liquid Temperature, Low, 95 F/105 F | Simultaneous Cooling and Heating Full Load Efficiency (COPSHC) c,d,e,f,g, W/W, Entering/Leaving Heating Liquid Temperature, Medium, 105 F/120 F | Simultaneous Cooling and Heating Full Load Efficiency (COPSHC) c,d,e,f,g, W/W, Entering/Leaving Heating Liquid Temperature, High, 120 F/140 F | Simultaneous Cooling and Heating Full Load Efficiency (COPSHC) c,d,e,f,g, W/W, Entering/Leaving Heating Liquid Temperature, Boost, 120 F/140 F | Test Procedure |
|---|---|---|---|---|---|---|
| Size Category Refrigerating Capacitya, TonR | Heating Source Conditions (leaving liquid) or OAT (db/wb)b, F | Simultaneous Cooling and Heating Full Load Efficiency (COPSHC) c,d,e,f,g, W/W, Entering/Leaving Heating Liquid Temperature, Low, 95 F/105 F | Simultaneous Cooling and Heating Full Load Efficiency (COPSHC) c,d,e,f,g, W/W, Entering/Leaving Heating Liquid Temperature, Medium, 105 F/120 F | Simultaneous Cooling and Heating Full Load Efficiency (COPSHC) c,d,e,f,g, W/W, Entering/Leaving Heating Liquid Temperature, High, 120 F/140 F | Simultaneous Cooling and Heating Full Load Efficiency (COPSHC) c,d,e,f,g, W/W, Entering/Leaving Heating Liquid Temperature, Boost, 120 F/140 F | Test Procedure |
| > 11.25 h and < 150 | 44i | > 8.33 | > 6.41 | > 4.42 | NAj | AHRI 550/590 |
| > 11.25 h and < 150 | 65 i | NAj | NAj | NAj | > 6.150 | AHRI 550/590 |
| > 150 and < 300 | 44i | > 8.33 | > 6.41 | > 4.42 | NAj | AHRI 550/590 |
| > 150 and < 300 | 65 i | NAj | NAj | NAj | > 6.150 | AHRI 550/590 |
| > 300 and < 400 | 44i | > 8.33 | > 6.41 | > 4.42 | NAj | AHRI 550/590 |
| > 300 and < 400 | 65 i | NAj | NAj | NAj | > 6.150 | AHRI 550/590 |
| > 400 and < 600 | 44i | > 8.9 | > 6.98 | > 5 | NAj | AHRI 550/590 |
| > 400 and < 600 | 65 i | NAj | NAj | NAj | > 6.85 | AHRI 550/590 |
| > 600 | 44i | > 8.9 | > 6.98 | > 5 | NAj | AHRI 550/590 |
| > 600 | 65 i | NAj | NAj | NAj | > 6.85 | AHRI 550/590 |
p.193TABLE 110.2-L Heat Pump and Heat Recovery Chiller Packages, Heat Recovery, Heating Operation– Minimum Efficiency Requirements Equipment Type: Air Source
p.195a. The size category is the full-load net refrigeration cooling mode capacity, which is the capacity of the evaporator available for cooling of the thermal load
| Size Category Refrigerating Capacitya, TonR | Heating Source Conditions (leaving liquid) or OAT (db/wb)b, F | Heat Recovery Heating Full Load Efficiency (COPSHC) c,d,e,f,g, W/W, Entering/Leaving Heating Liquid Temperature, Low, 95 F/105 F | Heat Recovery Heating Full Load Efficiency (COPSHC) c,d,e,f,g, W/W, Entering/Leaving Heating Liquid Temperature, Medium, 105 F/120 F | Heat Recovery Heating Full Load Efficiency (COPSHC) c,d,e,f,g, W/W, Entering/Leaving Heating Liquid Temperature, High, 120 F/140 F | Heat Recovery Heating Full Load Efficiency (COPSHC) c,d,e,f,g, W/W, Entering/Leaving Heating Liquid Temperature, Boost, 120 F/140 F | Test Procedure |
|---|---|---|---|---|---|---|
| < 150 | 47 db 43 wb | NAj | NAj | NAj | NAj | AHRI 550/590 |
| < 150 | 17 db 15 wb | NAj | NAj | NAj | NAj | AHRI 550/590 |
| > 150 | 47 db 43 wb | NAj | NAj | NAj | NAj | AHRI 550/590 |
| > 150 | 17 db 15 wb | NAj | NAj | NAj | NAj | AHRI 550/590 |
| Size Category Refrigerating Capacitya, TonR | Heating Source Conditions (leaving liquid) or OAT (db/wb)b, F | Heat Recovery Heating Full Load Efficiency (COPSHC) c,d,e,f,g, W/W, Entering/Leaving Heating Liquid Temperature, Low, 95 F/105 F | Heat Recovery Heating Full Load Efficiency (COPSHC) c,d,e,f,g, W/W, Entering/Leaving Heating Liquid Temperature, Medium, 105 F/120 F | Heat Recovery Heating Full Load Efficiency (COPSHC) c,d,e,f,g, W/W, Entering/Leaving Heating Liquid Temperature, High, 120 F/140 F | Heat Recovery Heating Full Load Efficiency (COPSHC) c,d,e,f,g, W/W, Entering/Leaving Heating Liquid Temperature, Boost, 120 F/140 F | Test Procedure |
| > 11.25h and < 150 | 44i | > 8.33 | > 6.41 | > 4.862 | > 4.42 | AHRI 550/590 |
| > 11.25 h and < 150 | 65 i | NAj | NAj | NAj | NAj | AHRI 550/590 |
| > 150 and < 300 | 44i | > 8.33 | > 6.41 | > 4.862 | > 4.42 | AHRI 550/590 |
| > 150 and < 300 | 65 i | NAj | NAj | NAj | NAj | AHRI 550/590 |
| > 300 and < 400 | 44i | > 8.33 | > 6.41 | > 4.862 | > 4.42 | AHRI 550/590 |
| > 300 and < 400 | 65 i | NAj | NAj | NAj | NAj | AHRI 550/590 |
| > 400 and < 600 | 44i | > 8.9 | > 6.98 | > 5.5 | > 5 | AHRI 550/590 |
| > 400 and < 600 | 65 i | NAj | NAj | NAj | NAj | AHRI 550/590 |
| > 600 | 44i | > 8.9 | > 6.98 | > 5.5 | > 5 | AHRI 550/590 |
| > 600 | 65 i | NAj | NAj | NAj | NAj | AHRI 550/590 |
| Size Category Refrigerating Capacitya, TonR | Heating Source Conditions (leaving liquid) or OAT (db/wb)b, F | Heat Recovery Heating Full Load Efficiency (COPSHC) c,d,e,f,g, W/W, Entering/Leaving Heating Liquid Temperature, Low, 95 F/105 F | Heat Recovery Heating Full Load Efficiency (COPSHC) c,d,e,f,g, W/W, Entering/Leaving Heating Liquid Temperature, Medium, 105 F/120 F | Heat Recovery Heating Full Load Efficiency (COPSHC) c,d,e,f,g, W/W, Entering/Leaving Heating Liquid Temperature, High, 120 F/140 F | Heat Recovery Heating Full Load Efficiency (COPSHC) c,d,e,f,g, W/W, Entering/Leaving Heating Liquid Temperature, Boost, 120 F/140 F | Test Procedure |
| > 11.25 h and < 150 | 44i | > 8.33 | > 6.41 | > 4.862 | > 4.42 | AHRI 550/590 |
| > 11.25 h and < 150 | 65 i | NAj | NAj | NAj | NAj | AHRI 550/590 |
| > 150 and < 300 | 44i | > 8.33 | > 6.41 | > 4.862 | > 4.42 | AHRI 550/590 |
| > 150 and < 300 | 65 i | NAj | NAj | NAj | NAj | AHRI 550/590 |
| > 300 and < 400 | 44i | > 8.33 | > 6.41 | > 4.862 | > 4.42 | AHRI 550/590 |
| > 300 and < 400 | 65 i | NAj | NAj | NAj | NAj | AHRI 550/590 |
| > 400 and < 600 | 44i | > 8.9 | > 6.98 | > 5.5 | > 5 | AHRI 550/590 |
| > 400 and < 600 | 65 i | NAj | NAj | NAj | NAj | AHRI 550/590 |
| > 600 | 44i | > 8.9 | > 6.98 | > 5.5 | > 5 | AHRI 550/590 |
| > 600 | 65 i | NAj | NAj | NAj | NAj | AHRI 550/590 |
p.192a. The size category is the full-load net refrigeration cooling mode capacity, which is the capacity of the evaporator available for cooling of the thermal
p.195external to the chilling package. b. For air source heat pumps, compliance with both the 47 F and 17 F heating source outdoor air temperature (OAT) rating efficiency is required for heating. Heating full load rating conditions are at standard rating conditions defined in AHRI 550/590 (I-P), Table 4, which includes the impact of defrost for air source heating ratings. d. For units that operate in both cooling and heating, compliance with both the cooling and heating efficiency is required. e. For heat recovery heating chilling package applications where there is simultaneous cooling and heating, compliance with the heating performance heat
p.192load external to the chilling package. b. For air source heat pumps, compliance with both the 47 F and 17 F heating source outdoor air temperature (OAT) rating efficiency is required for
p.192heating. c. Heating full load rating conditions are at standard rating conditions defined in AHRI 550/590 (I-P), Table 4, which includes the impact of defrost for air source heating ratings. d. For units that operate in both cooling and heating, compliance with both the cooling and heating efficiency is required. e. For heat recovery heating chilling package applications where there is simultaneous cooling and heating, compliance with the heating performance
p.195recover COPHR is only required at one of the four heating AHRI 550/590 (I-P) standard ratings conditions of Low, Medium, Hot-Water 1 or Hot-Water 2. Compliance with the cooling only performance is required as defined in footnotes b and c of Table 110.2-I. f. For liquid source heat recovery chilling packages that have capabilities for heat rejection to a heat recovery condenser and a tower condenser the COPHR applies to operation at full load with 100 percent heat recovery (no tower rejection). Units that only have capabilities for partial heat recovery shall meet the requirements of Table 110.2-D Water Chilling Packages Minimum Efficiency. g. For heat recovery heating chilling package applications where there is simultaneous cooling and heating, compliance with the heating performance heat recover COPHR is only required at one of the four heating AHRI 550/590 (I-P) standard ratings conditions of Low, Medium, Hot-Water 1 or Hot-Water 2. Compliance with the cooling only performance is required as defined in footnotes b and c of Table 110.2-I. h. Water to water heat pumps with a capacity less than 135,000 Btu/h are included in Table 110.2-B Heat Pumps, Minimum Efficiency Requirements. i. Source leaving liquid temperature.
p.192heat recover COPHR is only required at one of the four heating AHRI 550/590 (I-P) standard ratings conditions of Low, Medium, Hot-Water 1 or Hot- Water 2. Compliance with the cooling only performance is required as defined in footnotes b and c of Table 110.2-I. f. Heating full load rating conditions are at standard rating conditions defined in AHRI 550/590 (I-P), Table 4, which includes the impact of defrost for air source heating ratings. g. For simultaneous cooling and heating chillers applications where there is simultaneous cooling and heating, compliance with the simultaneous cooling performance heat recovery COPSHC is only required at one of the heating AHRI 550/590 (I-P) standard ratings conditions of Low, Medium, High, or Boost. Compliance with cooling performance is required as defined in footnotes b and c of Table 110.2-I. h. Water to water heat pumps with a capacity less than 135,000 Btu/h are included in Table 110.2-B Heat Pumps, Minimum Efficiency Requirements. i. Source leaving liquid temperature.p.193
p.1951. The cooling evaporator liquid flow rate used for the heating rating for a reverse cycle air to water heat pump shall be the flow rate determined during the full load cooling rating.p.196
p.192SECTION 110.2 – MANDATORY REQUIREMENTS FOR SPACE-CONDITIONING EQUIPMENT
p.193SECTION 110.2 – MANDATORY REQUIREMENTS FOR SPACE-CONDITIONING EQUIPMENT
p.194SECTION 110.2 – MANDATORY REQUIREMENTS FOR SPACE-CONDITIONING EQUIPMENT
p.195SECTION 110.2 – MANDATORY REQUIREMENTS FOR SPACE-CONDITIONING EQUIPMENT
p.196SECTION 110.2 – MANDATORY REQUIREMENTS FOR SPACE-CONDITIONING EQUIPMENT