1. Attic roof. Roofs with an attic space shall meet the requirements of A through C below:

p.471Section 160.1 – Mandatory Requirements for Building Envelopes

p.471(a) Ceiling and roof insulation. The opaque portions of ceilings and roofs separating conditioned

p.471spaces from unconditioned spaces or ambient air shall meet the requirements of Item 1 or 2, and 3 below:

p.4711. Attic roof. Roofs with an attic space shall meet the requirements of A through C below:

p.471A. Shall be insulated to achieve an area-weighted average U-factor not exceeding U-0.043 or

p.471shall be insulated between wood-framing members with insulation resulting in an installed thermal resistance of R-22 or greater for the insulation alone. For vented attics, the mandatory insulation shall be installed at the ceiling level; for unvented attics, the mandatory insulation shall be placed at either ceiling or roof level;

p.471B. Attic access doors shall have permanently attached insulation using adhesive or mechanical

p.471fasteners. The attic access shall be gasketed to prevent air leakage; and

p.471C. When loose-fill insulation is installed, the minimum installed weight per square foot shall

p.471conform with the insulation manufacturer's installed design weight per square foot at the manufacturer's labeled R-value.

p.4712. Non-attic roof. Roofs without attic spaces shall meet the applicable requirements of A through C below:

p.471A. Metal building—The area-weighted average U-factor of the roof assembly shall not exceed

p.4710.098.

p.471B. Wood framed and others—The area-weighted average U-factor of the roof assembly shall

p.471not exceed 0.075.

p.471C. Insulation placement—When insulation is installed at the roof, fixed vents or openings to

p.471the outdoors or to unconditioned spaces shall not be installed. When the space between the ceiling and the roof is either directly or indirectly conditioned space, it shall not be considered an attic for the purposes of complying with CBC attic ventilation requirements.

p.4713. Insulation shall be installed in direct contact with a roof or ceiling that is sealed to limit infiltration and exfiltration as specified in Section 110.7, including but not limited to placing insulation either above or below the roof deck or on top of a drywall ceiling.

p.471(b) Wall insulation. Opaque portions of above grade walls separating conditioned spaces from

p.471unconditioned spaces or ambient air shall meet the following applicable requirements:

p.4711. Metal building—The area-weighted average U-factor of the wall assembly shall not exceed 0.113.

p.4712. Metal framed—The area-weighted average U-factor of the wall assembly shall not exceed 0.151.

p.471SECTION 160.1 – MANDATORY REQUIREMENTS FOR BUILDING ENVELOPES