p.4723. Wood framed and others—
p.472A. Nominal 2x4 inch framing shall have an area-weighted average U-factor of the wall
p.472assembly not exceeding 0.095.
p.472B. Nominal 2x6 inch framing shall have an area-weighted average U-factor of the wall
p.472assembly not exceeding 0.069.
p.472C. Other wall assemblies shall have an area-weighted average U-factor of the wall assembly
p.472not exceeding 0.102.
p.4724. Light mass walls—A 6 inch or greater hollow core concrete masonry unit shall have a U-factor not to exceed 0.440.
p.4725. Heavy mass walls—An 8 inch or greater hollow core concrete masonry unit shall have a U- factor not to exceed 0.690.
p.4726. Spandrel panels and curtain wall—The area-weighted average U-factor of the spandrel panels and curtain wall assembly shall not exceed 0.280.
p.4727. Demising walls—The opaque portions of framed demising walls shall meet the requirements of Item A or B below:
p.472A. Wood framed walls shall be insulated to meet a U-factor not greater than 0.099.
p.472B. Metal framed walls shall be insulated to meet a U-factor not greater than 0.151.
p.4728. Bay or bow window roofs and floors shall be insulated to meet the wall insulation requirements of Table 170.2-A.
p.472(c) Floor and soffit insulation. The opaque portions of floors and soffits that separate conditioned
p.472spaces from unconditioned spaces or ambient air shall meet the applicable requirements of Items 1 through 3 below:
p.4721. Raised mass floors shall have a minimum of 3 inches of lightweight concrete over a metal deck or the area-weighted average U-factor of the floor assembly shall not exceed 0.269.
p.4722. Raised wood floor shall have an overall assembly U-factor not exceeding 0.037. In a wood framed assembly, compliance with the U-factor may be demonstrated by installing insulation with an R-value of 19 or greater.
p.4723. Other floors—The area-weighted average U-factor of the floor assembly shall not exceed 0.071.
p.4724. Heated slab on grade floor—A heated slab on grade floor shall be insulated to meet the requirements of Section 110.8(g).
p.472A. The foundation walls are insulated to meet the wall insulation minimums as shown in Table
p.472170.2-A; and
p.472B. A Class I or Class II vapor retarder is placed over the entire floor of the crawl space; and
p.472C. Vents between the crawl space and outside air are fitted with automatically operated louvers
p.472that are temperature actuated; and
p.472SECTION 160.1 – MANDATORY REQUIREMENTS FOR BUILDING ENVELOPES