p.554TABLE 170.2-A ENVELOPE COMPONENT PACKAGE – Multifamily Standard Building Design (continued)
p.555TABLE 170.2-A ENVELOPE COMPONENT PACKAGE – Multifamily Standard Building Design (continued)
p.556If using F-factor to comply, use Reference Joint Appendices JA4, Table 4.4.7 to determine alternate depth and R-value to be less than or equal to the required maximum F- Option B meets §170.2(a)1Bii 10. Option C meets §170.2(a)1BIiii 11. Option D meets §170.2(a)1Biv
p.552a. the lower-rated labeled SHGC shall be used with automatic controls to modulate the
| Building Component - Roofs and Ceilings | CZ 1 | CZ 2 | CZ 3 | CZ 4 | CZ 5 | CZ 6 | CZ 7 | CZ 8 | CZ 9 | CZ 10 | CZ 11 | CZ 12 | CZ 13 | CZ 14 | CZ 15 | CZ 16 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Option B9 Below Roof Deck Insulation 1,2 (with air space) | NR | NR | NR | R19 | NR | NR | NR | R19 | R19 | R13 | R19 | R19 | R19 | R19 | R19 | R13 |
| Option B9 Ceiling Insulation | R 38 | R 38 | R 30 | R 38 | R 30 | R 30 | R 30 | R 38 | R 38 | R 38 | R 38 | R 38 | R 38 | R 38 | R 38 | R 38 |
| Option B9 Radiant Barrier | NR | REQ | REQ | NR | REQ | REQ | REQ | NR | NR | NR | NR | NR | NR | NR | NR | NR |
| Option B9 Low-Slope-Aged Solar Reflectance | NR | NR | NR | NR | NR | NR | NR | NR | NR | NR | NR | NR | 0.63 | NR | 0.63 | NR |
| Option B9 Low-Sloped-Thermal Emittance | NR | NR | NR | NR | NR | NR | NR | NR | NR | NR | NR | NR | 0.75 | NR | 0.75 | NR |
| Option B9 Low-Sloped-Solar Reflectance Index | NR | NR | NR | NR | NR | NR | NR | NR | NR | NR | NR | NR | 75 | NR | 75 | NR |
| Option B9 Steep-Sloped-Aged Solar Reflectance | NR | NR | NR | NR | NR | NR | NR | NR | NR | 0.25 | 0.25 | 0.20 | 0.25 | 0.20 | 0.25 | NR |
| Option B9 Steep-Sloped-Thermal Emittance | NR | NR | NR | NR | NR | NR | NR | NR | NR | 0. 75 | 0.75 | 0.75 | 0.75 | 0.75 | 0.75 | NR |
| Option B9 Steep-Sloped-Solar Reflectance Index | NR | NR | NR | NR | NR | NR | NR | NR | NR | 23 | 23 | 16 | 23 | 16 | 23 | NR |
| Option C10-Ceiling Insulation | R 38 | R 30 | R 30 | R 30 | R 30 | R 30 | R 30 | R 30 | R 30 | R 30 | R 38 | R 38 | R 38 | R 38 | R 38 | R 38 |
| Option C10-Radiant Barrier | NR | REQ | REQ | REQ | REQ | REQ | REQ | REQ | REQ | REQ | REQ | REQ | REQ | REQ | REQ | NR |
| Option C10 Low-Sloped-Aged Solar Reflectance | NR | NR | NR | NR | NR | NR | NR | NR | NR | NR | NR | NR | 0.63 | NR | 0.63 | NR |
| Option C10 Low-Sloped-Thermal Emittance | NR | NR | NR | NR | NR | NR | NR | NR | NR | NR | NR | NR | 0.75 | NR | 0.75 | NR |
| Option C10 Low-Sloped-Solar Reflectance Index | NR | NR | NR | NR | NR | NR | NR | NR | NR | NR | NR | NR | 75 | NR | 75 | NR |
| Option C10 Steep-Sloped-Aged Solar Reflectance | NR | NR | NR | NR | NR | NR | NR | NR | NR | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | NR |
| Option C10 Steep-Sloped-Thermal Emittance | NR | NR | NR | NR | NR | NR | NR | NR | NR | 0. 75 | 0.75 | 0.75 | 0.75 | 0.75 | 0.75 | NR |
| Option C10 Steep-Sloped-Solar Reflectance Index | NR | NR | NR | NR | NR | NR | NR | NR | NR | 16 | 16 | 16 | 16 | 16 | 16 | NR |
| Option D11-Metal Building U-factor | 0.041 | 0.041 | 0.041 | 0.041 | 0.041 | 0.041 | 0.041 | 0.041 | 0.041 | 0.041 | 0.041 | 0.041 | 0.041 | 0.041 | 0.041 | 0.041 |
| Option D11-Wood Framed and Other U-factor | 0.028 | 0.028 | 0.034 | 0.028 | 0.034 | 0.034 | 0.039 | 0.028 | 0.028 | 0.028 | 0.028 | 0.028 | 0.028 | 0.028 | 0.028 | 0.028 |
| Option D11 Low-Sloped-Aged Solar Reflectance | NR | 0.63 | NR | 0.63 | NR | 0.63 | 0.63 | 0.63 | 0.63 | 0.63 | 0.63 | 0.63 | 0.63 | 0.63 | 0.63 | NR |
| Option D11 Low-Sloped-Thermal Emittance | NR | 0.75 | NR | 0.75 | NR | 0.75 | 0.75 | 0.75 | 0.75 | 0.75 | 0.75 | 0.75 | 0.75 | 0.75 | 0.75 | NR |
| Option D11 Low-Sloped-Solar Reflectance Index | NR | 75 | NR | 75 | NR | 75 | 75 | 75 | 75 | 75 | 75 | 75 | 75 | 75 | 75 | NR |
| Option D11 Steep-Sloped-Aged Solar Reflectance | NR | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | NR |
| Option D11 Steep-Sloped-Thermal Emittance | NR | 0.75 | 0.75 | 0.75 | 0.75 | 0.75 | 0.75 | 0.75 | 0.75 | 0.75 | 0.75 | 0.75 | 0.75 | 0.75 | 0.75 | NR |
| Option D Steep-Sloped-Solar Reflectance Index | NR | 16 | 16 | 16 | 16 | 16 | 16 | 16 | 16 | 16 | 16 | 16 | 16 | 16 | 16 | NR |
| Building Component - Fenestration | CZ 1 | CZ 2 | CZ 3 | CZ 4 | CZ 5 | CZ 6 | CZ 7 | CZ 8 | CZ 9 | CZ 10 | CZ 11 | CZ 12 | CZ 13 | CZ 14 | CZ 15 | CZ 16 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Curtain Wall/ Storefront7 - Maximum U-factor | 0.38 | 0.41 | 0.41 | 0.41 | 0.41 | 0.41 | 0.41 | 0.41 | 0.41 | 0.41 | 0.41 | 0.41 | 0.41 | 0.41 | 0.41 | 0.38 |
| Curtain Wall/ Storefront7 - Maximum RSHGC | NR | 0.26 | NR | 0.26 | NR | 0.26 | 0.26 | 0.26 | 0.26 | 0.26 | 0.26 | 0.26 | 0.26 | 0.25 | 0.26 | NR |
| Curtain Wall/ Storefront7 - Minimum VT, common use area | 0.46 | 0.46 | 0.46 | 0.46 | 0.46 | 0.46 | 0.46 | 0.46 | 0.46 | 0.46 | 0.46 | 0.46 | 0.46 | 0.46 | 0.46 | 0.46 |
| NAFS 2017 Performance Class AW5 - Maximum U-factor | 0.38 | 0.40 | 0.40 | 0.40 | 0.40 | 0.40 | 0.40 | 0.40 | 0.40 | 0.40 | 0.40 | 0.40 | 0.40 | 0.40 | 0.40 | 0.38 |
| NAFS 2017 Performance Class AW5 - Maximum RSHGC | NR | 0.24 | NR | 0.24 | NR | 0.24 | 0.24 | 0.24 | 0.24 | 0.24 | 0.24 | 0.24 | 0.24 | 0.24 | 0.24 | NR |
| NAFS 2017 Performance Class AW5 - Minimum VT, common use areas | 0.37 | 0.37 | 0.37 | 0.37 | 0.37 | 0.37 | 0.37 | 0.37 | 0.37 | 0.37 | 0.37 | 0.37 | 0.37 | 0.37 | 0.37 | 0.37 |
| All Other Fenestration - Maximum U- factor | 0.28 | 0.30 | 0.28 | 0.28 | 0.28 | 0.34 | 0.34 | 0.30 | 0.30 | 0.30 | 0.28 | 0.30 | 0.28 | 0.28 | 0.28 | 0.28 |
| All Other Fenestration - Maximum RSHGC | NR | 0.23 | NR | 0.23 | NR | 0.23 | 0.23 | 0.23 | 0.23 | 0.23 | 0.23 | 0.23 | 0.23 | 0.23 | 0.23 | NR |
| Maximum Window to Floor Ratio | 20% | 20% | 20% | 20% | 20% | 20% | 20% | 20% | 20% | 20% | 20% | 20% | 20% | 20% | 20% | 20% |
| Maximum Window to Wall Ratio | 40% | 40% | 40% | 40% | 40% | 40% | 40% | 40% | 40% | 40% | 40% | 40% | 40% | 40% | 40% | 40% |
| Maximum Skylight Roof Ratio | 5% | 5% | 5% | 5% | 5% | 5% | 5% | 5% | 5% | 5% | 5% | 5% | 5% | 5% | 5% | 5% |
| Building Component - Walls, Floors, Doors, and QII | CZ 1 | CZ 2 | CZ 3 | CZ 4 | CZ 5 | CZ 6 | CZ 7 | CZ 8 | CZ 9 | CZ 10 | CZ 11 | CZ 12 | CZ 13 | CZ 14 | CZ 15 | CZ 16 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Walls - Metal Building - Any Fire Rating | 0.061 | 0.061 | 0.061 | 0.061 | 0.061 | 0.061 | 0.061 | 0.061 | 0.061 | 0.061 | 0.057 | 0.057 | 0.057 | 0.057 | 0.057 | 0.057 |
| Walls - Framed (wood, metal) and other - >1hr fire rating | 0.059 | 0.059 | 0.059 | 0.059 | 0.059 | 0.065 | 0.065 | 0.059 | 0.059 | 0.059 | 0.051 | 0.059 | 0.059 | 0.051 | 0.051 | 0.051 |
| Walls - Framed (wood, metal) and other - ≤1hr fire rating3 | 0.051 | 0.051 | 0.051 | 0.051 | 0.051 | 0.065 | 0.065 | 0.051 | 0.051 | 0.051 | 0.051 | 0.051 | 0.051 | 0.051 | 0.051 | 0.051 |
| Walls - Mass Light4 | U 0.077 R 13 | U 0.077 R 13 | U 0.077 R 13 | U 0.077 R 13 | U 0.077 R 13 | U 0.077 R 13 | U 0.077 R 13 | U 0.077 R 13 | U 0.077 R 13 | U 0.077 R 13 | U 0.077 R 13 | U 0.077 R 13 | U 0.077 R 13 | U 0.077 R 13 | U 0.077 R 13 | U 0.059 R 17 |
| Walls - Mass Heavy | 0.253 | 0.650 | 0.650 | 0.650 | 0.650 | 0.690 | 0.690 | 0.690 | 0.690 | 0.650 | 0.184 | 0.253 | 0.211 | 0.184 | 0.184 | 0.160 |
| Floors/Soffits - Slab Perimeter8 | NR | NR | NR | NR | NR | NR | NR | NR | NR | NR | NR | NR | NR | NR | NR | F 0.58 R 7.0 |
| Floors/Soffits – Wood Framed | U 0.037 R 19 | U 0.037 R 19 | U 0.037 R 19 | U 0.037 R 19 | U 0.037 R 19 | U 0.037 R 19 | U 0.037 R 19 | U 0.037 R 19 | U 0.037 R 19 | U 0.037 R 19 | U 0.037 R 19 | U 0.037 R 19 | U 0.037 R 19 | U 0.037 R 19 | U 0.037 R 19 | U 0.037 R 19 |
| Floors/Soffits - Raised Mass | U 0.092 R 8.0 | U 0.092 R 8.0 | U 0.269 R 0 | U 0.269 R 0 | U-0.269 R 0 | U 0.269 R 0 | U 0.269 R 0 | U 0.269 R 0 | U 0.269 R 0 | U 0.269 R 0 | U 0.092 R 8.0 | U 0.138 R 4.0 | U 0.092 R 8.0 | U 0.092 R 8.0 | U 0.138 R 4.0 | U 0.092 R 8.0 |
| Floors/Soffits - Other | 0.048 | 0.039 | 0.071 | 0.071 | 0.071 | 0.071 | 0.071 | 0.071 | 0.071 | 0.071 | 0.039 | 0.071 | 0.071 | 0.039 | 0.039 | 0.039 |
| Exterior Doors6 - Max U- Factor Dwelling Unit Entry | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
| Exterior Doors6 - Max U-Factor Common Use Area Entry Non- Swinging | 0.50 | 1.45 | 1.45 | 1.45 | 1.45 | 1.45 | 1.45 | 1.45 | 1.45 | 1.45 | 1.45 | 1.45 | 1.45 | 1.45 | 1.45 | 0.50 |
| Exterior Doors6 - Max U-Factor Common Use Area Entry Swinging | 0.70 | 0.70 | 0.70 | 0.70 | 0.70 | 0.70 | 0.70 | 0.70 | 0.70 | 0.70 | 0.70 | 0.70 | 0.70 | 0.70 | 0.70 | 0.70 |
| Quality Insulation Installation up to 3 habitable stories | Yes | Yes | Yes | Yes | Yes | Yes | NR | Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes |
p.552amount of heat flow into the space in multiple steps in response to daylight levels or solar intensity; and
p.552b. chromogenic glazing shall be considered separately from other glazing; and
p.552c. area-weighted averaging with other glazing that is not chromogenic shall not be
p.552permitted.
p.552iv. Haze value. Have a glazing material or diffuser that has a measured haze value greater
p.552than 90 percent, determined according to ASTM D1003 or other test method approved by the Energy Commission.
p.5524. All exterior doors, excluding glazed doors, that separate conditioned space from unconditioned space or from ambient air shall have a U-factor not greater than the applicable value in Table 170.2-A. Glazed doors must comply with the requirements of Section 170.2(a)3A.
p.554Common Use Area Entry Non-
p.5525. Floors shall meet the following requirements:
p.552A. Raised floors shall be insulated such that the floor assembly has an assembly U-factor equal
p.552to or less than shown in Table 170.2-A, or shall be insulated between wood framing with insulation having an R-value equal to or greater than shown in Table 170.2-A.
p.555Footnote requirements to TABLE 170.2-A:
p.552B. Slab floors shall have perimeter insulation installed with an F-factor equal to or less than or
p.555Install the specified R-value with an air space present between the roofing and the roof deck. Such as standard installation of concrete or clay tile. R-values shown for below roof deck insulation are for wood-frame construction with insulation installed between the framing members. Alternatives including insulation above rafters or above roof deck shall comply with the performance standards. Assembly U-factors for exterior framed walls can be met with cavity insulation alone or with continuous insulation alone, or with both cavity and continuous insulation that results in an assembly U-factor equal to or less than the U-factor shown. Use Reference Joint Appendices JA4 Table 4.3.1, 4.3.1(a), or Table 4.3.4 to determine alternative insulation products to be less than or equal to the required maximum U-factor. Mass wall has a heat capacity greater than or equal to 7.0 Btu/h-ft2. Product must be certified to meet the North American Fenestration Standard/Specification for an Architectural Window (AW). Glazed doors must meet the fenestration requirements. Requirements apply to doors included in the Curtainwall/Storefront construction assembly.p.556
p.552R-value equal to or greater than shown in Table 170.2-A. The minimum depth of concrete slab floor perimeter insulation shall be 16 inches or the depth of the footing of the building, whichever is less.
p.5526. All buildings up to three habitable stories shall comply with the quality insulation installation (QII) requirements shown in Table 170.2-A. When QII is required, insulation installation shall meet the criteria specified in Reference Appendix RA3.5.
p.553SECTION 170.2 – PRESCRIPTIVE APPROACH
p.554SECTION 170.2 – PRESCRIPTIVE APPROACH
p.555SECTION 170.2 – PRESCRIPTIVE APPROACH