RA3.1.1 Purpose and Scope

p.3232025 Residential Appendices

Figure on PDF page 323
Text in this figure

Residential Appendix RA3

p.323 Needs alt text review

p.323Appendix RA3 – Residential Field Verification and Diagnostic Test Protocols

p.323RA3.1 Field Verification and Diagnostic Testing of Air Distribution Systems

p.323RA3.1.1 Purpose and Scope

p.323RA3.1 contains procedures for measuring the air leakage in forced air distribution systems as well as procedures for verifying duct location, duct surface area, duct R-value, return duct design, return grille design, and air filter installation.

p.323RA3.1 applies to air distribution systems in both new and existing single-family and multifamily residential buildings.

p.323RA3.1 provides required procedures for installers, ECC-raters and others who are required to perform field verification of air distribution systems.

p.323Table RA3.1-1 is a summary of the tests and criteria included in RA3.1.

p.323Table RA3.1-2 Provides compliance criteria for the duct leakage test protocols in Section RA3.1.4.3.

p.323Appendix RA3– Residential Field Verification and Diagnostic Test Protocols