NA5.5.2 Depressurization Test

p.5102025 Nonresidential Appendices NA5.5.2 Depressurization Test

p.5101. Reverse direction of fans.

p.5102. Measure bias pressures with fans off and covered.

p.5103. Perform a multi-point depressurization test from at least -25 to -50 Pa (optional).

p.5104. Record a minimum of 5 points between minimum and maximum induced pressures.

p.5105. Measure bias pressures at end of multi-point test with fans off and covered.

p.5106. Record interior and exterior temperatures after the testing is complete.

p.5107. If the pressure exponent n is less than 0.45 or greater than 1.0 per Section 9.5.1 of ASTM 3158-18, then the depressurization test is invalid and shall be repeated.

p.510Determination of Test Results

Figure on PDF page 510
p.510 Needs alt text review

p.5101. Calculate the building envelope air leakage in accordance with guidelines in ASTM E3158-18 multi-point regression tests or the relevant building envelope area when testing in sections.

p.5102. If the building envelope air leakage rate exceeds 0.4 cfm/ft2 but is less than 0.6 cfm/ft2, a visual inspection of the air barrier shall be conducted in accordance with NA5.7. Any leaks observed should be sealed where such sealing can be made without destruction of existing building components. An additional report identifying the corrective actions taken to seal air leaks should be submitted to the building owner and code official, and any further requirement to meet the air leakage rate will be waived.

p.5103. If the building envelope air leakage rate exceeds 0.6 cfm/ft2, a visual inspection of the air barrier shall be conducted in accordance with NA 5.7, and any leaks noted should be repaired. The building will then be re-tested until either the building envelope air leakage rate less than 0.4 cfm/ft2, or the building envelope air leakage rate is in the range of 0.4 cfm/ft2 but is less than 0.6 cfm/ft2 and a visual inspection and repair program is executed.

p.510Appendix NA45– Field Verification and Diagnostic Testing of Whole Building Air Leakage