p.3692025 Residential Appendices a. The measured value for fan Watt draw (Watt) at high fan speed shall be divided by the
p.369measured value for airflow rate (cfm) at the high fan speed to determine the fan efficacy (Watt/cfm) for the CFVCS at high fan speed.
p.369b. The measured value for fan Watt draw (Watt) at the ventilation fan speed shall be divided
p.369by the measured value for airflow rate (cfm) at the ventilation fan speed to determine the fan efficacy (Watt/cfm) for the CFVCS at ventilation fan speed.
p.369RA3.3.4.4 Determining Compliance with Fan Efficacy and System Airflow Requirements
p.369Compliance with the requirements for airflow rate and fan efficacy require that the Watt draw and airflow rate measurements are made simultaneously at both high speed and ventilation speed. The simultaneous measurements shall be used to calculate the following values used to determine compliance:
p.369RA3.3.4.4.1 Fan Efficacy Calculation (Watt/cfm)
p.369The measured value for fan Watt draw (Watt) shall be divided by the measured value for airflow rate (cfm) to determine the fan efficacy (Watt/cfm).
p.369RA3.3.4.5 Compliance Criteria
p.369In order for the CFVCS to comply, the requirements in both subsections a and b below shall be met:
p.369a. The system airflow (cfm/ton) shall meet or exceed the system airflow compliance criteria
p.369specified on the Certificate of Compliance at both the high fan speed, and the ventilation fan speed.
p.369b. The calculated value for fan efficacy (Watt/cfm) shall be equal to or less than the fan
p.369efficacy compliance criterion specified on the Certificate of Compliance at both the high fan speed, and the ventilation fan speed.
p.369RA3.4 Field Verification of Installed HVAC System Components and Devices
p.369RA3.4.1 Purpose and Scope
p.369The purpose of these procedures is to verify that residential space cooling systems and heat pumps have the required components to achieve the energy efficiency claimed in the compliance documents. The procedures apply when a Fault Indicator Display (FID) is specified for split system equipment, or when an HSPF2, SEER2, or EER2 higher than the default is claimed. For dwelling units with multiple systems, the procedures shall be applied to each system separately.
p.369The installer shall certify on the Certificate of Installation that the components required for compliance have been installed.
p.369Appendix RA3– Residential Field Verification and Diagnostic Test Protocols