| Table RA2-2 – (Continued) Air Conditioning | Summary of Measures Requiring Field Verification and Diagnostic Testing Measures | |||
| Measure Title | Description | Procedure(s) | ||
| Charge Improved Refrigerant | Component Packages require in some climate zones that air-cooled air conditioners and air-source heat pumps be diagnostically tested in the field to verify that the system has the correct refrigerant charge. For the performance method, the Proposed Design is modeled with less efficiency if diagnostic testing and field verification is not performed. The system must also meet the prerequisite minimum System Airflow requirement. | RA3.3 RA3.2 RA1.2 | ||
| Airflow Verified System | When compliance requires verified system airflow greater than or equal to a specified criterion, field verification and diagnostic testing is required. | RA3.3 | ||
| Fan Air-handling Unit Efficacy | When compliance requires verified fan efficacy (Watt/cfm) less than or equal to a specified criterion, field verification and diagnostic testing is required. | RA3.3 | ||
| (EER2) Verified Energy Efficiency Ratio | Compliance credit can be taken for increased EER2 by installation of specific air conditioner or heat pump models. Field verification is required.2 | RA3.4.3 RA3.4.4.1 | ||
| Energy Ratio Verified Seasonal Efficiency (SEER2) | ECC-Rater field verification of the SEER2 rating is required for some systems. | RA3.4.3 RA3.4.4.1 | ||
| Rated Heat Pump Capacity Verification | When performance compliance uses a heat pump, the rated capacity of the installed system shall be verified to be greater than or equal to the specified value. | RA3.4.4.2 | ||
| Cooled Evaporatively Condensers | Compliance credit can be taken for installation of evaporatively cooled condensers. Field verification of duct leakage is required. Field verification of refrigerant charge is required. Field verification of EER2 is required. This measure is only applicable to single-family buildings. | RA3.1.4.3, RA3.2 RA3.4.3. RA3.4.4.1 | ||
| Heat (VCHP) Option Variable Capacity Pump Compliance | When performance compliance uses the VCHP compliance option, the system shall be field verified to confirm it meets the eligibility requirements. | RA3.4.4.3 | ||
| Table RA2-3 – (Continued) Ventilation | Summary of Measures Requiring Field Verification and Diagnostic Testing Cooling Measures | |||
| Measure Title | Description | Procedure(s) | ||
| Whole | House Fan | When performance compliance uses a whole house fan, the installed whole house fan airflow rate (cfm) and fan efficacy (W/cfm) shall be verified to be equal to or better than the specified values. This measure is only applicable to single-family buildings. | RA3.9 |
| Measure Title | Description | Procedure(s) | |||
|---|---|---|---|---|---|
| Central Fan Ventilation Cooling System | When performance system (CFVCS), fan efficacy specified values. buildings. | compliance uses a central fan ventilation cooling the installed CFVCS ventilation airflow rate (cfm) and (W/cfm) shall be verified to be equal to or better than the This measure is applicable only to single-family | RA3.3.4 | ||
| Table RA2-4 – (Continued) Mechanical | Summary of Ventilation Measures | Measures Requiring Field Verification and Diagnostic Testing for Improved Indoor Air Quality | |||
| Measure Title | Description | Procedure(s) | |||
| Continuous Mechanical Ventilation Whole-Building Airflow | Measurement of whole-building mechanical ventilation is mandatory for newly constructed buildings. | RA3.7.4.1 | |||
| Intermittent Mechanical Ventilation Whole-Building Airflow | Measurement of whole-building mechanical ventilation is mandatory for newly constructed buildings. | RA3.7.4.2 | |||
| Kitchen Local Exhaust Verification Mechanical | Verification of kitchen local mechanical exhaust is mandatory for newly constructed buildings. | RA3.7.4.3 | |||
| Heat or (ERV) Recovery Energy Recovery Rated Verification Ventilation (HRV) Ventilation Performance | When performance compliance requires verification of the HRV/ERV fan efficacy (W/cfm) or heat recovery efficiency, then the installed ventilation system shall be verified. | RA3.7.4.4 | |||
p.296Table RA2-1 describes the measures that require installer certification and field verification and diagnostic testing, and identifies the protocol or test procedure in the Reference Residential Appendices that shall be used for completing installer and ECC-Rater field verification and
p.299Building Envelope Air Leakage and Dwelling Unit Compartmentalization
p.299Compliance credit can be taken for reduced building envelope air leakage in single-family homes. Field verification and diagnostic testing is required. Compliance with the enclosure leakage criteria specified in the Certificate of Compliance shall be verified for all multifamily dwelling units equipped with balanced or supply
| Measure Title | Description | Procedure(s) | ||
|---|---|---|---|---|
| Duct | Sealing | Component Packages require that space conditioning ducts be sealed. If sealed and tested ducts are claimed for compliance, field verification and diagnostic testing is required to verify that approved duct system materials are utilized, and that duct leakage meets the specified criteria. | RA3.1.4.3 | |
| Duct Location, Surface Area and R-value | Compliance credit can be taken for improved duct location, surface area and R-value. Field verification is required to verify that the duct system was installed according to the design, including location, size and length of ducts, duct insulation R-value and installation of buried ducts.1 For buried ducts measures, Duct Sealing and High Quality Insulation Installation (QII) is required. | RA3.1.4.1 | ||
| low in space Verification of leakage ducts located entirely conditioned | Duct system location shall be verified by visual inspection and diagnostic testing. Compliance credit can be taken for verified duct systems with low air leakage to the outside when measured in accordance with Reference Residential Appendix Section RA3.1.4.3.8. Field Verification for ducts in conditioned space is required. Duct sealing is required. | RA3.1.4.3.8 | ||
| Low Units Leakage Air-handling | Compliance credit can be taken for installation of a factory sealed air handling unit tested by the manufacturer and certified to the Commission to have met the requirements for a Low Leakage Air- Handling Unit. Field verification of the air handler’s model number is required. Duct Sealing is required. | RA3.1.4.3.9 | ||
| Return Design Verification of Duct | Verification to confirm that the return duct design conforms to the applicable criteria given in TABLE 150.0-B, TABLE 150.0-C, TABLE 160.3 A, or TABLE 160.3-B. | RA3.1.4.4 | ||
| Filter Design Verification of Air Device | Verification to confirm that the air filter devices conform to the requirements given in applicable Standards Sections 150.0(m) 12 or 160.2(b) 1. | RA3.1.4.5 | ||
| Bypass Verification of Prescriptive Duct Requirements | Verification to confirm zonally controlled systems comply with the bypass duct requirements in Section 150.1(c) 13 or 170.2(c) 3C. | RA3.1.4.6 | ||
p.299Compliance Software recognizes standard and improved envelope construction. Quality Insulation Installation is a prescriptive measure in all climate zones for newly constructed buildings and additions greater than 700 square feet, except low-rise multifamily buildings in Climate Zone 7. Field verification is required.
p.299Installation for Spray Polyurethane Foam (SPF)
p.299ECC-Rater shall verify the installation of SPF insulation whenever R- values other than the default R-value per inch are used for
p.299Table RA2-6 – Summary of Measures Requiring Field Verification and Diagnostic Testing Single Family Domestic Hot Water Measures
p.299Verified Pipe Insulation for Single Dwelling
p.299Inspection to verify that all hot water piping in non- recirculating systems is insulated and that corners and tees are fully insulated. No piping should be visible due to insulation voids with the exception of the last segment of piping that penetrate walls and delivers hot water to the sink, appliance, etc.
p.299Verified Parallel Piping (PP-H) Inspection that requires that the measured length of piping
p.299between the water heater and single central manifold does not exceed five feet
p.299Verified Compact Hot Water Distribution System Expanded Credit (CHWDS-H-EX)
p.299Inspection to verify that the eligibility criteria specified in RA 3.6.5 are met.
p.299Demand Recirculation: Manual Control (RDRmc-H)
p.299Inspection to verify that all recirculating hot water piping is insulated, and that corners and tees are fully insulated. No piping should be visible due to insulation voids
p.299Demand Recirculation: Sensor Control (RDRsc-H)
p.299Inspection to verify that all recirculating hot water piping is insulated, and that corners and tees are fully insulated. No piping should be visible due to insulation voids.
p.296Appendix RA2– Residential Field Verification and Diagnostic Testing Documentation Proceduresp.297
p.297Appendix RA2– Residential Field Verification and Diagnostic Testing Documentation Proceduresp.298
p.298Appendix RA2– Residential Field Verification and Diagnostic Testing Documentation Proceduresp.299
p.299Appendix RA2– Residential Field Verification and Diagnostic Testing Documentation Procedures