JA11.5.1 Remote Monitoring Capability

p.256Solar Assessment Tool

Figure on PDF page 256
p.256 Needs alt text review

p.256JA11.5 System Monitoring Requirements

p.256JA11.5.1 Remote Monitoring Capability

p.256The PV system shall have a web-based portal and a mobile device application that at a minimum provide the building owner, manager, or dwelling occupants access to the following information:

p.256(a) The nominal kW rating of the PV system.

p.256(b) Number of PV modules and the nominal watt rating of each module.

p.256(c) Hourly (or 15-minute interval), daily, monthly, and annual kWh production in

p.256numeric and graphic formats.

p.256(d) Running total of daily kWh production.

p.256(e) Daily kW peak power production.

p.256(f) Current kW production of the entire PV system.

p.256JA11.6 Interconnection Requirements

p.256The installed inverters shall be tested in accordance with the applicable requirements in UL1741 and UL1741 Supplement A. The PV system and the associated components, including inverters, shall comply with all applicable requirements specified in Rule 21 as adopted by the California Public Utilities Commission (CPUC).

p.256Appendix JA11 – Qualification Requirements for Photovoltaic System