p.5142025 Nonresidential Appendices meet residential energy compliance. If unable to acquire center of glass (COG) thermal performance values from the manufacturer, then the Energy Commissions Default Tables shall be used; Table 110.6-A for U-factors and Table 110.6-B for SHGC values and documented on the on a self-produced manufactured default label. The default label shall be attached to the unrated fenestration product. An example of the label can be found in the Residential Compliance Manual.
p.514(c) DOCUMENTATION
p.5141. The Energy Commission's Fenestration Label Certificate form for nonresidential application shall be used to document the Alternate Default Fenestration calculated values for each non-rated site-built fenestration unit; or
p.5142. For residential, a manufactured Default Label attached to each non-rated site- built fenestration unit.
p.514The equations listed below are to be used for only for unrated site-built fenestration that meets the requirements in either item 1 or 2 above.
p.514Default U-factor
Equation text: UT= C1 + (C2 X Uc)
Needs visual review
p.514UT = U-factor Is the Total Performance of the fenestration including glass and frame
p.514C1 = Coefficient selected from Table NA6-6
p.514C2 = Coefficient selected from Table NA6-6
p.514UC = Center of glass U-factor calculated in accordance with NFRC 100 Section 4.5.3.1 (http://www.nfrc.org/software.aspx)
p.514Appendix NA6– Alternate Default Fenestration Procedure to Calculate Thermal Performance