NA7.18.1.1.1 Construction Inspection

p.6002025 Nonresidential Appendices 2. If equipped, while the sash is closing, trigger the stop button, verify the sash stops immediately when the stop button is activated.

p.600c) Confirm that the sash object detection controls are operational. Verify and

p.600document the following:

p.6001. Open the sash to its maximum position or sash stop, whichever is lower.

p.6002. Place a transparent object in the pathway of the sash and simulate an unoccupied state by vacating the zone presence sensor range. Verify that the sash does not close automatically on the object within the closing time delay setting (maximum of 5 minutes).

p.6003. Open the sash to its maximum position or sash stop, whichever is lower, without any obstructions in the path of the sash.

p.6004. Simulate an unoccupied state by vacating the zone presence sensor range. When the sash begins to automatically close, insert a transparent object into the path of the sash and verify that the sash stops before contacting the object.

p.600d) Confirm that net downward force is not more than 10 pounds when closing. Verify

p.600and document the following:

p.6001. Disable object detection controls.

p.6002. Place scale in sash opening of fume hood.

p.6003. Close sash manually.

p.6004. Sash closing force shall not exceed 10 pounds as measured by scale.

p.6005. Repeat test with sash closing initiated by vacancy being detected by presence sensor.

p.600Multifamily Building Acceptance Tests

Figure on PDF page 600
p.600 Needs alt text review

p.600NA7.18.1 Dwelling Unit Ventilation System Acceptance

p.600NA7.18.1.1 Dwelling Unit Ventilation Acceptance

p.600NA7.18.1.1.1Construction Inspection

p.600Prior to functional testing, verify and document the following:

p.600a) System is designed to provide the required outside air when the unit is operating.

p.600b) Specify the ventilation system type, such as balanced, supply or exhaust.

p.600c) Specify the method of control.

p.600d) Confirm the kitchen range hood is ventilated to outside.

p.600e) Record the kitchen range hood manufacturer name and equipment model number.

p.600f) Confirm the kitchen range hood is HVI certified to perform in compliance.

p.600g) Confirm HRV or ERV equipment is HVI certified to perform in compliance.

p.600Appendix NA7 – Installation and Acceptance Requirements for Nonresidential Buildings and Covered Processes