p.5922025 Nonresidential Appendices Escalator and Moving Walkway Speed Control
p.592NA7.15.1 Construction Inspection
p.592Verify and document the following prior to functional testing:
p.592a) Variable speed drive is installed on the escalator.
p.592b) Occupancy sensor has been located to minimize false signals.
p.592c) Occupancy sensors do not trigger from pedestrians on adjacent escalators.
p.592d) Occupancy sensors do not encounter any obstructions that could adversely affect
p.592desired performance.
p.592e) Ultrasonic occupancy sensors do not emit audible sound.
p.592NA7.15.2 Functional Testing
p.592For each escalator or moving walkway being tested, confirm the following:
p.592a) Verify the amount of time necessary to ride the entire length of the escalator while
p.592standing still.
p.592b) Stand away from the escalator. After being in an unoccupied condition for more
p.592than three times the length of time for a full ride, the escalator should slow down.
p.592c) Approach the escalator entrance while in an unoccupied condition from multiple
p.592angles to ensure passenger detection cannot be bypassed.
p.592d) Verify the slow speed setting is 10 ft/min.
p.592e) Verify the full speed setting is below 100 ft/min.
p.592f) Verify the acceleration and deceleration of speed changes. The acceleration shall
p.592not exceed 1 ft/sec sq.
p.592g) Approach the escalator in an unoccupied condition at an average walking pace.
p.592The escalator should reach full speed before boarding.
p.592h) Approach the escalator in an unoccupied condition at an average walking pace in
p.592the wrong direction. An alarm should signal to alert that the pedestrian is approaching in the wrong direction.
p.592Lab Exhaust Ventilation System Acceptance Test
p.592NA7.16.1 Construction Inspection for VAV Lab Exhaust System with Occupancy Control
p.592Verify and document the following prior to functional testing:
p.592(a) Test and balance report confirms correspondence between design values on plans
p.592and specification and measure values to within 10%:
p.5921. Area and volume of each lab space.
p.5922. Design airflow rate of lab space, (cfm).
p.5923. Occupied minimum airflow rate of each lab space, (cfm).
p.592Appendix NA7 – Installation and Acceptance Requirements for Nonresidential Buildings and Covered Processes