NA6.1 Scope

p.5132025 Nonresidential Appendices

Figure on PDF page 513
Text in this figure

Nonresidential Appendix NA6

p.513 Needs alt text review

p.513Appendix NA6 – Alternate Default Fenestration Procedure to Calculate Thermal Performance

p.513Scope

Figure on PDF page 513
p.513 Needs alt text review

p.513This procedure provides for non-rated site-built skylights, and alterations to fenestration (i.e., repairs or replacement of glass), with an option to comply with the Energy Standards. The Center of Glass (COG) values are required to be used in Equation NA6­ 1, NA6-2 and NA6-3 and shall be determined by the manufacturers in accordance with NFRC procedures. A copy of the manufacturer cut sheets or data sheet shall be provided identifying the COG values as an attachment with the Fenestration Certificate of Compliance.

p.513(a) NONRESIDENTIAL AND MULTIFAMILY BUILDINGS FOUR STORIES OR

p.513GREATER

p.513For Nonresidential cases, the Alternative Default Fenestration Procedure option is available for up to 200 ft2 of site-built skylight area, and alterations to vertical fenestration. The manufacturer cut sheet or data sheet shall be used to identify the COG values for the U-factor, Solar Heat Gain Coefficient (SHGCC) and Visible Transmittance (VTC). If unable to determine center of glass information, the alternative Energy Commissions Default Tables in Section 110.6 of the Energy Standards must be used to determine the appropriate fenestration default values. The values listed in Table 110.6-A for U-factors and Table 110.6-B for SHGC values are whole fenestration product values. Since there is no default Visible Transmittance value available, the alternative is VTC =1.0; this will be used to determine the total fenestration product, VTT, which includes the glass and frame of the fenestration.

p.513For Nonresidential, the altered fenestration (other than a repair) shall meet the values listed in Table 141.0-A unless the altered glass area meets the Exception to Section 141.0(b)2A in the Energy Standards. If the altered fenestration or glass alone is not rated by NFRC then the Alternate Default Fenestration Procedure can be used.

p.513(b) RESIDENTIAL AND MULTIFAMILY BUILDINGS THREE STORIES OR LESS

p.513For Residential cases, the Alternate Default Fenestration Procedure option is available only when nonrated site-built fenestration is being installed in a residential dwelling. For Residential site-built fenestration up to 250 ft2 in area or 5% times the conditioned floor area (CFA), whichever is greater shall meet Sections §110.6(a)2 and §110.6(a)3.

p.513The Alternate Default Fenestration calculated values are typically less efficient than those listed in the Prescriptive Approach in Table 150.1-A and Table 150.1-B of the Energy Standards. The Visible Transmittance (VT) value is not required to

p.513Appendix NA6– Alternate Default Fenestration Procedure to Calculate Thermal Performance