p.273Performance Data Reporting
p.274Design documentation shall specify the operating conditions at which the primary heat pump water heater can supply hot water at design outlet water temperature without engaging auxiliary heating mechanism.
p.273The following performance specifications shall be submitted to the Energy Commission:
p.273a) Water heater input power;
p.273b) Water heater output capacity; and
p.273c) Water heater COP.
p.273The performance data shall be provided at the following conditions:
p.273d) Inlet ambient air temperature: Maximum, minimum, and two midpoint
p.273temperatures of the manufacturer specified operating range.
p.273e) Inlet water temperature: Maximum, minimum, and two midpoint
p.273temperatures of the manufacturer specified operating range.
p.273f) Outlet water temperature: Maximum, midpoint, and minimum of outlet water
p.273(setpoint) temperatures of the manufacturer specified operating range.
p.273For conditions where defrost strategies operate, reported data shall include at least one complete defrost cycle, or alternatively, for each model submitted for approval, provide a description of the defrost strategy including method, cycle length, and process.
p.273Basic Model Test Condition The Central HPWH basic model shall be tested at the following conditions:
p.273(a) Inlet ambient air temperature: If the minimum operating temperature is above
p.273400F, the following three test conditions are required: the DOE test Procedure condition, the minimum, and one midpoint temperatures within the manufacturer specified operating range. If the minimum operating temperature limit is below 400F, the following four test conditions are required: the DOE test procedure condition, the minimum, and two midpoint temperatures within the manufacturer specified operating range.
p.273(b) Two inlet water temperatures: maximum and minimum within the manufacturer
p.273specified operating range.
p.273(c) Two outlet water temperatures: Maximum and minimum outlet water (setpoint)
p.273temperatures within the manufacturer specified operating range.
p.273JA14.4 Design Condition Documentation Requirements The Central HPWH system shall be capable of supplying hot water at design outlet water temperature under specified operating ranges for:
p.273a) Minimum and maximum ambient air temperature;
p.273b) Minimum and maximum cold-water temperature;
p.273c) Minimum and maximum building demand at design draw and recovery
p.273conditions and duration; and
p.273d) Recirculation loop heat loss.
p.273Appendix JA14 – Qualification Requirements for Central Heat Pump Water Heater Systemsp.274
p.274Appendix JA14 – Qualification Requirements for Central Heat Pump Water Heater Systems