NA7.13.2.2 Functional Testing

p.5912025 Nonresidential Appendices (f) Visual trending display of each recorded point, load, and specific efficiency.

p.591NA7.13.2.2 Functional Testing

p.591Verify and document the following monitoring system capabilities:

p.591(a) Data observed during test is being recorded to a log file that can be opened and

p.591viewed to see trend of airflow, power, and specific efficiency in at least 5 minute intervals.

p.591(d) Airflow and compressor power data vary with loading and unloading of the

p.591compressor within typical performance expectations. Measurements should be observed across various loading, whether manually varied in response to actual operational loads.

p.591Elevator Lighting and Ventilation Controls

Figure on PDF page 591
p.591 Needs alt text review

p.591NA7.14.1 Construction Inspection

p.591Verify and document the following prior to functional testing:

p.591a) The occupancy sensor has been located to minimize false signals, and the

p.591elevator cab does not have any obstructions that could adversely affect the sensor’s performance.

p.591b) For PIR sensors, the sensor pattern does not enter into the elevator lobby.

p.591c) For ultrasonic sensors, the sensor does not emit audible sound.

p.591Note that some elevators are able to use weight sensors to provide occupancy sensing. In this case, document that the elevator uses weight sensing to provide occupant sensing and proceed to the functional test.

p.591NA7.14.2 Functional Testing

p.591For each elevator cab being tested, confirm the following:

p.591a) Verify that the lighting and ventilation controlled inside the elevator cab turn off

p.591after 15 minutes from the start of an unoccupied condition.

p.591b) Verify that the signal sensitivity is adequate to achieve desired control. The sensor

p.591should not detect motion in the elevator lobby.

p.591c) Verify that lighting and ventilation immediately turn "on" when an unoccupied

p.591condition becomes occupied.

p.591d) Verify that the lighting and ventilation will not shut off when occupied. Stand in the

p.591elevator with the door closed and wait 15 minutes to confirm that the lighting and ventilation remain on.

p.591Appendix NA7 – Installation and Acceptance Requirements for Nonresidential Buildings and Covered Processes