p.2792025 Joint Appendices
Text in this figure
Joint Appendix JA17
p.279Appendix JA17 – Qualification Requirements for Ventilation System Fault Indication Displays (FIDs)
p.279JA17.1 Introduction
p.279Joint Appendix JA17 provides the technical specifications for fault indication display devices (FIDs) that provide visual and/or audible indications that heat/energy recover ventilation systems (HRV/ERV) systems, and balanced or supply-only ventilation systems that require an FID according to Section 150.0(o)Civa1 and Section 160.2(b)2Axia1, maintain their rated airflow and fan efficacy for the life of the equipment.
p.279JA17.2 Fault Indication Categories
p.279Fault indication devices shall respond to the following categories:
p.279(a) Filter check or maintenance, either based on performance or a predetermined
p.279schedule. (b) Low supply airflow. (c) Low exhaust airflow (balanced systems only). (d) Sensor failure for sensors that assist in monitoring or controlling airflow regulation,
p.279frost control, supply air tempering, and economizing.
p.279JA17.3 Fault Indication Means
p.279Fault indication shall use one or more of the following means:
p.279(a) A visual display that is readily accessible to occupants of the dwelling unit. (b) An electronic application. (c) An audible alarm accompanied by a visual display.
p.279JA17.4 Instrumentation and Reporting
p.279Instrumentation shall measure and report the following: (a) Airflow. (b) Fan power.
p.279Appendix JA17 – Qualification Requirements for Ventilation System Fault Indication Displays (FIDs)