p.5892025 Nonresidential Appendices NA7.12.2 Functional Testing
p.589Conduct the following tests with garage ventilation system operating in occupied mode and with actual garage CO concentration well below setpoint.
p.589Step 1: With all sensors active and all sensors reading below 25 ppm, observe that fans
p.589are at minimum speed and fan motor demand is no more than 30 percent of design wattage.
p.589Step 2: Apply CO span gas with a concentration of 30 ppm, and a concentration accuracy
p.589of +/- 2%, one by one to 50% of the sensors but no more than 10 sensors per garage and to at least one sensor per proximity zone. For each sensor tested observe:
p.589(a) CO reading is between 25 and 35 ppm.
p.589(b) Ventilation system ramps to full speed when span gas is applied.
p.589(c) Ventilation system ramps to minimum speed when span gas is removed.
p.589Step 3: Temporarily override the programmed sensor calibration/replacement period to 5
p.589minutes.
p.589(d) Wait 5 minutes and observe that fans ramp to full speed and an alarm is received
p.589by the facility operators. Restore calibration/replacement period.
p.589Step 4: Temporarily place the system in unoccupied mode and override the programmed
p.589unoccupied sensor alarm differential from 30% for 4 hours to 1% for 5 minutes. Wait 5 minutes and observe that fans ramp to full speed and an alarm is received by the facility operators. Restore programming.
p.589Step 5: Temporarily override the programmed occupied sensor proximity zone alarm
p.589differential from 30% for 4 hours to 1% for 5 minutes. Wait 5 minutes and observe that fans ramp to full speed and an alarm is received by the facility operators. Restore programming.
p.589Compressed Air System Acceptance Tests
p.589NA7.13.1 Compressed Air Control System
p.589Acceptance tests for compressed air controls in accordance with Section 120.6(e)2.
p.589NA7.13.1.1 Construction Inspection
p.589Verify and document the following prior to functional testing:
p.589(a) Size (hp), rated capacity (acfm), and control type of each air compressor.
p.589(b) Total system capacity (the sum of the individual capacities).
p.589(c) System operating pressure.
p.589(d) Compressor(s) designated as trim compressors.
p.589(e) Method for observing and recording the states of each compressor in the system,
p.589which shall include at least the following states:
p.589Appendix NA7 – Installation and Acceptance Requirements for Nonresidential Buildings and Covered Processes