NA2.3.1 Purpose and Scope

p.4962025 Nonresidential Appendices 5. Determining compliance.

p.496a. If the value determined for SRE by one or both of the alternatives in step 4 for

p.496the installed system is greater than or equal to the SRE required for compliance, then the system complies with the sensible recovery efficiency rating requirement. Otherwise, the system does not comply.

p.496b. If the value determined for fan efficacy (W/cfm) by one or both of the

p.496alternatives in step 3 for the installed system is less than or equal to the fan efficacy required for compliance, then the system complies with the fan efficacy rating requirement. Otherwise, the system does not comply.

p.496c. If compliance with both fan efficacy and sensible recovery efficiency ratings are

p.496required, then both ratings shall comply at the same Net Airflow (cfm), otherwise the system does not comply.

p.496d. If the system is not listed in the HVI or other CEC-approved directory, then the

p.496system does not comply.

p.496Field Verification and Diagnostic Testing of Multifamily Dwelling Unit Compartmentalization

Figure on PDF page 496
p.496 Needs alt text review

p.496NA2.3.1 Purpose and Scope

p.496The purpose of this test procedure is to measure and determine compliance with multifamily dwelling unit compartmentalization requirements .

p.496The measurement procedure shall be based on the specifications of Residential Energy Services Network's (RESNET) Standard for Testing Airtightness of Building, Dwelling Unit, and Sleeping Unit Enclosures; Airtightness of Heating and Cooling Air Distribution Systems; and Airflow of Mechanical Ventilation Systems (ANSI/RESNET/ICC 380-2019) (RESNET 380) as further specified in Subsections NA2.3.2, NA2.3.3, NA2.3.4 below.

p.496This enclosure leakage procedure is applicable to Multifamily dwelling unit enclosures.

p.496NA2.3.2 Instrument Specifications

p.496The instrumentation for the enclosure leakage measurements shall conform to the specifications in RESNET 380 Section 4.1.

p.496NA2.3.3 Enclosure Leakage Measurement Procedures

p.496The enclosure leakage measurement procedure shall conform to the following specifications:

p.4961) The procedure for preparation of the building or dwelling unit for testing shall conform to the applicable requirements in RESNET 380 Section 4.2.

p.4962) The procedure for installation of the test apparatus, and preparations for measurement shall conform to the applicable requirements in RESNET 380 Section 4.3.

p.496Appendix NA2 – Nonresidential Field Verification and Diagnostic Test Procedures