p.4622025 Residential Appendices (b) The installation configuration (e.g., equal flow, unequal flow to the water heater, or
p.462unequal flow to the showers) and the percent of served shower fixtures shall match the compliance documents.
p.462(c) For water heating system serving a single dwelling, the DWHR system shall, at the
p.462minimum, recover heat from the master bathroom shower and must at least transfer that heat either back to all the respective showers or the water heater.
p.462(d) For central water heating system serving multiple dwellings, the DWHR system shall, at
p.462the minimum, recover heat from half the showers located above the first floor and must at least transfer that heat either back to all the respective showers or the water heater.
p.462(e) The DWHR unit(s) shall be installed within 1 degrees of the rated slope. Sloped DWHR
p.462shall have a minimum lengthwise slope of 1 degree. The lateral level tolerance shall be within plus or minus 1 degree.
p.462(f) The installation shall comply with any applicable California Plumbing Code requirements.
p.462RA4.5 Other Measures
p.462RA4.5.1 Controlled Ventilation Crawlspace (CVC)
p.462Drainage. Proper enforcement of site engineering and drainage, and emphasis on the importance of proper landscaping techniques in maintaining adequate site drainage, is critical.
p.462Ground Water and Soils. Local ground water tables at maximum winter recharge elevation should be below the lowest excavated site foundation elevations. Sites that are well drained and that do not have surface water problems are generally good candidates for this stem-wall insulation strategy. However, the eligibility of this alternative insulating technique is entirely at the enforcement agency officials' discretion. Where disagreements exist, it is incumbent upon the applicant to provide sufficient proof that site drainage strategies (e.g., perimeter drainage techniques) will prevent potential problems.
p.462Ventilation. All crawl space vents must have automatic vent dampers to receive this credit. Automatic vent dampers must be shown on the building plans and installed. The dampers should be temperature actuated to be fully closed at approximately 40°F and fully open at approximately 70°F. Cross ventilation consisting of the required vent area reasonably distributed between opposing foundation walls is required.
p.462Foam Plastic Insulating Materials. Foam plastic insulating materials must be shown on the plans and installed when complying with the following requirements:
p.462Fire Safety—CBC Section 719. Products shall be protected as specified. Certain products have been approved for exposed use in under floor areas by testing and/or listing.
p.462Direct Earth Contact—Foam plastic insulation used for crawl-space insulation having direct earth contact shall be a closed cell water resistant material and meet the slab-edge insulation requirements for water absorption and water vapor transmission rate specified in the mandatory measures.