RA4.4.20 Solar Water Heating Systems

p.4612025 Residential Appendices 3. If the recirculation return temperature falls more than 5°F below the specified temperature during the draw period, then adjust MMV setup to ensure compliance.

p.461RA4.4.20 Solar Water Heating Systems

p.461Solar water-heating systems and/or collectors shall be certified and rated by the Solar Rating and Certification Corporation (SRCC), the International Association of Plumbing and Mechanical Officials, Research and Testing (IAPMO R&T), or by a listing agency that is approved by the Executive Director.

p.461To use collectors with the SRCC OG-100 certification and rating, the installed system shall meet the following eligibility criteria:

p.461(a) Include all of the features modeled and generated in the Commission approved solar

p.461savings fraction calculation.

p.461(b) The collectors shall be installed according to manufacturer’s instructions.

p.461(c) The collectors shall be located in a position that is not shaded by adjacent buildings or

p.461trees between 9:00 AM and 3:00 PM (solar time) on December 21.

p.461To use a solar water-heating system with the SRCC OG-300 certification and rating, the installed system shall meet the following eligibility criteria:

p.461(a) The collectors shall face within 35 degrees of south and be tilted at a slope of at least

p.4613:12.

p.461(b) The system shall be installed in the exact configuration for which it was rated. The

p.461system shall have the same collectors, pumps, controls, storage tank and backup water heater fuel type as the rated condition.

p.461(c) The system shall be installed according to manufacturer’s instructions.

p.461(d) The collectors shall be located in a position that is not shaded by adjacent buildings or

p.461trees between 9:00 AM and 3:00 PM (solar time) on December 21.

p.461RA4.4.21 Verified Drain Water Heat Recovery System

p.461An ECC-rater inspection is required to obtain this credit. All DWHR unit(s) shall be certified to the Energy Commission according to the following requirements:

p.461(a) Vertical DWHR unit(s) shall be compliant with CSA B55.2 and tested and labeled in

p.461accordance with CSA B55.1 or IAPMO IGC 346-2017. Sloped DWHR unit(s) shall be compliant with IAPMO PS 92 and tested and labeled with IAPMO IGC 346-2017.

p.461(b) The DWHR unit(s) shall have a minimum rated effectiveness of 42 percent.

p.461The ECC-rater shall verify that:

p.461(a) The make, model, and CSA B55.1 or IAPMO IGC 346-2017 rated effectiveness of the

p.461DWHR unit(s) shall match the compliance documents. The DWHR unit(s) shall also be verified as a model certified to the Energy Commission as qualified for credit as a DWHR unit(s).

p.461– Eligibility Criteria for Energy Efficiency Measures