JA5.3 HVAC System Interface

p.175programmed or occupant selected prevailing setpoint temperature upon initiation of the price event or Demand Response Period.

p.1754. By default, thermostats shall not be remotely set above 90°F or below 50°F. Occupants shall have the ability to redefine these limits. This measure protects occupant premises from extreme temperatures that might otherwise be imposed by event responses, should the occupant already have a very high or low temperature setpoint in effect.

p.175The occupant may still override or change the setpoint during all price events and Demand Response Periods. Price signal response and Demand Responsive Control only modify the operating range of the thermostat. They do not otherwise affect the operation and use of features provided by the manufacturer’s design.

p.175JA5.3 HVAC System Interface

p.176(This page intentionally left blank.)

p.175HVAC wiring terminal designations shall be clearly labeled.

p.175Appendix JA5 – Technical Specifications for Demand Responsive Thermostatsp.176